Document qaRg4j1YnEYqQnzyG7mkgaaNk

ANSI A21.51-1976 (AWWA C151-76) Revision of A21.51-1971 (AWWA C151--71) AMERICAN NATIONAL STANDARD for DUCTILE-IRON PIPE, CENTRIFUGALLY CAST IN METAL MOLDS OR SAND-LINED MOLDS, FOR WATER OR OTHER LIQUIDS Secretariats AMERICAN GAS ASSOCIATION AMERICAN WATER WORKS ASSOCIATION NEW ENGLAND WATER WORKS ASSOCIATION Revised edition approved by American National Standards Institute, Inc., Aug. 4, 1976 PUBLISHED BY AMERICAN WATER WORKS ASSOCIATION 6666 West Quincy Avenue. Denver, Colorado 80235 CTD014618 American National Standard An American National Standard implies a consensus of those substantially con cerned with its scope and provisions. An American National Standard is intended as a guide to aid the manufacturer, the consumer, and the general public. The existence of an American National Standard does not in any respect preclude anyone, whether he has approved the standard or not, from manufacturing, marketing, pur chasing, or using products, processes, or procedures not conforming to the standard. American National Standards are subject to periodic review and users are cautioned to obtain the latest editions. Producers of goods made in conformity with an Amer ican National Standard are encouraged to state on their own responsibility in adver tising, promotion material, or qp tags or labels, that the goods are produced in con formity .with,ppr^cjgiar American National Standards. CAUTION'N*6t|[Ei iSmfcAmeriAn National Standard may Tie revised or with drawn at any time. The procedures of the American National Standards Institute require that action be taken to reaffirm, revise, or withdraw this standard no later than 5 yr from the date of publication. Purchasers of American National Standards may receive current information on all standards by calling or writing the American National Standards Institute, 1430 Broadway, New York, N.Y. 10018, (212) 868-1220. C Copyright 1976 by the American Water Works Assn. Printed in US ii j CTD014619 Committee Personnel Subcommittee 1, Pipe, which reviewed this standard, had the following per sonnel at that time: Edward C. Sears, Chairman Walter Amory, Vice-Chairman User Members Robert S. Bryant Frank E. Dolson George F. Keenan Leonard Orlando Jr. John E. Perry Producer Members Alfred F. Case W. D. Goode Thouas D. Holmes Harold Kennedy Jr. W. Harry Smith Sidney P. Teague Standards Committee A21, Cast-Iron Pipe and Fittings, which reviewed and approved this standard, had the following personnel at the time of approval: Lloyd W. Weller, Chairman Edward C. Sears, Vice-Chairman James B. Ramsey, Secretary Organization Represented Q American Gas Association American Society of Civil Engineers American Society of Mechanical Engineers American Society for Testing and Materials American Water Works Association r Cast Iron Pipe Research Association Individual Producer Manufacturers' Standardization Society of the Valve and Fittings Industry New England Water Works Association Naval Facilities Engineering Command Underwriters' Laboratories, Inc. Canadian Standards Association Name of Representative Leonard Orlando Jr. Kenneth W. Henderson James S. Vanick H. M. Cobb* Arnold M. Tinkey Lloyd W. Weller Thomas D. Holmes Harold Kennedy Jr. Edward C. Sears W. Harry Smith Alfred F. Case Abraham Fenster Walter Amory Stanley C. Baker John E. Perry W. F. Semenchuk f * Alternate t Liaison representative without vote J 111 CTD014620 Table of Contents SEC. PACE Foreword ................................... v Standard SI--1 Scope ............................................ 51--2 Definitions .................................... 51-3 General Requirements ................ 51-4 Inspection and Certification by Manufacturer ...................... 51-5 Inspection by Purchaser ....... 51-6 Delivery and Acceptance....... 51-7 Tolerances or Permitted Variations ................................. 51-8 Coatings and Linings ................... 51-9 Hydrostatic Test.....................' 51-10 Marking Pipe................................ 51-11 Weighing Pipe.............................. 51-12 Acceptance Tests.......................... 51-13 Additional Control Tests by Manufacturer ............................ 51-14 Foundry Records.......................... 51-15 Additional Tests Required by Purchaser .................................. 51-16 Defective Specimens and Retests 51-17 Rejection of Pipe.......................... 51-18 Determining Rejection ................. 1 1 1 2 2 3 3 3 3 3 6 6 6 6 6 Figures 1. Tensile-Test Specimen...................... 4 sec. pace 2. Impact Test Specimen....................... 3 3. Standard Laying Conditions ............ 11 Tables 51.1 Standard Thickness for Earth Load Plus Truck Load........................ 51.2 Standard Thickness for Internal Pressure ....................................... 51.3 Rated Working Pressure and Maximum Depth of Cover......... 51.4 Standard Dimensions and Weights of Push-On-Joint Ductile-Iron Pipe ............................................... 51.5 Standard Dimensions and Weights of Mechanical-Joint Ductile-Iron Pipe ............................................... A.l Pipe Thicknesses Required for Different Tap Sizes as per ANSI B2.1 for Standard Taper Pipe Threads With Two, Three, and Four Full Threads....................... A.2 Pipe Thicknesses Required for Different Tap Sizes as per AWWA C800 for Standard Corporation Stop Threads With Two, Three, and Four Full Threads ............................... 7 12 13 15 18 ") 20 )21 Appendix 20 tv CTD0U621 Foreword This foreword is for information only and is not a part of ANSI A21.S1 {AWWA C151). American National Standards Com mittee A21 on Cast-Iron Pipe and Fit tings was organized in 1926 under the sponsorship of the American Gas As sociation, The American Society for Testing and Materials, the American Water Works Association, and the New England Water Works Associa tion. Since 1972, the co-secretariats have been A.G.A., AWWA, and NEWWA, with AWWA serving as the administrative secretariat. The present scope of Committee A21 ac tivity is Standardization of specifications for cast-iron and ductile-iron pressure pipe for gas, water and other liquids, and fittings for use with such pipe. These specifications to include design, dimensions, materials, coatings, lin ings, joints, accessories and methods of in spection and test The work of Committee A21 is con ducted by subcommittees. The direc tive to Subcommittee 1--Pipe is that The scope of the subcommittee activity shall include the periodic review of all current A21 standards for pipe, the preparation of revisions and new standards when needed, as well as other matters pertaining to pipe standards. The first edition of A21.51, the stan dard for ductile-iron pipe for water and other liquids, was issued in 1965, and a revision was issued in 1971. Subcom mittee 1 reviewed the 1971 edition and submitted a proposed revision to Amer ican National Standards Committee A21 in 1975. Major Revisions 1. An additional minus tolerance of 0.02 in. is permitted along the barrel of the pipe for a distance not to ex ceed 12 in. The weight tolerance permitted for any single pipe is 6 per cent for pipe 12 in. or smaller and 5 per cent for pipe larger than 12 in. 2. The tables include data for the five standard laying conditions covered in A21.50-1976. Types 1, 2, and 3 replace A, B, and S, respectively, in A21.51-1971. Types 3 and 4 have been added to provide a wider selec tion of laying conditions. 3. The pipe thickness selection tables have been revised to reflect the changes in the 1976 edition of A21.50, the standard for thickness design of ductile-iron pipe. 4. The standard thickness classes have been renumbered. Class 1 becomes Class 51; Class 2 becomes Class 52; and so on. Class 50 has been added for 6-54-in. pipe, and Class 51 has been added for 3-12-in. pipe. 5. Pipe weights have been adjusted for 3-24-in. push-on joint pipe to reflect lighter bell weights based on pushon joint bells, which are more com patible with the barrel thicknesses of ductile-iron pipe. 6. A table (Table 3) has been added to show rated working pressure and maximum depth of cover of the standard laying conditions and stan dard thickness classes. Options This standard includes certain op tions that, if desired, must be specified on the purchase order. Also, a number of items must be specified to describe completely the pipe required. The fol lowing summarizes the details and V available options and lists the sections of the standard where they can be found. 1. Size, joint type, thickness or class, and laying length (Tables). 2. a. Special joints (Sec. 51-3.1). b. Specifying ductile-iron gland, if required (Sec. 51-3.1). 3. Certification by manufacturer (Sec. 51-4.2). 4. Inspection by purchaser (Sec. 51-5). 5. a. No requirement for outside coat ing (Sec. 51-8.1). b. Cement lining (Sec. 51-8.2). Ex perience has indicated that bitu minous inside coating is not com plete protection against loss in pipe capacity caused by tubercu- lation. Cement linings are recommended for most waters. c. No requirement for inside coat ing (Sec. 51-8.3). d. Special coatings and linings (Sec. 51-8.4). 6. Special marking on pipe (Sec. 51- 10); 7. Written transcripts of foundry rec ords (Sec. 51-14). 8. Special tests (Sec. 51-15). k f > VI CTD014623 % ANSI A21.51-1976 (AWWA C1SI-76) Revision of A21.51-1971 (AWWA Cl51-71) American National Standard for Ductile-Iron Pipe, Centrifugally Cast in Metal Molds or Sand-Lined Molds, for Water or Other Liquids Sec. 51-1--Scope This standard covers 3-in. through 54-in. ductile-iron pipe centrifugally cast in metal molds or sand-lined molds for water or other liquids with push-on joints or mechanical joints. This standard may be used for pipe with such other types of joints as may be agreed upon at the time of purchase. Sec. 51-2--Definitions Under this standard, the following definitions shall apply: 51-2.1 Purchaser. The party en tering into a contract or agreement to purchase pipe according to this stan dard. 51-2.2 Manufacturer. The party that produces the pipe. 51-2.3 Inspector. The representa tive of the purchaser, authorized to in spect on behalf of the purchaser to de termine whether or not the pipe meets this standard. 51-2.4 Ductile iron. A cast ferrous material in which a major part of the carbon content occurs as free carbon in nodular or spheroidal form. 51-2.5 Mechanical joint. The gas keted and bolted joint as detailed in ANSI A21.ll (AWWA Clll) of lat est revision. 51-2.6 Push-on joint. The single rubber-gasket joint as described in ANSI A21.ll (AWWA Clll) of lat est revision. Sec. 51-3--General Requirements 51-3.1 Pipe with mechanical joints or push-on joints shall conform to the applicable dimensions and weights shown in the tables in this standard and to the applicable requirements of ANSI A21.ll (AWWA Clll) of lat est revision. Unless otherwise speci fied, the mechanical-joint glands shall be cast iron in accordance with ANSI A21.ll of latest revision and bolts shall conform to the requirements of the same standard. Pipe with other types of joints shall comply with the joint dimensions and weights agreed upon at the time of purchase but in all other respects shall fulfill the require ments of this standard. 51-3.2 The nominal laying length of the pipe shall be as shown in the tables. A maximum of 20 per cent of the total number of pipe of each size specified in an order may be furnished. by as much as 24 in. shorter than the 1 CTD014624 2 AMERICAN NATIONAL STANDARD nominal laying length, and an addi tional 10 per cent may be furnished by as much as 6 in. shorter than nominal laying length. Sec. 51-4--Inspection and Certifi cation by Manufacturer 51-4.1 The manufacturer shall es tablish the necessary quality-control and inspection practice to ensure com pliance with this standard. 51-4.2 The manufacturer shall, if required on the purchase order, furnish a sworn statement that the inspection and all of the specified tests have been made and the results thereof comply with the requirements of this standard. 51-4.3 All pipe shall be clean and sound without defects that could impair service. Repairing of defects by weld ing or other methods shall not be al lowed if such repairs could adversely affect the serviceability of the pipe or its capability to meet strength require ments of this standard. Sec. 51-5--Inspection by Purchaser 51-5.1 If the purchaser desires to inspect pipe at the manufacturer's plant, the purchaser shall so specify on the purchase order, stating the condi tions (such as time and the extent of inspection) under which the inspection shall be made. 51-5.2 The inspector shall have free access to those parts of the manu facturer's plant that are necessary to ensure compliance with this standard. The manufacturer shall make available for the inspector's use such gages as are necessary for inspection. The manufacturer shall provide the in spector with assistance as necessary for handling of pipe. ply with this standard. Pipe and ac cessories not complying with this standard shall be replaced by the man ufacturer at the agreed point of de livery. The manufacturer shall not be liable for shortages or damaged pipe after acceptance at the agreed point of delivery, except as recorded on the de livery receipt or similar document by the carrier's agent. Sec. 51-7--Tolerances or Permitted Variations 51-7.1 Dimensions. The spigot end, bell, and socket of the pipe and the accessories shall be gaged with suit able gages at sufficiently frequent inter vals to ensure that the dimensions com ply with the requirements of this stan dard. The smallest inside diameter of the sockets and the outside of the spigot ends shall be tested with circular gages. Other socket dimensions shall be gaged as may be appropriate. 51-7.2 Thickness. Minus thickness tolerances of pipe and bell shall not ex- ceed the following: Size in. 3-8 10-12 14-42 48 54 Minus Tolerance in. 0.05 0.06 0.07 0.08 0.09 An additional minus tolerance of 0.02 in. shall be permitted along the barrel of the pipe for a distance not to exceed 12 in. 51-7.3 Weight. The weight of any single pipe shall not be less than the tabulated weight by more than 6 per cent for pipe 12 in. or smaller in diam eter, or by more than 5 per cent for pipe larger than 12 in. in diameter. Sec. 51-6--Delivery and Acceptance Sec. 51-8--Coatings and Linings All pipe and accessories shall com 51-8.1 Outside coating. The out- ) I GTD014625 DUCTILE-IRON PIPE 3 side coating for use under normal con ditions shall be a bituminous coating approximately 1 mil thick. The coat ing shall be applied to the outside of all pipe, unless otherwise specified. The finished coating shall be continu ous, smooth, neither brittle when cold nor sticky when exposed to the sun, and shall be strongly adherent to the pipe. 51-8.2 Cement-mortar linings. Ce ment linings shall be in accordance with ANSI A21.4 (AWWA C104) of latest revision. If desired by the purchaser, cement linings shall be spec ified in the invitation for bids and on the purchase order. 51--8.3 Inside coating. Unless other wise specified, the inside coating for pipe that is not cement-lined shall be a bituminous material as thick as prac ticable (at least 1 mil) which conforms to all appropriate requirements for seal coat in ANSI A21.4 of latest revision. 51-8.4 Special coatings and linings. For special conditions, other types of coatings and linings may be available. Such special coatings and linings shall be specified in the invitation for bids and on the purchase order. Sec. 51-9--Hydrostatic Test Each pipe shall be subjected to a hydrostatic test of not less than 500 psi. This test may be made either before or after the outside coating and inside coating have been applied, but shall be made before the application of cement lining or of a special lining. The pipe shall be under the full test pressure for at least 10 s. Suitable controls and recording devices shall be provided so that the test pressure and duration may be adequately ascer tained. Any pipe that leaks or does not withstand the test pressure shall be rejected. In addition to the hydrostatic test before application of a cement lining or special lining, the pipe may be retested, at the manufacturer's option, after ap plication of such lining. Sec. 51-10--Marking Pipe The weight, class or nominal thick ness, and casting period shall be shown on each pipe. The manufacturer's mark, the year in which the pipe was produced, and the letters "DI" or "DUCTILE" shall be cast or stamped on the pipe. When specified on the purchase order, initials not exceeding four in number shall be cast or stamped on the pipe. All required markings shall be clear and legible, and all cast marks shall be on or near the bell. All letters and numerals on pipe sizes 14 in. and larger shall be not less than in. in height. Sec. 51-11--Weighing Pipe Each pipe shall be weighed before the application of any lining or coating other than the bituminous coating and the weight shown on the outside or in side of the bell or spigot end. Sec. 51-12--Acceptance Teste The standard acceptance tests for the physical characteristics of the pipe shall be as follows: 51-12.1 Tensile test. A tensile test specimen shall be cut longitudinally from the midsection of the pipe wall. This specimen shall be machined and tested in accordance with Fig. 1 and ASTM E8-69, "Tension Testing of Metallic Materials." The yield strength shall be determined by the 0.2 per cent offset, halt-of-pointer, or extension-un der-load method. If check tests areto be made, the 0.2 per cent offset CTD014626 4 AMERICAN NATIONAL STANDARD The tensile-test specimen dimensions are given in the following table: Standard Specimen 0.500 in. round Dimension Small-Size Specimens Proportional to Standard 0.350 in. round 0.2501 n. round 0.175 in. round 0.125 in. round Dimensions--in T* 0.71 and 0.50-0.70 0.35-0.49 0.25-0.34 0.18-0.24 greater G 2.000 0.005 1.400 0.005 1.000 0.005 0.700 0.005 0.500 =t 0.005 D 0.500 0.010 0.350 0.007 0.250 0.005 0.175 0.005 0.125 0.005 R f (min.) 1 (min.) A (min.) A (min.) A (min.) A 21 (min.) 11 (min.) 11 (min.) 1 (min.) | (min.) Thickness of the section from the wall of the pipe from which the tensile specimen is to be machined. Note. /. The reduced section A may have a gradual taper from the ends toward the center with the ends not more than 0.005 in. larger in diameter than the center on the standard specimen and not more than 0.003 in. larger in diameter than the center on the small size specimens. Note. 2. If desired, on the small size specimens the length of the reduced section may be increased to accommodate an extensometer. However, reference marks for the measurement of elongation should nevertheless be spaced at the indicated gage length C. .Vole. 3. The gage length and fillets shall be as shown, but the ends may be of any form to fit the ho'ders of the testing machine in such a way that the load shall be axial. If the ends are to be held in grips it is desirable, if possible, to make the length of the grip section great enough to allow the specimen to extend into the grips a distarice equal to two thirds or more of the length of the grips. method shall be used. Alt specimens shall be tested at room temperature [70F 10 (21C6)]. 51-12.1.1 Acceptance values. The acceptance values for test specimens shall be as follows: Grade of iron: 60-42-10 1. Minimum tensile strength: 60 000 psi. 2. Minimum yield strength: 42 000 psi. 3. Minimum elongation: 10 per cent. 51-12.2 Impact test. Tests shall be made in accordance with ASTM E23-72 "Notched Charpy Tests," ex cept that specimens shall be 0.500 in. by full thickness of pipe wall. The notched impact test specimen shall be in accordance with Fig. 2. If the pipe v/all thickness exceeds 0.40 in., the im pact specimen may be machined to a nominal thickness of 0.40 in. In all tests, impact values are to be corrected to 0.40-in. wall thickness by calcula tions as follows: Impact value (corrected) 0.40 = ---- X impact value (actual) in which t is the thickness of the speci men in inches (wall thickness of pipe). CTD014627 DUCTILE-IRON PIPE 5 Fig. 2. Impact Test Specimen In Diagrams (a) and (b) the symbol t is jor the pipe-wall thickness. The Charpy test machine anvil shall not be moved to compensate for the variation of cross section dimensions of the test specimen. 51-12.2.1 Acceptance value. The corrected acceptance value for notched impact test specimens shall be a mini mum of 7 ft-lb for tests conducted at 70 F 10 (21C6). 51-12.3 Sampling. At least one ten sile and impact sample shall be taken during each casting period of approxi mately 3 hr. 'Samples shall be selected to represent extremes of pipe diameters and thicknesses properly. Sec. 51-13--Additional Control Tests by Manufacturer Low-temperature impact tests shall be made from at least one third of the test pipe specified in Sec. 51-12.3 to ensure compliance with a minimum corrected value of 3 ft-lb for tests con ducted at --40 F (--40C). Test speci mens shall be prepared and tested in accordance with Sec. 51-12.2. CTD014628 6 AMERICAN NATIONAL STANDARD In addition, the manufacturer shall conduct such other control tests as nec essary to assure continuing compliance with this standard. Sec. 51-14--Foundry Records The results of the acceptance tests (Sec. 51-12) and low-temperature im pact tests (Sec. 51-13) shall be re corded and retained for one year and shall be available to the purchaser at the foundry. Written transcripts shall be furnished, if specified on the pur chase order. Sec. 51-15--Additional Tests Re quired by Purchaser When tests other than those required in this standard are required by the purchaser, such tests shall be specified in the invitation for bids and on the purchase order. Sec. 51-16--Defective Specimens and Retests When any physical-test specimen shows defective machining or lack of continuity of metal, it shall be dis carded and replaced by another speci men. When any sound test specimen fails to meet the specified requirements, the pipe from which it was taken shall be rejected, and a retest may be made on two additional sound specimens from pipe cast in the same period as the specimen that failed. Both of the additional specimens shall meet the pre scribed tests to qualify the pipe pro duced in that period. Sec. 51-17--Rejection of Pipe If the results of any physical accept ance test fail to meet the requirements of Sec. 51-12 or Sec. 51-16, the pipe cast in the same period shall be re jected, except as provided in Sec. 5118. Sec. 51-18--Determining Refection The manufacturer may determine the amount of rejection by making similar additional tests of pipe of the same size until the rejected lot is bracketed, in order of manufacture, by an accept able test at each end of the interval in question. When pipe of one size is re jected from a casting period, the ac ceptability of pipe of different sizes from that same period may be estab lished by making the acceptance tests for these sizes as specified in Sec. 51-12. CTD014629 DUCTILE-IRON PIPE 7 TABLE 51.1 Standard Thickness for Earth Load Plus Truck Load* Laying Condition Depth Size of IK. Cover Type It Type 2f Type 3t 1 T ype 4t Type 5f ft. Thick- Thick Thick Thick Thick Thick Thick Thick Thick Thick ness ness ness ness ness ness ness ness ness ness in. Class in. Class in. Class in. Class in. Class 3 2.5 0.25 51 0.25 51 0.25 51 0.25 51 0.25 51 3 0.25 51 0.25 SI 0.25 51 0.25 SI 0.25 51 4 0.25 51 0.25 51 0.25 51 0.25 SI 0.25 51 5 0.25 51 0.25 51 0.25 51 0.25 51 0.25 51 6 0.25 St 0.25 51 0.25 51 0.25 51 0.25 51 7 0.25 51 0.25 51 0.25 51 0.25 51 0.25 51 8 0.25 51 0.25 51 0.25 51 0.25 SI 0.25 51 9 0.25 51 0.25 51 0.25 51 0.25 St 0.25 51 10 0.25 51 0.25 51 0.25 51 0.25 SI 0.25 5t 12 0.25 51 0.25 51 0.25 51 0.25 51 0.25 51 14 0.25 51 0.25 51 0.25 51 0.25 51 0.25 51 16 0.25 51 0.25 51 0.25 SI 0.25 51 0.25 51 20 0.25 51 0.25 51 0.25 51 0.25 SI 0.25 51 24 0.25 51 0.25 51 0.25 51 0.25 51 0.25 51 28 0.25 51 0.25 51 0.25 51 0.25 St 0.25 51 32 0.25 51 0.25 51 0.25 51 0.25 51 0.25 51 4 2.5 0.26 51 0.26 51 0.26 51 0.26 51 0.26 51 3 0.26 51 0.26 51 0.26 51 0.26 51 0.26 51 4 0.26 51 0.26 51 0.26 51 0.26 51 0.26 51 5 0.26 51 0.26 SI 0.26 51 0.26 51 0.26 51 6 0.26 51 0.26 51 0.26 51 0.26 51 0.26 51 7 0.26 51 0.26 51 0.26 51 0.26 51 0.26 51 8 0.26 51 0.26 51 0.26 51 0.26 51 0.26 SI 9 0.26 51 0.26 51 0.26 51 0.26 51 0.26 51 10 0.26 51 0.26 51 0.26 51 0.26 51 0.26 51 12 0.26 51 0.26 51 0.26 SI 0.26 51 0.26 51 14 0.26 51 0.26 51 0.26 51 0.26 51 0.26 51 16 0.26 SI 0.26 51 0.26 51 0.26 51 0.26 51 20 0.26 St 0.26 51 0.26 51 0.26 51 0.26 51 24 0.26 51 0.26 51 0.26 51 0.26 51 0.26 51 28 0.26 51 0.26 51 0.26 51 0.26 51 0.26 51 32 0.26 51 0.26 51 0.26 51 0.26 51 0.26 51 6 2.5 0.25 50 0.25 50 0.25 50 0.25 50 0.25 50 3 0.25 50 0.25 50 0.25 50 0.25 50 0.25 50 4 0.2S 50 0.25 50 0.25 50 0.25 50 0.25 50 5 0.25 50 0.25 50 0.25 50 0.25 50 0.25 SO 6 0.25 50 0.25 SO 0.25 SO 0.25 50 0.25 50 7 0.25 50 0.25 50 0.2S 50 0.25 50 0.25 50 8 0.25 50 0.25 50 0.25 50 0.25 SO 0.25 50 9 0.25 50 0.25 50 0.25 50 0.25 50 0.25 50 10 0.25 50 0.25 50 0.25 SO 0.25 50 0.25 50 12 0.25 50 0.25 50 0.25 50 0.25 50 0.2S 50 14 0.25 50 0.25 50 0.25 50 0.25 50 0.25 50 16 0.25 SO 0.25 50 0.25 50 0.25 SO 0.25 50 20 0.25 SO 0.25 50 0.25 50 0.25 50 0.25 50 24 0.25 50 0.25 50 0.25 50 0.25 50 0.25 50 28 0.25 50 0.25 50 0.25 50 0.25 50 0.25 50 32 0.25 50 0.25 SO 0.25 50 0.25 50 0.25 50 2.5 0.27 50 0.27 50 0.27 50 0.27 50 0.27 SO 3 0.27 SO 0.27 50 0.27 50 0.27 50 0.27 50 4 0.27 SO 0.27 50 0.27 50 0.27 50 0.27 50 S 0.27 50 0.27 50 0.27 50 0.27 50 0.27 50 6 0.27 50 0.27 50 0.27 50 0.27 50 0.27 SO 7 0.27 50 0.27 50 0.27 50 0.27 SO 0.27 50 8 0.27 50 0.27 SO 0.27 50 0.27 SO 0.27 50 9 0.27 50 0.27 50 0.27 50 0.27 50 0.27 50 10 0.27 50 0.27 50 0.27 SO 0.27 50 0.27 50 12 0.27 50 0.27 50 0.27 50 0.27 50 0.27 50 14 0.27 SO 0.27 50 0.27 50 0.27 50 0.27 SO 16 0.27 50 0.27 50 0.27 50 0.27 50 0.27 50 20 0.27 50 0.27 50 0.27 50 0.27 50 0.27 50 24 0.27 50 0.27 50 0.27 50 0.27 50 0.27 50 28 0.30 St 0.27 SO 0.27 50 0.27 50 0.27 50 32 0.30 51 0.30 51 0.27 50 0.27 50 0.27 50 * Truclcloade uied Is computing tbit table are baaed os a tingle H-20 truck with 16 000-lb wheel load tad l..` Impact (actor. f See corTtepondlng illuatratiose Is Fig. 3 of typei of laying condition!. 8 AMERICAN NATIONAL STANDARD TABLE 51.1--(cont.) Laying Condition Size in. Depth ot fl. 10 32 Type It Type 2f Type 3f Type If Type 5f in. 0.29 0.29 0.29 0.29 0.29 0.29 0.29 0.29 0.29 0.29 0.29 0.32 0.32 0.35 0.35 Thick- Class 50 50 50 so 50 50 50 50 50 50 50 50 51 51 52 52 Thick- in. 0.29 0.29 0.29 0.29 0.29 0.29 0.29 0.29 0.29 0.29 0.29 0.29 0.29 0.29 0.32 0.32 Thickness Class 50 50 50 50 50 50 50 50 50 50 50 50 50 50 51 51 Thickness in. 0.29 0.29 0.29 0.29 0.29 0.29 0.29 0.29 0.29 0.29 0.29 0.29 0.29 0.29 0.29 0.32 Thickness Class 50 50 50 50 50 50 50 50 50 50 50 5) 50 50 50 51 Thickness in. 0.29 0.29 0.29 0.29 0.29 0.29 0.29 0.29 0.29 0.29 0.29 0.29 0.29 0.29 0.29 0.29 Thickness Class 50 50 50 50 50 50 50 50 50 50 50 50 SO 50 50 50 Thickness in. 0.29 0.29 0.29 0.29 0.29 0.29 0.29 0.29 0.29 0.29 0.29 0.29 0.29 0.29 0.29 U.29 Thickness Class 50 50 50 50 50 50 50 50 50 50 50 50 50 SO 50 50 32 0 31 0.40 50 50 50 50 50 SO SO 50 50 SO 50 50 51 52 52 S3 0.31 0.31 0.31 0.31 0.31' 0.31 0.31 0.31 0.31 0.31 0.31 0.31 0.31 0.34 0.34 0.37 5D 50 50 50 50 51) 50 50 50 50 50 50 SO 51 51 52 0.31 0.31 0.31 0.31 0.31 0.31 0.31 0.31 0.31 0.31 0.31 0.31 0.31 0.3 1 0.34 0.14 50 50 50 50 50 50 50 50 50 50 50 50 50 50 51 51 0.31 0.31 0.31 0.31 0.31 0.31 0.31 0.31 0.31 0.31 0.31 0.31 0.31 0.1) O.U 0.31 50 0.31 50 0.31 50 0.31 50 0.31 50 0.31 50 0.31 50 0.31 50 0.31 50 0.31 50 0.31 50 0.31 50 0.31 50 0.31 50 0.31 50 0.31 50 0.31 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 0 36 50 50 50 50 50 50 50 50 50 50 SO 51 52 52 0.31 0.33 0.33 0.33 0.31 0.33 0.31 0.33 0.33 0.33 0.33 0.33 0.36 0.39 50 50 SO 50 50 50 50 50 50 50 50 50 51 52 0.13 0.33 0.33 0.33 0.31 0.1.1 0.31 0.31 0.31 0.33 0.33 0.31 0.11 0.33 50 SO 50 50 50 50 50 50 50 50 50 50 50 50 0.33 0.33 0.33 0.33 0.13 0.3.1 0.33 0.31 0.33 0.33 0.33 0.33 0.33 0.33 SO 50 50 50 50 50 SO 50 50 50 50 50 50 50 0.33 0.33 0.33 0.33 0.33 0.33 0.33 0.33 0.33 0.33 0.33 0.33 0.33 0.33 50 50 50 50 50 50 50 50 50 50 50 50 32 0 *2 0.45 53 54 0.39 0,42 52 53 0.36 0.39 51 52 0.3.1 0.33 50 50 0.33 0.33 .? , SO 50 50 50 50 50 50 50 50 SO 51 51 52 51 54 0.34 0 34 0.14 0.34 0.34 0.34 0.34 0.34 0.34 0.34 0.34 0.34 0 37 0.40 0 43 SO 50 50 50 50 50 50 50 50 SO 50 SO 51 52 S3 0.34 0.14 0.34 0.34 0.34 0.34 0.34 0.34 0.34 0.34 0.34 0.34 0.34 0.37 0.40 SO 50 50 50 50 50 50 50 SO 50 50 50 50 51 52 0.34 0.34 0.34 0.34 0.34 0.34 0.34 0.34 0.34 0.34 0.34 0.34 0.34 0.34 0.34 50 SO SO SO 50 50 50 50 50 50 so 50 50 50 50 0.34 0.34 0.34 0.34 0.34 0.34 0.34 0.34 0.34 0.34 0.34 0.34 0.34 0.34 0.34 50 50 50 50 50 50 50 SO 50 50 50 50 50 50 50 32 0.49 55 0.46 54 0.43 53 0.37 51 0.34 50 t See corresponding illustration! in Fig. 3 of types of laying conditions. I I $ I CTD014631 t DUCTILE-IRON PIPE 9 TABLE 51.1--(cont.) Laying Condition Size in. 18 Depth of Cover //. 2.5 3 4 5 6 7 8 9 10 12 14 16 20 24 28 32 Type If Thick ness in. 0.35 0.35 0.35 0.35 0.35 0.35 0.3S 0.35 0.35 0.38 0.38 0.41 0.44 0.47 0.50 0.53 Thick ness Class 50 50 50 50 50 SO SO 50 50 51 51 52 53 54 55 56 Type 2t Thick ness in. 0.35 0.35 0.35 0.35 0.35 0.35 0.35 0.35 0.35 0.35 0.35 0.38 0.41 0.44 0.47 0.50 Thick ness Class 50 SO 50 50 50 50 50 50 50 50 50 51 52 53 54 55 Type 3f Thick ness in. 0.35 0.35 0.35 0.35 0.35 0.35 0.35 0.35 0.35 0.35 0.35 0.35 0.35 0.41 0.44 0.47 Thick ness Ctass 50 50 50 50 SO so 50 SO 50 50 50 50 50 52 53 54 Type 4f Thick ness in. 0.35 0.35 0.35 0.35 0.35 0.35 0.35 0.35 0.35 0.35 0.35 0.35 0.35 0.35 0.35 0.38 Thick ness Class 50 50 50 50 50 50 50 50 SO 50 50 50 50 50 50 51 Type 5t Thick ness in. 0.35 0.35 0.35 0.35 0.35 0.35 0.35 0.35 0.35 0.35 0.35 0.35 0.35 0.35 0.35 0.35 Thick ness Class 50 50 SO 50 50 50 50 50 50 50 SO 50 50 50 50 53 20 2.S 0.39 51 0.36 SO 0.36 50 0.36 SO 0.36 50 3 0.36 50 0.36 so 0.36 50 0.36 SO 0.36 50 4 0.36 50 0.36 so 0.36 50 0.36 50 0.36 50 S 0.36 50 0.36 50 0.36 SO 0.36 SO 0.36 50 6 0.36 50 0.36 50 0.36 50 0.36 SO 0.36 SO 7 0.36 SO 0.36 50 0.36 SO 0.36 50 0.36 SO 8 0.36 50 0.36 50 0.36 50 0.36 SO 0.36 50 9 0.36 50 0.36 50 0.36 50 0.36 50 0.36 50 10 0.36 50 0.36 50 0.36 50 0.36 50 0.36 50 12 0.39 51 0.36 50 0.36 SO 0.36 50 0.36 50 14 0.42 52 0.36 50 0.36 so 0.36 50 0.36 50 16 0.42 S2 0.39 51 0.36 50 0.36 SO 0.36 50 20 0.48 54 0.42 52 0.39 51 0.36 50 0.36 50 24 0.51 55 0.48 54 0.42 52 0.36 50 0.36 SO 28 0.54 56 0.51 55 0.45 53 0.39 51 0.36 50 32 --* -- 0.54 56 0.48 54 0.42 52 0.36 50 24 2.5 0.41 51 0.38 SO 0.3fl 50 0.38 50 0.38 SO 3 0.38 50 0.38 50 0.38 50 0.38 50 0.38 50 4 0.38 50 0.38 50 0.38 50 0.38 50 0.38 50 5 0.38 50 0.38 50 0.38 50 0.38 SO 0.38 50 6 0.38 SO 0.38 50 0.38 50 0.38 SO 0.38 50 7 0.38 50 0.38 50 0.38 50 0.38 SO 0.38 50 8 0.38 50 0.38 50 0.38 SO 0.38 50 0.38 50 9 0.41 SI 0.38 50 0.38 50 0.38 50 0.38 50 10 0.41 St 0.38 50 0.38 50 0.38 50 0.38 50 12 0.44 52 0.38 SO 0.38 SO 0.38 50 0.38 50 14 0.47 53 0.41 51 0.38 SO 0.38 50 0.38 50 16 0.50 54 0.44 52 0.38 50 0.38 SO 0.38 50 20 0.53 55 0.50 54 0.44 52 0.38 50 0.38 50 24 0.56 56 0.53 55 0.47 53 0.41 51 0.38 50 28 -- 0.56 56 0.53 55 0.44 52 0.38 SO 52 -- -- -- -- 0.56 56 0.47 Si 0.4t 51 30 2.5 3 4 S 6 7 8 9 10 12 14 16 20 24 28 32 t : 0.39 50 0.39 50 0.39 50 0.39 50 0.39 SO 0.39 50 0.39 50 0.39 50 0.39 50 0.39 50 0.39 50 0.39 50 0.39 50 0.39 50 0.39 50 0.39 50 0.39 SO 0.39 50 0.39 50 0.39 50 0.39 SO 0.39 50 0.39 so 0.39 50 0.39 SO 0.39 50 0.39 so 0.39 50 0.39 SO 0.39 50 0.39 50 0.39 50 0.39 SO 0.39 50 0.39 50 0.39 50 0.43 SI 0.39 50 0.39 50 . 0.39 50 0.47 52 0.39 50 0.39 50 0.39 50 0.51 S3 0.43 51 0.39 50 0.39 50 0.59 55 0.51 53 0.43 51 0.39 50 0.63 56 0.55 54 0.47 52 0.39 SO ___ -- 0.63 56 o.st 53 0.43 51 -- 0.55 54 0.47 52 t See corresponding illustrations In Fig. 3 of types of laying conditions. t For pipe 30 in. and Larger, consideration should be given to the use of laying conditions other than Type 1. 10 AMERICAN NATIONAL STANDARD TABLE 51.1--(coni.) > Laying Condition i Depth Size of in. Cover fU Type It Thick ness in. Thick ness Class Type 2f Thick Thick ness ness in. Class Type 3f Thick ness in. Thick ness Class Type 4f Thick ness tn. Thick ness Class Type 5f Thick Thick ness ness in, Class 36 2.5 3 4 5 6 7 8 9 10 12 14 16 20 24 28 32 t X 0.43 50 0.43 50 0.43 SO 0.43 50 0.43 50 0.43 50 0.43 50 0.43 50 0.43 50 0.43 SO 0.43 50 0.43 50 0.43 50 0.43 50 0.43 50 0.43 50 0.43 50 0.43 50 0.43 50 0.43 50 0.43 50 0.43 50 0.43 50 0.43 50 0.43 50 0.43 50 0.43 50 0.43 50 0.43 50 0.43 50 0.43 50 0.43 50 0.43 50 0.43 50 0.43 50 0.43 50 0.48 51 0.43 50 0.43 SO 0.43 50 0.53 52 0.48 51 0.43 SO 0.43 50 0.58 S3 0.48 SI 0.43 50 0.43 SO 0.63 54 O.S8 53 0.48 51 0.43 50 0.73 -- 56 -- 0.63 0.68 54 55 0.53 0.58 52 53 0.43 0.48 50 51 ~~ 0.63 54 0.53 52 42 2.5 3 4 5 6 7 8 9 10 12 14 16 20 24 28 32 tt 0.47 50 0.47 50 0.47 50 0.47 50 0.47 50 0.47 50 0.47 50 0.47 50 0.47 50 0.47 50 0.47 50 0.47 50 0.47 50 0.47 50 0.47 50 0.47 50 0.47 50 0.47 50 0.47 50 0.47 50 0.47 50 0.47 50 0.47 50 0.47 50 0.47 50 0.47 50 0.47 50 0.47 50 0.47 50 0.47 50 0.47 50 0.47 50 0.53 51 0.47 50 0.47 50 0.47 50 0.53 51 0.47 50 0.47 50 0.47 50 0.S9 52 0.53 51 0.47 50 0.47 50 0.65 53 0.59 52 0.47 50 0.47 50 0.71 54 0.65 53 0.59 52 0.47 50 0.83 -- 56 -- 0.71 0.77 54 55 0.65 0.71 53 54 0.47 0.59 50 52 0.71 54 0.65 53 48 2.5 3 ,4 5 6 7 8 9 10 12 14 16 20 24 28 32 t : 0.51 50 0.51 50 0.51 50 0.51 50 0.51 50 0.51 SO 0.51 50 0.51 50 )0.51 50 0.51 50 0.51 50 0.51 50 0.51 50 0.51 50 0.51 50 0.51 50 0.51 50 o.st 50 0.51 50 0.51 50 0.51 50 0.51 50 0.51 50 0.51 50 0.51 so 0.51 50 0.51 50 0.51 50 0.51 50 0.51 50 0.51 50 0.51 50 0.58 51 0.51 SO o.st 50 0.51 50 0.58 51 0.51 50 0.51 50 0.51 50 0.65 52 0.58 51 0.51 50 0.51 50 0.72 53 0.65 52 0.58 51 0.51 50 0.79 54 0.72 53 0.65 52 0.51 50 0.93 56 0.79 54 0.72 53 0.58 51 -- -- 0.86 55 0.79 54 0.65 52 -- 0.86 55 0.72 53 54 2.5 3 4 5 6 7 8 9 10 12 14 16 20 24 28 32 t t 0.57 50 0.57 50 0.57 50 0.57 SO 0.57 50 0.57 50 0.57 50 0.57 50 0.57 SO 0.57 50 0.57 50 0.57 50 0.57 0.57 50 50 0.57 0.57 50 50 0.57 0.57 50 SO 0.57 0.57 50 50 J0.57 0.57 0.57 0.65 0.65 0.73 0.81 0.89 1.05 -- SO 50 50 51 51 52 53 54 56 -- 0.57 0.57 0.57 0.57 0.57 0.65 0.73 0.81 0.89 0.97 50 50 50 50 50 51 52 53 54 S5 0.57 0.57 0.57 0.57 0.57 0.57 0.65 0.73 0.81 0.89 50 SO 50 50 50 50 51 52 53 54 0.57 0.57 0.57 0.57 0.57 0.57 0.57 0.57 0.65 0.73 50 50 50 50 50 50 50 50 51 52 0.97 55 0.81 53 t See corresponding illustrations in Pig. i of types of laying conditions. t For pipe 30 in. and larger, consideration should be given to the use of laying conditions other than Type i. CTD014633 DUCTILE-IRON PIPE 11 Type 3 Pipe bedded in 4-in.-minimum loose soil .J Backfill lightly consolidated to top of pipe. Type 4 Pipe bedded in sand, gravel, or crushed stone to depth of i pipe diameter, 4-in. minimum. Backfill compacted to top of pipe. (Approx. 80 per cent Standard Proctor, AASHTO T-99) Type 5 Pipe bedded to its centerline in compacted granular material, 4-in. minimum under pipe. Compacted granular or select J material to top of pipe. (Approx. 90 per cent Standard Proctor, AASHTO T-99) Fig. 3. Standard Laying Conditions * For pipe 30 in. and larger, consideration should be given to the use oi laying conditions other than Type 1. t "Flat-bottom" is defined as undisturbed earth. t "Loom soil" or "select material" is defined as native soil excavated from the trench, free of rocks, foreign materials, and frosen *nrth. I American Association of State Highway and Transportation Officials, 141 National Press Bldg., Washington, D.C 20004. CTD014634 12 AMERICAN NATIONAI. STANDARD TABLE 51.2 Standard Thickness for Internal Pressure Rated Water Working Pressure*--psi Tipe Size in. 3 4 6 8 10 12 14 16 18 20 24 30 36 42 48 54 150 200 250 300 350 Thick. ness in. Thick- ness Class Thicknesa in. Thickness Class ThickDess in. Thickness Class Thickness in. Thickness Class Thickness in. Thick- ness Class 0.25 51 0.25 51 0.25 51 0.25 51 0.25 51 0.26 51 0.26 51 0.26 51 0.26 51 0.26 51 0.25 50 0.25 50 0.25 50 0.25 50 0.25 50 0.27 50 0.27 50 0.27 50 0.27 50 0.27 50 0.29 50 0.29 50 0.29 50 0.29 50 0.29 50 0.31 50 0.31 50 0.31 50 0.31 50 0.31 50 0.33 50 0.33 50 0.33 50 0.33 50 0.33 50 0.34 50 0.34 50 0.34 50 0.34 50 0.34 50 0.35 50 0.35 50 0.35 50 0.35 50 0.35 50 0.36 50 0.36 so 0.36 50 0.36 50 0.39 51 0.38 50 0.38 50 0.38 50 0.41 51 0.44 52 0.39 50 0.39 50 0.43 51 0.47 52 0.51 53 0.43 50 0.43 50 0.48 51 0.53 . 52 0.58 53 0.47 50 0.47 50 0.53 51 0.59 52 0.65 53 0.51 50 0.51 50 0.58 51 0.65 52 0.72 53 0.57 50 0.57 50 0.65 51 0.73 52 0.81 ,53 * These pipe are adequate for the rated working pressure plus a surge allowance of 100 psi. CTD014635 DUCTILE--IRON PIPE TABLE 51.3 Rated Working Pressure and Maximum Depth of Cover 13 Pipe Size in* Thickness Class Nominal Thickness in, Rated Water Working Pressure* psi 3 51 52 S3 54 55 56 4 51 52 53 54 55 56 ` 6 50 51 52 53 54 S5 56 8 50 5L 52 53 54 55 56 10 50 51 52 53 54 55 56 12 50 51 52 53 54 ' 55 56 14 50 51 52 53 54 55 56 15 SO 51 52 53 54 55 56 18 50 51 52 53 54 55 56 0.25 0.28 0.31 0.34 0.37 0.40 0.26 0.29 0.32 0.35 0.38 0.41 0.25 0.28 0.31 0.34 0.37 0.40 0.43 0.27 0.30 0.33 0.36 0.39 0.42 0.4S 0.29 0.32 0.35 0.38 0.41 0.44 0.47 0.31 0.34 0.37 0.40 0.43 0.46 0.49 0.33 0.36 0.39 0.42 0.45 0.48 0.51 0.34 0.37 0.40 0.43 0.46 0.49 0.52 0.35 0.38 0.41 0.44 0.47 0.50 0.53 350 350 350 350 350 3S0 350 350 350 350 350 350 350 350 350 350 350 350 350 3S0 350 350 3S0 350 350 350 350 350 350 350 350 350 350 350 350 350 350 350 350 350 350 350 350 350 350 350 350 350 350 350 350 350 350 350 350 350 350 350 350 350 350 Type 1 98 100} 100} 100} 100} 100} 76 100} 100} 100} 100} 100} 32 49 67 91 wot 100} 100} 25 36 47 64 80 98 100} 19 27 3S 45 57 67 81 17 23 30 36 45 54 64 15 19 24 30 36 43 52 13 16 20 2S 30 35 4! 11 14 18 22 25 30 35 Laying Condition Type 2 Type 3 Type 4 Maximum Depth of Cover--/If 100} 100} 100} loot 100} 100} 100} 100} 100} 100} 100} 100} 100} 100} 100} 100} 100} 100} 86 100} 100} 100} 100} 100} 96 100} 100" 100} 100} 100} 100} 100} 100} 100} 100} 100} 38 57 77 100} loot 100} 100} 44 64 86 100} wot 100} 100} 56 80 100} 100} 100} 100} 100} 30 42 54 73 91 100} 100} 24 32 41 52 65 77 92 36 49 62 82 100} 100} 100} 29 38 47 59 74 86 100} 46 61 77 100} 100} 100} 100} 38 49 59 74 91 100} 100} 22 27 36 28 33 43 35 41 53 42 49 61 52 59 74 62 71 87 73 83 100} 19 24 33 23 28 38 29 34 44 35 41 53 42 49 61 50 57 71 59 67 83 17 21 30 21 25 34 25 30 40 30 36 46 35 41 53 41 47 59 48 55 68 15 20 29 19 23 32 22 27 36 26 31 41 30 36 46 35 41 53 41 47 59 Type S 100} 100} 100} 100} 100} 100} 100} 100} 100} 100} 100} 100} 75 100} 100} 100} 100} 100} 100} 64 81 99 100} 100} 100} 100} 55 66 79 95 100} 100} 100} 52 60 71 81 95 100} 100} 49 55 62 71 81 92 100} 47 51 57 64 71 79 89 42 49 53 58 64 79 * These pipe are adequate for the rated working pressure plm a surge allowance of 100 pai. Ductile-iron pipe for working pressures higher than 350 psi is available, t An allowance for a single H-20 truck with 1.5 impact factor Is included for all depths of cover } Calculated maximum depth of cover exceeds 100 ft. CTD014636 14 AMERICAN NATIONAL STANDARD TABLE 51.3--(cont.) 1 ) Pipe Size in. Thickness Class Nominal Thickness in. Rated Water Working Pressure* PS* 20 50 51 52 53 54 55 56 24 50 51 52 S3 54 55 56 30 50 51 52 53 54 55 56 36 50 51 . 52 53 54 5$ 56 42 so 51* 52 53 54 55 56 48 50 51 52 53 54 55 56 54 50 51 52 53 54 55 IS 0.36 0.39 0.42 0.45 0.48 0.51 0.54 0.38 0.41 0.44 0.47 0.50 0.53 0.56 0.39 0.43 0.47 0.51 0.55 0.59 0.63 0.43 0.48 0.53 0.58 0.63 0.68 0.73 0.47 0.53 ' 0.59 0.65 0.71 0.77 0.83 0.51 0.58 0.65 0.72 0.79 0.86 0.93 0.57 0.65 0.73 0.81 0.89 0.97 1.05 300 350 350 350 350 350 350 250 300 350 350 350 350 350 200 250 300 350 ` 350 350 350 200 250 300 350 350 350 350 200 250 300 350 350 350 350 200 250 300 350 350 350 350 200 250 300 350 350 350 350 Type 1 10 13 16 19 22 26 30 8 10 13 IS 18 20 24 i 5 Laying Condition Type 2 Type 3 Type 4 Maximum Depth of Cover--/If 14 18 27 17 21 30 20 25 34 23 28 38 27 32 42 31 37 47 3S 41 53 12 17 23 1$ 19 27 17 21 30 19 24 33 22 27 36 25 30 40 29 34 44 10 14 18 12 16 21 14 19 24 17 21 29 19 24 33 22 27 36 26 31 41 10 13 17 12 16 20 15 19 24 17 21 28 20 25 33 23 28 37 26 31 41 9 13 16 12 15 19 14 18 22 17 22 27 20 24 32 23 28 38 26 31 41 9 12 15 12 14 18 14 18 21 17 21 25 20 24 30 23 28 37 26 31 41 9 12 15 12 14 18 14 17 21 17 21 25 20 25 30 23 28 37 27 32 42 Type 5 38 44 50 54 59 65 71 31 36 41 47 53 57 61 25 29 33 38 44 51 57 25 28 32 37 43 50 59 24 27 30 35 42 48 57 23 26 30 34 40 47 55 23 25 29 34 40 47 55 * These pipe are adequate for the rated working pressure plus a surge allowance of 100 psi. Ductile-iron pipe for working pressures higher than 350 psi is available, t An allowance for a single H-20 truck with 1.5 impact factor is included for all depths of cover. & For pipe 30 in. and larger, consideration should be given to the use of laying conditions other than Type 1 CTD014637 DUCTILE--IRON PIPE IS TABLE 51.4 Standard Dimensions and Weights of Push-On-Joint Ductile-Iron Pipe Size in. Thick ness Class Thick ness in. 3| 51 52 0.25 0.28 53 0.31 54 0.34 55 0.37 56 0.40 4 51 0.26 52 0.29 53 0.32 54 0.35 55 0.38 56 0.41 6 SO 0.25 SI 0.28 52 0.31 53 0.34 54 0.37 S5 0.40 56 0.43 g 50 0.27 51 0.30 52 0.33 53 0.36 54 0.39 55 0.42 56 0.45 10 50 0.29 51 0.32 52 0.35 53 0.38 54 0.41 55 0.44 56 0.47 OD* in. 3.96 3.96 3.96 3.96 3.96 3.96 4.80 4.80 4.80 4.80 4.80 4.80 6.90 6.90 6.90 6.90 6.90 6.90 6.90 9.05 9.05 9.05 9.05 9.05 9.05 9.05 11.10 11.10 11.10 11.10 11.10 11.10 11.10 Wt. of Barrel Per Ft 16 Wt. of Bell lb 8.9 9.9 10.9 11.8 12.8 13.7 11.3 12.6 13.8 15.0 16.1 17.3 16.0 17.8 19.6 21.4 23.2 25.0 26.7 22.8 25.2 27.7 30.1 32.5 34.8 37.2 30.1 33.2 36.2 39.2 42.1 45.1 48.0 9 9 9 9 9 9 11 11 11 11 11 11 18 18 18 18 18 18 18 26 26 26 26 26 26 26 34 34 34 34 34 34 34 18-Ft Laying Length 20-Ft Laying Length Wt. Per Lgth.f lb 170 185 205 220 240 255 215 240 260 280 300 320 305 340 370 405 435 470 500 435 480 525 570 610 650 695 575 630 685 740 790 845 900 Avg. Wt. Per Ft* lb 9.4 10.4 11.4 12.3 13.3 14.2 11.9 13.2 14.4 15.6 16.7 17.9 17.0 18.8 20.6 22.4 24.2 26.0 27.7 24.2 26.6 29.1 31.5 33.9 36.2 38.6 32.0 3S.1 38.1 41.1 44.0 47.0 49.9 Wt. Per uth.t 185 205 225 245 26S 285 235 265 285 310 335 355 340 375 410 445 480 520 550 480 530 580 630 675 720 770 635 700 760 820 875 935 995 Avg. Wt. Per FtJ lb 9.4 10.4 11.4 12.2 13.2 14.2 11.8 13.2 14.4 15.6 16.6 17.8 16.9 18.7 20.5 22.3 24.1 25.9 27.6 24.1 26.5 29.0 31.4 33.8 36.1 38.5 31.8 34.9 37.9 40.9 43.8 46.8 49.7 Tolerance of OD of spigot ends ^12 in., 0.06 in.; 14-24 in., +0.05 In., --0.08 in.; 30-54 In.. +0.08 In., u.uo in. t Including bell; calculated weight of pipe rounded off to nearest 5 lb. 1 Including bell; average weight, per foot, based on calculated weight of pipe before rounding. { Pipe of 3-in. size also available in 12-ft laying length with following weights: Thickness Class 51 52 53 54 55 56 Thickness in. 0.25 0.28 0.31 0.34 0.37 0.40 Wt. Per Lgth.f lb 115 130 140 150 165 175 Avg. Wt. Per Ftf lb 9.6 10.6 11.6 12.6 13.6 14.4 II CTD014638 16 AMERICAN NATIONAL STANDARD ) TABLE 51.4--{cont.) Size in. Thick. ness Class Thick ness in. 12 50 0.31 51 0.34 52 0.37 53 0.40 54 0.43 55 0.46 56 0.49 u 50 0.33 51 0.36 52 0.39 53 0.42 54 0.45 55 0.48 56 0.51 16 50 0.34 51 0.37 52 0.40 53 0.43 54 0.46 55 0.49 56 0.S2 18 50 0.35 51 0.38 52 0.41 53 0.44 54 0.47 55 0.50 56 0.53 20 50 0.36 SI 0.39 52 0.42 53 0.45 54 0.48 55 O.Sl 56 0.54 OD* in. 13.20 13.20 13.20 13.20 13.20 13.20 13.20 IS.30 15.30 15.30 15.30 15.30 15.30 15.30 17.40 17.40 17.40 17.40 17.40 17.40 17.40 19.50 19.50 19.50 19.50 19.50 19.50 19.50 21.60 21.60 21.60 21.60 21.60 21.60 21.60 Wt. of Barrel Per Ft lb 38.4 42.0 45.6 49.2 52.8 56.3 59.9 47.5 51.7 55.9 60.1 64.2 68.4 72.5 55.8 60.6 65.4 70.1 74.9 79.7 84.4 64.4 69.8 75.2 80.6 86.0 91.3 96.7 73.5 79.5 85.5 91.5 97.5 103.4 109.3 Wt. of Blebll 43 43 43 43 43 43 43 63 63 63 63 63 63 63 76 76 76 76 76 76 76 87 87 87 87 87 87 87 97 97 97 97 97 97 97 18-Ft Laying Length 20-Ft Laying Length Wt. Per Lgth.f lb Avg. Wt. Per Ft{ lb 735 800 865 930 995 1 055 1 120 40.8 44.4 48.0 51.6 55.2 58.7 62.3 920 995 1 070 1 145 1 220 1 295 1 370 51.0 55.2 59.4 63.6 67.7 71.9 76.0 1 080 1 165 l 255 1 340 1 425 1 510 1 595 ' 60.0 64.8 69.6 74.3 79.1 83.9 88.6 1 245 1 345 1 440 1 540 t 635 l 730 1 830 69.2 74.6 80.0 85.4 90.8 96.1 101.5 1 420 1 530 1 635 1 745 1 850 l 960 2 065 78.9 84.9 90.9 96.9 102.9 108.8 114.7 Wt. Per Lgltbh.f 810 885 955 1 025 1 100 1 170 1 240 015 i 095 1 180 1 265 1 345 1 430 1 515 1 190 1 290 1 385 1 480 1 575 1 670 1 765 1 375 1 485 1 590 1 700 1 805 1 915 2 020 1 565 1 685 1 805 1 925 2 045 2 165 2 285 Avg. Wt. PerlbFtf 40.6 44.2 47.8 51.4 55.0 58.4 62.0 50.6 54.8 59.0 63.2 67.4 71.6 75.6 59.6 64.4 69.2 73.9 78.7 83.5 88.2 68.8 74.2 79.6 85.0 90.4 95.6 101.0 78.4 84.4 90.4 96.4 102.4 108.2 114.2 Tolerance of OD of spigot end: 3-12 in., 0.06 in.; 14-24 in.. +0.05 in., -0.08 in.; 30-54 in., +0.08 in. --0.06 in. t Including bell; calculated weight of pipe rounded off to nearest 5 lb. t Including bell; average weight per foot, based on calculated weight of pipe before rounding. CTD014639 DUCTILE-IRON PIPE 17 TABLE 51.4--(cont.) Size in. Thick ness Class Thick ness in. OD* in. Wt. of Barrel Per Ft lb Wt. of Bell lb I8-Ft Laying Length 20-Ft Laying Lentgh Wt. Per Lgth.f lb Avg. Wt. Per FtJ lb Wt. Per Lgth.f lb Avg. Wt. Per Fit lb 24 50 0.38 25.80 92.9 120 1 790 99.6 1 980 98.9 51 0.41 25.80 100.1 120 1 920 106.8 2 120 106.1 52 0.44 25.80 107.3 120 2 050 114.0 2 265 113.3 53 0.47 25.80 114.4 120 2 ISO 121.1 2 410 120.4 54 0.50 25.80 121.6 120 2 310 128.3 2 550 127.6 55 0.53 25.80 128.8 120 2 440 135.5 2 695 134.8 56 0.56 25.80 135.9 120 2 565 142.6 2 840 141.9 30 50 51 52 53 54 55 56 0.39 0.43 0.47 0.51 0.55 0.59 0.63 32.00 32.00 32.00 32.00 32.00 32.00 32.00 118.5 130.5 142.5 154.4 166.3 178.2 190.0 ** 2 350 2 565 2 780 2 995 3 210 3 425 3 635 130.5 142.5 154.5 166.4 178.3 190.2 202.0 . 2 535 2 775 3015 3 250 3 490 3 725 3 965 126.6 138.6 150.6 162.6 174.4 186.4 198.2 36 50 0.43 38.30 156.5 tt 51 0.48 38.30 174.5 52 0.53 38.30 192.4 53 0.58 38.30 210.3 54 0.63 38.30 228.1 55 0.68 38.30 245.9 56 0.73 38.30 263.7 3 110 3 435 3 755 4 075 4 400 4 720 5 040 172.7 190.7 208.6 226.5 244.3 262.1 279.9 3 345 3 705 4 065 4 420 4 780 5 135 5 490 167.3 18$.3 203.2 221.1 238.9 256.7 274.5 42 50 0.47 44.50 198.9 261 51 0.53 44.50 224.0 261 52 0.59 44.50 249.1 261 53 0.65 44.50 274.0 261 54 0.71 44.50 298.9 261 55 0.77 44.50 323.7 261 56 0.83 44.50 348.4 261 4 240 4 740 5 245 5 740 6 240 6 735 7 230 212.0 237.0 262.2 287.0 312.0 336.8 361.4 48 50 0.51 50.80 246.6 316 51 0.58 50.80 280.0 316 52 0.65 50.80 313.4 316 53 0.72 50.80 346.6 316 54 0.79 50.80 379.8 316 55 0.86 50.80 412.9 316 56 0.93 50.80 445.9 316 5 250 5 915 6 585 7 250. 7 910 8 575 9 235 262.4 295.8 329.2 362.4 395.6 428.7 461.7 54 50 0.57 57.10 309.8 370 51 0.65 57.10 352.7 370 52 0.73 57.10 395.6 370 53 0.81 57.10 438.3 370 54 0.89 57.10 480.9 370 55 0.97 57.10 523.4 370 56 1.05 57.10 565.8 370 6 565 7 425 8 280 9 135 9 990 10 840 11 685 328.3 371.2 414.1 456.8 499.4 541.9 584.3 Tolerances of OD of spigot end: 3-12 in.. 0.06 in.; 14-24 in., +0.05 in., --0.08 in.; 30-54 in., +0.08 In., --0.06 in. t Including bell; calculated weight of pipe rounded off to nearest 5 lb. t Including bell; average weight per foot, based on calculated weight of pipe before rounding. ** Weight of 30-in. bell is 216 lb for 18-ft pipe and 163 lb for 20-ft pipe, tt Weight of 36-in. bell is 292 lb for 18-ft pipe and 216 lb for 20-ft pipe. CTD014640 18 AMERICAN NATIONAL STANDARD TABLE 51.5 Standard Dimensions and Weights of Mechanical-Joint Ductile-Iron Pipe Size in. Thick ness Class Thick ness in. 3$ 51 52 53 54 55 56 4 51 52 53 54 55 56 6 50 51 52 53 54 55 56 8 50 51 52 53 54 55 56 10 50 51 52 53 54 55 56 12 SO 51 52 ' 53 54 55 56 14 50 51 52 S3 54 55 56 0.25 0.28 0.31 0.34 0.37 0.40 0.26 0.29 0.32 0.35 0.38 0.41 0.25 0.28 0.31 0.34 0.37 0.40 0.43 0.27 0.30 0.33 0.36 0.39 0.42 0.45 0.29 0.32 0.35 0.38 0.41 0.44 0.47 0.31 0.34 0.37 0.40 0.43 0.46 0.49 0.33 0.36 0.39 0.42 0.45 0.48 0.51 OD* in. 3.96 3.96 3.96 3.96 3.96 3.96 4.80 4.80 4.80 4.80 4.80 4.80 6.90 6.90 6.90 6.90 6.90 6.90 6.90 9.05 9.05 9.0S 9.05 9.05 9.05 9.05 11.10 11.10 11.20 11.10 11.10 11.10 11.10 13.20 13.20 13.20 13.20 13.20 13.20 13.20 15.30 15.30 15.30 15.30 15.30 15.30 15.30 Wt. of Barrel PeT Ft lb 8.9 9.9 10.9 11.8 12.8 13.7 11.3 12.6 13.8 15.0 16.1 17.3 16.0 17.8 19.6 21.4 23.2 25.0 26.7 22.8 25.2 27.7 30.1 32.5 34.8 37.2 30.1 33.2 36.2 39.2 42.1 45.1 48.0 38.4 42.0 45.6 49.2 52.8 56.3 59.9 47.5 51.7 55.9 60.1 64.2 68.4 72.5 Wt. of Bell lb 11 11 11 11 11 11 16 16 16 16 16 16 22 22 22 22 22 22 22 29 29 29 29 29 29 29 39 39 39 39 39 39 39 49 49 49 49 49 49 49 76 76 76 76 76 76 76 18-ft Laying Length 20-ft Laying Length Wt. Per Lgth.f lb 170 190 205 225 240 260 220 245 265 28S 305 325 310 340 375 405 440 470 505 440 485 530 570 615 655 700 580 635 690 745 795 850 905 740 805 870 935 1 000 1 060 1 125 930 1 005 1 080 1 160 1 230 1 305 1 380 Avg. Wt. Per Fit lb 9.5 10.5 11.5 12.4 13.4 14.3 12.2 13.5 14.7 15.9 17.0 18.2 17.2 19.0 20.8 22.6 24.4 26.2 27.9 24.4 26.8 29.3 31.7 34.1 36.4 38.8 32.3 35.4 38.4 41.4 44.3 47.3 50.2 41.1 44.7 48.3 51.9 5S.5 59.0 62.6 51.7 55.9 60.1 64.3 68.4 72.6 76.7 Wt. Per Lgth.t lb 190 210 230 245 265 285 240 270 290 315 340 360 340 380 415 450 485 520 555 485 535 585 630 680 725 775 640 705 765 825 880 940 1 000 815 890 960 l 035 1 105 1 175 1 245 1 025 i no 1 195 1 280 1 360 1 445 1 525 Avg. Wt. Per Ft: lb 9.4 10.4 11.4 12.4 13.4 14.2 12.1 13.4 14.6 15.8 16.9 18.1 17.1 16.9 20.7 22.5 24.3 26.1 27.8 24.2 26.6 29.2 31.6 34.0 36.2 38.6 32.0 35.2 38.2 41.2 44.0 47.0 50.0 40.8 44.4 48.0 51.6 55.2 58.8 62.3 51.3 55.5 59.7 63.9 68.0 72.2 76.3 Tolerances of OD of spigot end: 3--12 in.. 0.06 in.; 14--24 in.. +0.05 in., --0.08 in.; 30--48 in., +0.08 in., 0.06 in. t Including bell; calculated weight of pipe rounded off to nearest 5 lb. 2 Including bell; average weight, per foot, based on calculated weight of pipe before rounding. { Pipe of 3-in. size also available in 12-ft laying length with following weights: Thickness Class 51 52 53 54 55 56 Thickness in. 0.25 0.28 0.31 0.34 0.37 0.40 Wt. Per Lgth.f lb 120 130 140 155 165 175 Avg. Wt. Per FtJ a 9.8 10.8 11.8 12.7 13.7 14.6 1 t CTD014641 DUCTILE-IRON PIPE 19 TABLE 51.S--(coni.) Size in. Thick ness Class Thick ness in. OD* in. Wt. of Barrel Per Ft lb Wt. of Belltf lb 18-ft Laying Length 20-ft Laying Length Wt. Per Lgth.f lb Avg. Wt. Per FtJ lb Wt. Per Lgth.t lb Avg. Wt. Per FtJ lb 16 0.34 17.40 55.8 93 1 095 0.37 17.40 60.6 93 1 185 0.40 17.40 65.4 93 1 270 0.43 17.40 70.1 93 1 355 0.46 17.40 74.9 93 1 440 0.49 17.40 79.7 93 1 530 56 0.52 17.40 84.4 93 1 610 61.0 65.8 70.6 75.3 80.1 84.9 89.6 1 210 1 305 1 400 1 495 1 590 1 685 1 780 60.4 65.2 70.0 74.8 79.6 84.4 89.0 18 0.35 0.38 19.50 19.50 64.4 69.8 111 111 1 270 1 365 70.6 1 400 76.0 1 505 70.0 75.4 0.41 19.50 75.2 111 1 465 81.4 1 615 80.8 0.44 19.50 80.6 111 1 56 1 86.8 1 725 86.2 0.47 19.50 86.0 111 i r-6J 92.2 1 830 91.6 0.50 19.50 91.3 111 1 755 97.5 t 935 96.8 56 0.53 19.50 96.7 111 1 850 102.9 2 045 102.2 20 0.36 21.60 73.5 131 0.39 21.60 79.5 131 1 455 1 560 80.8 86.8 1 600 1 720 80.0 86.0 0.42 21.60 85.5 131 1 670 92.8 1 840 92.0 53 54 55 0.45 0.48 0.51 21.60 21.60 21.60 91.5 97.5 103.4 131 131 131 1 780 1 885 1 990 98.8 104.8 110.7 1 960 2 080 2 200 98.0 1n0o4..o0 56 0.54 21.60 109.3 131 2 100 116.6 2 315 115.8 24 5S0I 0.38 0.41 25.80 25.80 92.9 100.1 174 174 1 845 1 975 102.6 109.8 2 030 2 175 101.6 J08.8 52 0.44 25.80 107.3 174 2 105 117.0 2 320 116.0 S3 54 0.47 o.so 25.80 25.80 114.4 121.6 174 174 2 23S 2 365 124.1 131.3 2 460 2 605 123.1 130.3 55 0.53 25.80 128.8 174 2 490 138.5 2 750 137.5 56 0.56 25.80 135.9 174 2 620 145.6 2 890 144.6 30 50 0.39 32.00 118.5 216 2 350 130.5 2 585 129.3 51 0.43 32.00 130.5 216 2 565 142.5 2 825 141.3 52 0.47 32.00 142.5 216 2 780 154.5 3 065 153.3 53 0.51 32.00 154.4 216 2 995 166.4 3 305 165.2 54 0.55 32.00 166.3 216 3 210 178.3 3 540 177.1 55 0.59 32.00 178.2 216 3 425 190.2 3 780 189.0 56 0.63 32.00 190.0 216 3 635 202.0 4 015 200.8 36 50 0.43 38.30 156.5 310 3 125 173.7 3 440 172.0 51 0.48 38.30 174.5 310 3 450 191.7 3 800 190.0 52 0.53 38.30 192.4 310 3 775 209.6 4 160 207.9 53 0.58 38.30 210.3 310 4 095 227.5 4515 225.8 54 0.63 38.30 228.1 310 4 415 245.3 4 870 243.6 55 0.68 38.30 245.9 310 4 735 263.1 5 230 261.4 56 0.73 38.30 263.7 310 5 055 280.9 5 585 279.2 42 50 0.47 44.50 198.9 405 51 0.53 44.50 224.0 405 52 0.59 44.50 249.1 405 53 0.65 44.50 274.0 405 54 0.71 44.50 298.9 405 5S 0.77 44.50 323.7 405 56 0.83 44.50 348.4 405 4 385 4 885 5 385 5 885 6 385 6 880 7 375 219.2 244.2 269.4 294.2 319.2 344.0 368.6 48 50 0.51 50.80 246.6 505 51 0.58 50.80 280.0 505 52 0.65 50.80 313.4 505 53 0.72 50.80 346.6 505 54 55 0U..7896 50.80 50.80 379.8 412.9 505 505 56 0.93 50.80 445.9 505 5 435 6 105 6 775 7 435 8 100 8 765 9 425 271.8 305.2 338.6 371.8 405.0 438.2 471.2 * Tolerances of OD of spigot endt 3-- 12 in., 0.06 in.; 14--24 in., 4-0.OS in., --0.08 in.; 30--48 in., 4-0.08 in., --0.06 in. ft The mechanical joint bell for 30-48 in. sizes of ductile-iron pipe have thicknesses different from those shown in ANSI A21.11 (AVVVVA Cl 11). which are based on gray-iron pipe. These reduced thicknesses provide a lighter weight bell, which is compatible with the wall thicknesses of ductile-iron pipe. The internal socket dimensions, bolt circle and bolt holes of the redesigned bell remain identical to those specified in A21.ll (AWWA Clll) to as sure interchangeability of the joint. t Including bell; calculated weight of pipe rounded off to nearest 5 lb. X including bell; average weight per foot, based on calculated weight of pipe before rounding. CTD014642 20 AMERICAN NATIONAL STANDARD Appendix This appendix is for information and is not a part of ANSI A21J1 (AWWA ClSl). TABLE A.1 Pipe Thicknesses Required for Different Tap Sites as per ANSI B2.1 for Standard Taper Pipe Threads With Two, Three, and Four Full Threads Tap SUe--in. Pipe Size in. No. of Threads i t 1 a it 2 St 3 Pipe Thickness--in. 4 i2 33 34 42 43 44 62 63 64 82 83 84 10 2 10 3 10 4 12 2 12 3 12 4 14 2 14 3 14 4 14 2 16 3 16 4 18 2 18 3 18 4 2< 2 20 3 20 4 24 2 24 3 24 4 30 2 30 3 30 4 36 2 36 3 36 4 42 2 42 3 42 4 48 2 48 3 48 4 54 2 1 454 3 54 0.18 0.26 0.33 0.17 0.25 0.32 0.17 0.25 0.32 0.16 0.24 0.31 0.(5 0.23 0.30 0.1$ 0.23 0.30 0.15 0.23 0.30 0.15 0.23 0.30 0.15 0.23 0.30 0.15 0.23 0.30 0.14 0.22 0.29 0.14 0.22 0.29 0.14 0.22 0.29 0.(4 0.22 0.29 0.14 0.22 0.29 0.14 0.21 0.29 0.21 0.29 0.36 0.19 0.27 0.34 0.18 0.26 0.33 0,17 0.25 0.32 0.(7 0.25 0.32 0.16 0.24 0.31 0.16 0.24 0.31 0.16 0.24 0.31 0.15 0.23 0.30 0.15 0.23 0.30 0.15 0.23 0.30 0.15 0.23 0.30 0.14 0.22 0.29 0.14 0.22 0.29 0.14 0.22 0.29 0.14 0.21 0.29 0.28 0.37 0.46 0.26 0.35 0.44 0.23 0.32 0.41 0.22 0.31 0.40 0.21 0.30 0.39 0.20 0.29 0.38 0.20 0.29 0.38 0.20 0.29 0.38 0.19 0.28 0.37 0.19 0.28 0.37 0.19 0.28 0.37 0.19 0.28 0.37 0.18 0.27 0.36 0.18 0.27 0.36 0.18 0.27 0.36 0.17 0.26 0.35 0.31 0.40 0.49 0.27 0.36 0.45 0.24 0.33 0.42 0.23 0.32 0.41 0.22 0.31 0.40 0.22 0.31 0.40 0.21 0.30 0.39 0.21 0.30 0.39 0.20 0.29 0.38 0.20 0.29 0.38 0.19 0.28 0.37 0.19 0.28 0.37 0.19 0.28 0.37 0.18 0.27 0.36 0.18 0.27 0.35 0.30 0.39 0.48 0.27 0.36 0.45 0.25 0.34 0.43 0.24 0.33 0.42 0.23 0.32 0.41 0.22 0.31 0.40 0.22 0.31 0.40 0.21 0.30 0.39 0.21 0.30 0.39 0.20 0.29 0.38 0.20 0.29 0.38 0.19 0.28 0.37 0.19 0.28 0.37 0.18 0.27 0.36 0.33 0.42 0.51 0.30 0.39 0.48 0.28 0.37 0.46 0.26 0.35 0.44 0.25 0.34 0.43 0.24 0.33 0.42 0.23 0.32 0.41 0.22 0.31 0.40 0.21 0.30 0.39 0.21 0.30 0.39 0.20 0.29 0.38 0.20 0.29 0.38 0.19 0.28 0.37 0.44 0.56 0.69 0.40 0.52 0.65 0.38 0.50 0.63 0.37 0.50 0.62 0.35 0.48 0.60 0.34 0.46 0.59 0.32 0.44 0.57 0.31 0.44 0.56 0.30 0.42 0.55 0.29 0.42 0.54 0.29 0.42 0.54 0.28 0.41 0.53 0.48 0.60 0,73 0.45 0.58 0.70 0.43 0.56 0.68 0.41 0.54 0.66 0.39 0.52 0.64 0.37 0.50 0.62 0.34 0.46 0.59 0.33 0.46 0.58 0.32 0.44 0.57 0.31 0.44 0.56 0.30 0.43 0.55 0.51 0.64 0.76 0.48 0.60 0.73 0.46 0.58 0.71 0.44 0.56 0.69 0.40 0.52 0.65 0.37 0.50 0.62 0.35 0.48 0.60 0.34 0.46 0.59 0.32 0.44 0.57 0.32 0.44 0.57 0.58 0.70 0.83 0.54 0.66 0.79 0.51 0.64 0.76 0.49 0.62 0.74 0.45 0.58 0.70 0.41 0.S4 0.66 0.38 0.50 0.63 0.36 0.48 0.61 0.35 0.48 0.60 0.34 0.47 0.59 CTD014643 DUCTILE-IRON PIPE 21 TABLE A.2 Pipe Thicknesses Required for Different Tap Sizes as per A WIVA CSOO for Standard Corporation Stop Threads* With Two, Three, and Four Fail Threads Pipe Size in. No. of Threads Tap Size--in. < 1u Pipe Thickset*--*. 2 3 2 0.21 0.24 0.25 0.33 3 3 0.29 0.32 0.33 0.41 3 4 0.36 0.39 0.40 0.49 2 0.19 0.22 0.23 0.30 3 0.27 0.30 0.31 0.38 4 4 0.34 0.37 0.38 0.46 6 2 0.18 0.20 0.20 0.26 3 0.26 0.28 0.28 0.34 6 4 0.33 0.35 0.35 0.42 g 2 0.17 0.18 0.19 0.24 8 3 0.25 0.26 0.27 0.32 8 4 0.32 0.33 0.34 0.40 10 10 10 2 0.17 0.17 0.18 0.23 3 0.25 0.2S 0.26 0.31 4 0.32 0.32 0.33 0.39 12 12 12 2 0.16 0.17 0.17 0.22 3 0.24 0.25 . 0.25 . 40.30 4 0.31 0.32 0.32 ` 0.38 14 `1 ' \ 0.16 vo.hr* 4 o.to ^ 14 3 0.24 0.25 0.25 14 4 0.31 0.32. 0.32 0.37 . 16 2 0.16 0.16 0.17 0.21 16 3 0.24 0.24 0.25 0.29 16 4 0.31 0.31 0.32 0.37 IS 2 0.15 0.16 0.16 0.20 18 3 0.23 0.24 0.24 0.28 18 4 0.30 0.31 0.31 0.36 20' 2 0.15 0.16 0.16 0.20 20 3 0.23 0.24 0.24 0.28 20 4 0.30 0.31 0.31 0.36 24 2 0.15 0.15 0.16 0.19 24 3 0.23 0.23 0.24 0.27 24 4 0.30 0.30 0.31 0.35 30 2 0.1S 0.15 0.16 0.19 30 3 0.23 0.23 0.24 0.27 30 4 0.30 0.30 0.31 0.35 36 2 0.14 0.15 0.15 0.19 36 3 0.22 0.23 0.23 0.27 36 4 0.29 0.30 0.30 0.35 42 2 0.14 0.14 0.15 0.18 42 3 0.22 0.22 0.23 0.26 42 4 0.29 0.29 0.30 0.34 48 2 0.14 0.14 0.15 0.18 48 3 0.22 0.22 0.23 0.26 48 4 0.29 0.29 0.30 0.34 54 2 0.14 0.14 0.14 0.17 54 3 0.22 0.22 0.22 0.25 54 4 0.29 0.29 0.29 0.34 * This thread is commonly known to the trade as the Mueller thread. 0.36 0.45 0.54 0.30 0.39 0.48 0.27 0.36 0.45 0.25 0.34 0.43 0.24 0.33 0.41 0.22 0.31 0.40 0.21 0.30 0.39 0.21 0.30 0.39 0.21 0.30 0.39 0.20 0.29 0.38 0.20 0.29 0.38 0.19 0.28 0.37 0.18 0.27 0.36 0.18 0.27 0.36 0.35 0.44 0.53 0.31 0.40 0.49 0.28 0.37 . 0.46 0.26 0.35. * P-44 V 0.25 0.34 0.43 0.24 0.33 0.42 0.23 0.32 0.41 0.23 0.32 0.41 0.22 0.31 0.40 0.21 0.30 0.39 0.20 0.29 0.38 0.20 0.29 0.38 0.19 0.28 0.37 0.19 0.28 0.36 0.39 0.48 0.57 0.35 0.44 0.53 0.32 0.41 0.50 0.30 0.39 0.48 0.28 0.37 0.46 0.27 0.36 0.45 0.26 0.35 0.44 0.24 0.33 0.42 0.23 0.32 0.41 0.22 0.31 0.40 0.21 0.30 0.39 0.20 0.29 0.38 0.20 0.29 0.38 CTD014644 3P--5X1--4/78--43151 9 7 J