Document qaL8Xk14M0ekLX18NzjwBz44G

Example of a Wall Joint Example of a Door Baffle FlG 44-11 --Design details ofjoints between different protective materials The sum of radiations through all paths ABCF and DEF to the point F should not be more than the maximum permissible dose of F man occupied area The supporting structure for the lead door or wall is assumed to be a frame of relatively X-ray transparent material From N Y State Dept of Labor, Dio of Industrial Hygiene, ` The Control of Radiation Hazards m Industry " these places to the X-ray generating room is required, a labyrinth or maze, such as indi cated in Fig 44-12, may be incorporated in the layout Since the outer wall and the door can be reached only by multiple scattered radiation and the primary beam is dissipated by having to travel a greater distance, the shielding thickness requirement for this wall and the door may be so reduced as to be an overall economy Plan supplementary electrical de vices, a necessary adjunct to the other meth ods of control Such recommended devices include Interlock switches for doors All doors or panels opening into the X-ray room should 1465