Chapter 6 .
1945 Guide
outside design temperature prevails, the latter being not an average but rather a near extreme, that is, a specified number of degrees, above the lowest temperature recorded, in the .locality involved. Therefore instead of using the aforementioned average wind velocity, it is the practice of some designers to use in all cases a wind velocity of 15 mph together with the proper design temperature. Although a 15 mph wind velocity is higher than the general average wind velocity during December, January and February in various United States cities, this and higher wind veloci ties frequently occur during periods of outside temperature corresponding to the design temperature. It should be added that this wind velocity also corresponds with that on which the heat loss coefficients in Chapter 4 are based, although the effect of variations in wind velocity on the in filtration losses is generally much greater than the effect of wind velocity on the heat loss ,by transmission through walls. Therefore, pending further investigation of this subject, either the average during December, January and February or a 15 mph wind velocity may be used at the discretion of the designer. Where the air change method is used for estimating infiltration losses, the wind velocity is not considered.
Exposure Factors: Many designers use empirical exposure factors to increase the calculated heat loss of rooms or spaces on the side or sides of the building exposed to the prevailing winds. However, according to a survey made in 1943, many Guide users have found that the use of exposure factors is not necessary as the Guide method of calculating heat losses provides an ample heat loss allowance. Therefore exposure factors may be regarded as "factors of safety" for the rooms or spaces exposed to the prevailing winds, to allow for additional capacity for these rooms or spaces, or to "balance the radiation," particularly in the case of multi story buildings. Although the exposure allowance is frequently assumed to be 15 per cent, the actual allowance to be made, if any, must to a large extent be a matter of experience and judgment of the designer, since there are at present no authentic test data available from which rules could be developed for the many conditions encountered in practice.
As stated previously, the value of U in the tables of Chapter 4 is based on a wind velocity of 15 mph and the surface resistance for this wind velocity (0.17) is sufficiently low that higher wind velocities will decrease the surfage resistance to a negligible degree and therefore have, only a slight effect on the average over-all coefficient. On the other hand, in filtration losses vary almost directly as the wind velocity as will be . apparent from the factors in Table 2 of Chapter 5. The more exact method therefore would be to differentiate among the various exposures more accurately by calculating the infiltration and transmission losses separately for the different sides of the building, using different assumed wind velocities for the infiltration losses on the various sides of the building.
AUXILIARY HEAT SOURCES
The heat supplied by persons, lights, motors and machinery should always be ascertained in the case of theaters, assembly 'halls, and in dustrial plants, but allowances for such heat sources must be made only after careful consideration of all local conditions. In many cases, these heat sources should'not be allowed to affect the size of the installation at all, although they may have a marked effect on the operation and con trol of the system. In general, it is safe to say that where audiences are involved, the heating installation must have sufficient capacity to bring the building up to the stipulated inside temperature before the audience
Heating Load Fig. 2. Elevations and Floor Plans of Residence