CHAPTER 25
1957 Guide
explained in Chapter 37, the latent heat of the moisture removed is changed to sensible heat, so that coils must be used as after-coolers to obtain the right dry-bulb temperatures. , Factory produced units are also available for use with solid adsorbents such assilica gel.
Another recent development as a manufactured item is the small re frigeration-type dehumidifying unit for the control of moisture in residential
basements.
Remote Room Units
For individual rooms, with cooling load requirements of i to I5 tons,
remote units are available in attractive casings for installation within the
Fig. 6. Self-Contained Water-Cooled Air Conditioner
Fig. 7. Self-Contained Air-Cooled Unit Air Conditioner
room. A suspended type is shown in Fig. 3 and a floor type, such as is usually installed in place of an existing radiator, is shown in Fig. 5. Furnished with chilled water from a central plant, these units offer a satisfactory method of conditioning existing offices, hotel, and apartment rooms. These units may be obtained with filters and outside air con nections, but for most satisfactory application are used as supplements to central systems that supply properly conditioned and filtered air to the
areas served.
Induction type units, using primary conditioned air under pressure to
induce local circulation, are described in Chapter 29.
Self-Contained Units
A typical large self-contained unit is shown in Fig. 6. It is essentially a remote vertical-type conditioner mounted on top of a sound-insulated enclosure containing the condensing unit.. Air distribution is obtained by means of grilles mounted in the discharge plenum, when the unit is lca"" in the conditioned area. . Duct distribution of conditioned air can he
Unit Air Conditioners and Unit Air Coolers
657.
obtained by removing the plenum, connecting directly to the blower dis charge, and safing the top of the unit.
The heat generated by the compression of refrigerant gases and that
given off by the electric motor are removed from the compressor compart ment in four ways: by the use of a water coil in the compressor compart ment ; by utilizing the cold suction gases; by drawing part of the return air through the compressor compartment, and finally by circulating room air
through the compressor compartment by means of a fan attached to the motor shaft.
Most self-contained conditioners are constructed with enough sound-
isolation material for installation directly in the conditioned spaces of the
higher-sound-level commercial-type of applications. Special sound treat
ment means are to be supplied as part of the installation when applying
these conditioners to spaces having low sound-level requirements. Con
ditioners may be installed outside the conditioned area and the connecting
supply and return-air ducts can be acoustically treated as required for the
specific installation.
-
Self-Contained Room Cooling Units
Small self-contained units can be obtained with water-cooled conden sers, but they are generally air cooled.
The air-cooled types are small in capacity, ranging from J to 1J hp. Their principal application is for conditioning such spaces as hotel rooms, offices and residential living quarters. A duct connection between the unit and an outside window or ventilated air shaft is required to permit, disposal of the heat extracted from the conditioned area. The unit may stand in front of the window or be mounted on the window sill. Various styles and types of windows encountered tend to increase the difficulty of making the window connections. The evaporation of condensate on the condenser coils, as a means of disposing of moisture, will tend to increase the condensing capacity and reduce the operating head pressure. Connections to an electrical outlet may be made through a conventional cord and plug or a permanent electrical connection, depending on local code rulings pertaining to the installation of small motors. The exterior finish of the unit in metal, wood or fabric is decorated to harmonize with office or bedroom furnishings. Some room air conditioners are being made for installation in special building openings provided in the walls as part of the initial construction.
A unit of the air-cooled condenser type for floor mounting is shown in 7. Of the two fans shown, the lower one acts as condenser, air fan,
and in some units this fan is arranged with slingers for discharging con densate on the condenser coil, while the upper fan discharges air into the conditioned area. A feature of most room air conditioners is that the condensate from the cooling coil is sprayed over the. condenser surface and vaporized, thus eliminating the need for drain connections. A simple dampering arrangement is generally provided for exhausting some air rom the room, in addition to introducing outside air and recirculating equired amounts of air. It is possible to remove the equipment for winter
orage or utilize the ventilating features for winter operation.
Controls for Room Cooling Units
in ??trol devices provided for self-contained cooling units generally will
elude all necessary means for automatic operation. Provision is so made for adding auxiliary external controls, when desired. Remote