Document q3a5DmerjaxErnGZeMzMjpVZE
Heating Ventilating Air Conditioning Guide 1938
975 hours represent a third of the summer period, cooling equipment based upon the noon average July wet-bulb of 68 F would be'inadequate. Commercial practice is to choose a wet-bulb temperature for refrigeration
design purposes which is not exceeded during more than 5 to 8 per cent of the summer hours (75 F for New York City), with somewhat lower requirements for steam turbines and internal combustion engines. This difference is made because the heaviest load on a refrigerating plant is coincident with high wet-bulb temperatures, whereas the heaviest electric
power demand occurs either in the winter or after nightfall in summer, when the wet-bulb temperature is low. Table 1, Chapter 8, shows design wet-bulb temperatures which will not be exceeded more than 8 per cent
of the time in an average summer. Knowing the hot water temperature and the wet-bulb temperature for
which the equipment must be designed, the cold water temperature must
Table 3. Efficiency of Atmospheric Water Cooling Equipment
Equipment
Spray Ponds........... ............................... Natural Draft Deck or Atmospheric
Cooling Efpxcdenct--Peb Cent
Minimum
Usual
Maximum
30 45 to 55 60 40 45 to 55 60
35 35
50 to 70 55 to 75
90 90
be chosen to place the requirement within the efficiency range of the type of atmospheric water cooling apparatus to be used. Efficiency of atmos pheric water cooling apparatus is expressed as the percentage ratio of the actual cooling range to the possible cooling range. Since the wet-bulb temperature of the entering air is the lowest temperature to which the
water could possibly be cooled this is:
Percentage cooling efficiency of atmospheric water cooling equipment =
(hot water temperature -- cold-water temperature ) X 100 hot water temperature -- wet^bulb temperature of entering air
Efficiencies of various types of atmospheric water cooling apparatus vary through wide limits, depending upon air velocity, concentration of water per square foot of area, and the type of equipment. The commercial range of efficiencies is given in Table 3 although unusual designs may
operate outside these ranges. From consideration of the factors which include the cooling range and
design wet-bulb temperature, the quantity of water required can be calculated from the amount of heat to be dissipated. The normal amounts of heat to be removed from various processes of the cooling equipment are:
Compressor refrigeration________ Condenser turbine........................... Steam jet refrigerating apparatus. Diesel engine....... ............................
. 220 to 270 Btu per minute per ton. . 950 to 980 Btu per pound of steam. .1030 to 1150 Btu per pound of steam. .2800 to 4500 Btu per horsepower.
512
Chapter 25. Spray Equipment for Humidification & Dehumidification
Cooling Ponds
A natural pond is often used as a source of condensing water. The hot water should be discharged close to the surface at the shore line. Natural air movement over the surface of the water will cause evaporation and carry away heat. Because increased density due to the loss of heat causes the cooled water to sink to the bottom of the pond, the suction connection for intake water should be placed as far below the surface as possible, and at as great a distance from the discharge as practicable.
Spray Cooling Ponds
The spray pond consists of a basin, above which nozzles are located to spray water up into the air. Properly designed spray nozzles break up the water into small drops, but not into a mist because the individual drops must be heavy enough to fall back into the basin and not drift away with the air movement. The water surface exposed to the air for cooling is the combined area of all the small drops. Since the rate of heat removal by atmospheric water cooling is a function of the area of water exposed to the air, the difference in temperature between the water and the wetbulb temperature of the air, the relative velocity of air and water, and the duration of contact of the air with the water, a much larger quantity of heat may be dissipated in a given area with the spray pond than with the cooling pond, because of (1) the speed with which the drops travel as they are propelled into the air and fall back into the water basin, (2) the increased wind velocity at a point above the surrounding structures or terrain, (3) the increased volume of air used, and (4) the vastly increased area of contact between air and water.
Spray pond efficiencies are increased by (1) elevating the nozzles to a higher point above the surface of the Water in the basin, (2) increasing the spacing between nozzles of any one capacity, (3) using smaller capacity nozzles, to decrease the concentration of water per unit area, and (4) using smaller nozzles and increasing the pressure to maintain the same concentration of water per unit area. Usual practice is to locate the' nozzles from 3 to 7 ft above the edge of the basin, to supply from 5 to 12 lb pressure -at the nozzles, using nozzles spraying from 20 .gpm to 60 gpm each and spacing them so the average water delivered to the surface of the pond is from 0.1 gpm per square foot in a small pond to 0.8 gpm per square foot in a large pond.
Increasing the pressure, spacing the nozzles farther apart, or increasing the elevation of the nozzles will increase the cross-section of spray cloud exposed to the air, and therefore increase the quantity of air coming in contact with the water. Best results are obtained by placing the nozzles in a long relatively narrow area located broadside to the wind.
Spray ponds may be located on the ground if they have an earthen or a concrete basin, or they may be placed on roofs having special waterproof roofing. To prevent excessive drift loss, or the carrying of entrained water beyond the edge of the pond by the air on the leeward side, louver fences are required for roof locations and for those ground locations where space is so restricted that the outer nozzles cannot be located at least 20 ft to 25 ft from the edge of the basin. Such fences usually are con structed of horizontal louvers overlapping so the air is forced to turn a
513