TABLE 50. VOLUME OF AIR REQUIRED FOR COMBUSTION OF DIFFERENT GASES*
Gas
BwT.U. PER Cu. Ft.
Cu. Ft. Air to Burn
Cu. Ft. Gas
B.t.u. per Cu. Ft. of Mixture
Carburetted Water Gas.......
1084 580 510 575
10.27 5.21 4.43 5.02
96.2 93.4 93.9 95.5
Thomson King, American Gas Journal, October 22, 1921.
The fact that "more air is burned".with one fuel than another does not necessarily affect the efficiency with those particular fuels; the air required varies almost directly as the B.t.u. content of the combustibles.
FUEL REQUIREMENTS FOR GAS HEATING
It is a fact, based upon experience, that the user of a gas-fired central heating appliance uses more heat during the course of a year than he does when depending upon solid fuel. The pilot light of the gas-fired furnace or boiler is lighted on the first cool day of the season. Thereafter, the system generally operates entirely under thermostatic control; upon many days when very little heat is required to keep the inside tempera ture at 70 or 72 deg.r and when it would be considered impracticable to start a coal fire, the gas-fired appliance will be working. Furthermore, the gas unit can operate at maximum capacity hour after hour, without attention; in the coldest weather, then, premises do not cool below the temperature ordinarily maintained.
Table 51 gives an approximate idea of fuel requirements in various climates, and is based upon a. heating season of seven calendar months:
TABLE 51.
FUEL REQUIREMENTS FOR RESIDENTIAL BUILDINGS FOR DIFFERENT OUTSIDE TEMPERATURES
Gas op 500 B.t.u. (Gross) per Cu. Ft.*_________________________________ __
Cu. Ft. per Square Foot of Radiation
Average Outside Temperature, October 1. to May 1
25 30 35 40 45 50 55
Water...................... 850
775
700 625 550 475 400
Vapor....................... 1080
985
890 795 700 605 510
Steam......... ............. 1380
1260
1140
1020
900
780
650
The figures are based on maintaining a temperature of 70 deg. fahr. over practically the entire house,
for 15-hr. per day. (Requirements for gases of other heating values vary inversely as the heating value; e- g., for natural
gas of 1000 B.t.u., consumption per square foot is one-half that shown in table.)
The requirements of individual installations may vary considerably from an average of several. Generally, stores, offices, factories or other commercial premises require less heat per season than do residential buildings provided with an equal amount of radiation. This is borne out on investigation of some actual installations.
94
AMERICAN SOCIETYOf HEATING &
VENTILATING ENGINEERSGBDJEflS
CONDENSATION IN VENT PIPES
An important point to care for in gas heating work is the ever present condensation resulting from the combustion of gas. To those who have had experience with gas appliances, it is hardly necessary to mention the eating out or deteriorating of the vent pipe, the water dripping from every joint, the scale and the corrosion forming at the joints.
Ordinary galvanized iron vent pipe last from six months to a year and a half at the best, but makes a messy unsatisfactory installation from the start as the water or condensation is apparent from the first day the
Fig. 49. Steam Heating Unit for House Heating Service
appliance is put into service. In many cases the, interior of this pipe is painted with acid resisting paint, and while this adds somewhat to the life of the pipe, it does not in any way tend to eliminate the condensa tion. This applies also to copper pipe. Planished iron pipe also used, but is little better than painted galvanized iron pipe.
In some cases the efficiency of the appliance has been dropped from 85 to 60 per cent, to allow for a greater heat or stack loss in an effort to vaporize and carry off the greater part of this condensation. This, how ever, is a very feeble effort to eliminate this-evil--it being entirely at the expense of the consumer.
The solution of the problem is: First, to have a minimum of con densation and, Second, to carry this off, thereby eliminating practically all of the condensation "on the job." This was accomplished recently