Document ppvjLLoGvmbrKEYGBwdrDR38D
738
CHAPTER 70
in its pressure will cause some of the refrigerant to flash into
gw* The presence of flash gas in the liquid line has several detri
mental effects: (a) it increases the pressure drop due to fric tion, and this, in turn causes further flashing; (b) it reduces the capacity of the liquid metering device, and starves the evaporator unless the device is purposely over-sized to handle the expected amount of flash gas; (c) it causes erosion of the valve pin and seat, anH creates a noticeable noise as it passes through the metering device; (d) it causes erratic con trol of the liquid refrigerant entering the evaporator.
In consideration of these potential difficulties, it is apparent that the liquid line should be designed so that the liquid en tering the liquid metering device is slightly subcooled, and troublesome flash gas is eliminated.
The liquid refrigerant as it leaves the condenser or receiver is normally at a temperature equal to or higher than the ambient temperature. Thus flashing of liquid into gas is usu ally not the result of temperature increase but rather of pres sure decrease caused by line friction and static head.
liquid leaving the condenser is also usually subcooled 5 to 10 deg, depending on type of condenser and operating con ditions. This amount of liquid subcooling will take care of a moderate amount of line friction and a small lift without ex cessive flash gas.
With a noticeable friction drop or a static bead due to ele vation of the liquid metering device above the condenser, or both, it may be necessary to resort to some means o! liquid subcooling to prevent flashing in the liquid line.
Line Subcooling Requirements
Where liquid subcooling is required this is usually accom plished in one or both of the following ways: by use of a liquid-suction heat interchanger and/or by liquid suboooling coils in evaporative condensers.
The determination ol bow much liquid subcooling is re quired to offset friction and static head losses is quite ample. At normal liquid temperatures, the static pressure loss due to elevation at the top of a liquid lift is equal to one psi for every 1.8 ft of Refrigerant 12 and 2.0 ft of Refrigerant 22.
For example, mwimA & Refrigerant 12 system having a condensing temperature of 100 F, a liquid lift of 35 ft, & pip ing friction loss of 3 psi, plus losses through valves and ac cessories totaling 7.4 psi.
Following are the calculations for the amount of liquid subcooling required under these conditions:
Pressure loss due to pipe friction Pressure less due to valve, etc.
Pressure loss due to 35 ft liquid lift 35/1.8
-- 3.Ops = 7.4 psi
*= 19.5pej
Total pressure loss in liquid line
Condensing pressure (at 100 F)
Net pressure at liquid feed valve inlet 116.9-29.9
* Saturation Temperature at 87.0 psig
29.9 psi 116.9psig
87.0 psig 82.OP
1962 Guide And Data Book
the coil to get as even distribution as possible of subcooled liquid to each valve.
Where long vertical lifts occur between evaporators on a common liquid riser it becomes difficult to completely elim inate liquid flashing, as a result of the pressure reduction due
to elevation. Ibis condition will, of course, result in poor performance and loss of capacity at the expansion devices. To make it worse it also causes unequal distribution of liquid refrigerant because the uppermost evaporators get most of the flash gas.
The liquid riser arrangement (Fig. 1) helps to correct this situation. Flash-gas formed in each section of the riser will tend to go to the nearest evaporator. This will help prevent the uppermost evaporator from getting all of the flash gas in the riser.
Since, expansion valve capacities are reduced due to gas and reduced inlet pressure, they should be oversized as directed by manufacturer's ratings, when these conditions are present.
SUCTION LINES
Design Considerations
Suction lines are the most critical from a design and con
struction standpoint. Refrigerant suction lines should be de signed:
1. To provide the correct size for a practicable pressure droo
at full load. (See Chapter 69.)
F
2. To return oil from the evaporator to the compressor under minimum load conditions.
3. To prevent liquid from draining into the compressor dur ing shutdown.
The subcooling required is equal to the condensing tem perature minus the saturation temperature at 87 psig, or 100 -82 18 F deg.
Therefore, the liquid subcooling required to prevent liquid flashing is 18 F.
Piping Arrangements
The preferred method ol running a liquid line to multiple expansion valves on a coil bank is to drop down vertically at
Whoa tofMoat liquid cubcooliny h not naMA.
Fig. 1 .... Liquid Riser Piping for Evaporators at Different Levels Above Receiver**1
Refrigerant Piping Systems for Refrigerants 12, 22 and 500
739
returned to the compressor by gravity or by entrainment with the returning gas.
OH Return Up Suction Risers
Most refrigeration piping systems contain a suction riser either because the evaporator is at a lower level than the compressor, or to minimize the possibility of liquid draining from the evaporator into the compressor during compressor
off cycles. Oil circulating in the system can be returned up gas risers
only by entrainment with the returning gas.
fig. 2____Minimum Gas Velocity for OD Entrainment in Copper Tube Suction Risers (Refrigerant 12}*
4. To prevent draining of oil from an active evaporator into an idle evaporator.
Oil Grculation in Halocarbon Type Systems
Lubricating oil is lost from reciprocating machines during normal operation because these machines are designed so that the pistons and piston rings ride on a film of oil while travers ing the cyclinder. A small quantity of this oil is continuously pushed on through the cylinders and out with the discharge gas.
Since it is inevitable that oil will leave the compressor with the refrigerant, means must be provided in systems using Refrigerants 12, 22 and 500 to return this oil at the same rate at which it leaves.
Oil which leaves the compressor reaches the condenser and there becomes dissolved with the liquid refrigerant. In this condition it readily passes through the liquid supply lines to the evaporators. In the evaporator, however, a distillation process occurs and there is almost complete separation of the oil and refrigerant. Very little oil can remain in the relatively cold and less dense refrigerant vapor at the temperature and pressure corresponding to its evaporating condition. There fore, the oil which is separated in the evaporator can only be
Minimum Gas Velocities for Oil Return Up Suction
Risers
The principal criteria determining whether or not oil can be
entrained and thereby carried up a suction riser are gas veloc
ity, gas density and pipe inride diameter. Since mass velocity is more the determining factor than
actual gas velocity only, in achieving oil entrainment, the gas
density plays an important part. At lower suction tempera
tures refrigerant gas becomes less dense and the required
minimum gas velocity necessary to entrain oil up risers is
greater than at higher suction temperatures. The mass velocity concept however, is not sufficient by
itself. The variances in tire relationship between pipe cross-
section area and wetted perimeter for the different pipe sizes
must be taken into account. The oil returning up a suction
riser usually creeps up the inner surface of the pipe. It is
therefore dependent on the
velocity of the gas at the
wall surface. The larger the pipe diameter, the greater will be
the required velocity at the center of the pipe to maintain
a given velocity at the wall surface. Other factors effecting oil entrainment are oil viscosity, oil
to refrigerant ratio in the system and oil density. However, these factors are relatively constant for the average refrig
erant system and need not be treated as variables. The curves in Figs. 2 and 3 are based on the concepts out
lined above and indicate the minimum suction gas velocities
for successful oil entrainment with Refrigerants 12 and 22 up
Type L copper tube suction risers for various suction tem
peratures and pipe sizes. The suction gas temperature shown
indicates the saturated temperature corresponding to the
compressor suction pressure. It does not represent the actual
'suction gas temperature which will usually be superheated to
some extent. It would be good practice to size suction line risers for
about 25 percent greater gas velocity than shown in Figs. 2
and 3, at lowest partial loading. Suction risers must be sized for minimum system capacity.
It is extremely important that oil be returned to the com pressor at the operating condition corresponding to the
rrriritnrum displacement and minimum suction temperature at
which the compressor will operate. For compressors with capacity control, the minimum
capacity is the lowest capacity at which the compressor can operate. For multiple compressors with capacity control the
minimum capacity is the lowest at which the last operating
compressor can run.
Riser Sizing Example I illustrates the use of Figs. 2 and 3 in establishing
maximum riser sizes for satisfactory oil entrainment down to minimum partial loading.
Example I: Determine the maximum size suction riser