CHAPTER 26
1957 Guide'
Table 22. Application of Pipe, Tube and Fittings for Heating and Air Conditioning
Application
Matebiau Commonly Used
Chilled Water Cooling Tower
Type K or L"hard copper or black steel, Schedule 40
Type K or L hard copper, wrought iron or black steel, Schedule 40
Underground Water 2-in. and smaller
2J-in. and larger
Type K, soft copper or galvanized steel, Schedule 40 (for corrosive soils, a coated steel pipe should be used)
Type K, soft copper, cast iron, Class 150 or galvanized steel, Schedule 40 (for corrosive soils, a coated steel pipe should be used)
City Water--Inside Building
Type K or L, hard copper or galvanized steel, Schedule 40
Underground Rain Water Conductors
Small Installations
Vitrified clay or cast iron soil
Under paved areas
Cast iron soil
Large Installations
8-in. and smaller
Cast iron soil XH or vitrified clay
10 to 24-in.
Vitrified clay or concrete
30-in. and larger
Concrete
5 feet outside bldg, and un Cast iron soil XH
der paving
Interior Rain Water Conductors Small Installations
Large Installations
Black or galvanized wrought iron or steel
Schedule 40
.,
Cast iron soil XH, black or galvanized
wrought iron or steel, Schedule 40
Panel Heating*
Type K or L soft copper. Black steel or wrought iron, Schedule 40
Hot Water Heating1*
Type K, hard copper or black steel, Schedule 40
Refrigerant*
Type K or L hard copper or black steel, Schedule 40
Steam Heating
Supply 90 psi and less 100 psi and over
Return Pipe All sizes
Black steel, Schedule 40, standard fittings . Black steel. Schedule 80. XH fittings
Black wrought iron or steel, Schedule 40. Standard fittings
Receiver Vent All sizes
Galvanized wrought iron or steel. Schedule
40. Standard fittings
___
Sanitary1* Small Installations Waste: lli-in. and smaller
2-in. and larger Vents:
and smaller
3-in. and larger
Galvanized wrought iron or steel, Schedule 40
Cast iron
Galvanized wrought iron or steel, Schedule 40
Cast iron
Pipe, Fittings, Welding
693
Table 22. Application of Pipe, Tube and Fittings for Heating and Air Conditioning (Concluded)
Application
Mateeiai Commonly Used
Sanitaryd (Continued) Large Installations Waste: 2-in. and larger Vents: 2-in. and larger
Gas (All kinds) All sizes
Cast iron Cast iron Black steel. Schedule 40. Malleable iron
fittings
* Panel heating copper fittings should be soldered with 95-5 solder. Steel fittings should be welded. D All underground feed and return lines buried in slab, should be equipped with fittings as outlined for panel heating. Refrigerant fittings on copper pipe must be wrought copper. All welded fittings should be long turn.
House sewer to main should be cast iron XH.
There is also the bending moment that may be caused by the flexure of the
pipe. For this chapter however, the flexure loading will not be treated
for the reason of complexity, as previously stated for the problem of ex pansion.
----------
uuuiuu
tto uKi ucoi^ncu ukj
cue ucuurng inuinniii,
(including buckling)'from the pipe, it is necessary to design the hangers or
supports for the maximum bending stress. Even with perfect support
spacing there will be some sagging; therefore, the supports should be on a
gradient if it is necessary to prevent pockets. Such a condition arises for
condensate piping.
Typical bending and deflection equations are given in Table 21 in order that supports can be properly sized, and if necessary, pitched. These
equations are typical beam equations. If more complex loadings exist, proper beam equations can be applied. Such equations are found in standard texts on mechanics of materials.
By application of the equations given in this section and the section of expansion and flexibility, it is possible to determine the proper location and type of support for straight lines. The types are anchors and hangers.
Anchors are used to guide the expansion (sliding anchors) or to fix the
pipe. They are needed to take the stress out of the line and translate the stresses to the foundations. In that way all stress can be taken out of jfe before it can be transferred to such equipment as boilers or pumps,
y means of solid anchors, the anchors can be used to divide the piping to isolated sections that cannot transmit the stresses to other sections. Hangers are used to support the piping and to take out the bending
er^pes- They are of the spring, roller, or rod type. Such types gen ii' aUow the free movement of the pipe and yet maintain full support,
he Code for Pressure Piping, ASA B31.1, has strict requirements for
materials used in hangers and supports. The structural properties
j e,a safety factor of five, and consequently there is little chance of failure e to a sudden change of load.
's. a type of support for almost every conceivable requirement. P ete information can best be obtained from a hanger manufacturer.
application of pipe, tube and fittings
In the application of pipe, tube and fittings it is necessary to comply with regulations contained in local codes and ordinances. Table 22 is