June 9, 1970
]
Zonolite Construction Products Dlv. V. R. Grace & Company 62 Whittemore Avenue Cambridge, Massachusetts 02140
Attention: Mr. Thomas P. Felt Manager, Technical Services
IT JUN 1 2 1970 CAMBRIDGE
Dear Mr. Felt:
This is in reply to your letter dated May 20, 1970. We apologize for the delay In answering; however, we did not receive the letter until June 5* 1970.
It is correct that based upon a successful fire test, the revised Mono-Kote formulation will be Listed for all existing designs presently Listed for use with Mono-Kote cementitious
material except Floor and Ceiling Design Nos. 219 - 2 Hr and 257 - 2 Hr. The use of the revised Mono-Kote for these two designs when the steel floor and form units are arranged in an alternating one-to-one pattern may be approved on an individual engineering study basis. The reason for this is that cellular steel floor units have better temperature transmission properties when compared to fluted units. Therefore, a one-to-one pattern may Jeopardize the fire resistance classification of Floor and Ceiling Design No. 219 - 2 Hr.
Very truly yours,
RMB:eJ
ROBERT M. BERHINIG Cj
Project Engineer
^