CHAPTER 1
1965 Guide And Data Book
Fig. 26 .... Basic Absorption Refrigeration Cyde with liquid Heat Exchanger and Refrigerant Precooler
absorber pressure, then the work required by the pump is:
(P, - P,)(144)(Af + 1) ft lbfi/uoit time
(SpGrof Stream 6] (62.4)
(27)
The heat equivalent is thus:
(P, - P.)(144)(A/ + 1)
9v
Btu/unit time (778) [Sp Gr.of Stream 6) (62.4)
(28)
Te determine the value of M, which is defined as the ratio of the weight of absorbing solution supplied to the absorber to the weight of refrigerant supplied to the evaporator (some times called relative pumping or relative circulation), a material balance can be made around either the absorber or generator. In the absorber material balance, note that stream 5 is one pound per unit time, stream 12 is AT pounds per unit time (by definition), and stream 6 must therefore be (Af + 1) pounds per unit time, to maintain steady-state conditions. An ab sorbent balance may be set up as follows:
Mxu - (Af + l)i,
(29)
where.
xi*. - weight fraction of absorbent in stream 12. zt " weight fraction of-absorbeot in stream 6.
Solving for Jfcf yields the expression:
. , **
M = ---------------In -- X
(30)
Equation 30 can be used to determine the numerical value of Af-if the values*# and x,i are known.
The 'expansion.'device in.the refrigerant stream located betwfeenipointe 2 and 3 is assumed to operate adiabatic&lly. During- the expansion' process, a part of liquid refrigerant at condition 2 will be evaporated to cool the refrigerant to the condition 3, but .the enthalpy will remain constant, Le., h, = ht. The same is true of. the flow of absorbent solution through the flow control device between points 11 and 12, exceptfchat, in the'latter case, there is no expansion'and no change, in temperature, assuming that the liquid heat ex
changer is sufficiently large to cool the stream of absorbent
solution to a temperature equal to or below its equilibrium
temperature at the absorber pressure.
In the foregoing discussion, it was assumed that sufficient
date are available to evaluate the enthalpy of all the streams
of fluids in the cycle. In order to design thesystem, however, it
is necessary to set up specifications and make certain as
sumptions regarding operating conditions' ami equipment
effectiveness. Then the heat and material balances can be
made; impossible or impractical assumptions will become
obvious and subsequent assumptions must be modified ac
cordingly.
/
Example 10 illustrates the application of this procedure-
.Example 10: Determine the conditions in a water-lithium bromide system that might be practical for a refrigeration ma chine to be used for air conditioning, if cooling water is available
at 75 F and the required evaporator temperature is 40 F. Solution: In order te be able to proceed with the calculations,
certain assumptions are required. These assumptions are:
1. The absorbent solution leaves the absorber in equilibrium
- with the vapor and at a temperature of 80 F. 2. The absorbent solution enters the absorber at a concentra
tion of 57 percent lithium bromide, and has been cooled in the liquid neat exchanger to within 10 F of the temperature
of the solution leaving the absorber. 3. The condensing temperature is 100 F.
4_ The vapor leaving the precoolcr is warmed te within 10 F of the temperature of the liquid refrigerant leaving the condenser.
From the p-tr-x chart for the water-lithium bromide system, Figure 20, determine that the evaporator pressure is 6.5 mm Hg
at 40 F. Next, from assumption 1, determine that tee concentra tion of the solution having a vapor pressure of 6.5 mm at 80 F
is 50.8 percent lithiumbromide. Then using Equation 20, calculate
Fig. 27 .... Basic Absorption Refrigeration Cyde with Rectifier Added
Thermodynamics and Refrigeration Cycles
Table 3 .... Conditions in Cyde of Example 10
Point
7 8 9 10 12
Temp, f
100 77 40 40 90 80 80 145 170 . 170 90 90
Pressure
mwHg
51 51
6.5 6.5 6.5 6.5 51 51 51 51 51 6.5
Weight Fraction ' . UBr
0.0 0.0 0.0 0.0 0.0 0.508 0.508 0.508 0.0 0.570 0.570 0.570
nfha!pyh
tht/lb
67.9 45.3 45.3 1077 1100 -76 -76 -43 1135 -38 -75 -75
TV
Flow H
lb/ unit time
1.0 1.0 1.0 1.0 1.0 9.19 9.19 9.19 1.0 8.19. 8.19 8.19
..Heal Flow, Stv/uoit time.
67.9 ' " - . ,45-3 ' . - . 45.3 --
.1077. . 1102 -698 -- 698. ' -395 - 1136 -312 -615 -615
the ratio of entering absorbent liquid to refrigerant as follows:
0J508 M ------ -----------8.19
0.570 - 0.508
On the basis of &ssumption 3, determine from Fig. 20, that the
pressure, and hence the generator pressure, is 51 mm
Hg. Then determine that the generator temperature (the tem
perature at which tee 57 percent lithium'bromide solution exerts
a vapor pressure of 51 mm Hg) is 170 F.
As these values are obtained, they can be placed in a table such
as Table 3.
Next find the enthalpy of stream 1-to be 67.9 Btu/lb (Steam
Tables).? Also find enthalpy of saturated water vapor at 40 F to
be 1077 Btu/lb, point 4. Determine that the enthalpy of vapor of
stream 9, at a pressure of 51 mm and superheated to 170 F, is 1136
Btu/lb.
:
Through tho precooler, the water vapor from the evaporator is
heated from 40 .to 90 F (assumption *4). At this low pressure tho
value of c, for the' water vapor is essentially constant at 0.453.
Therefore, the increase of vapor enthalpy is. 0.453 .(90 -- 40)
-- 22.6 Btu/lb'. Thus, the enthalpy of the vapor'at point 5 is 1100
Btu/lb and the enthalpy of the liquid refrigerant stream at points
2 and 3 is 453. Btu/lb. From the Steam Tables, determine that
the temperature of stream 2 is approximately 77 F.
From the enthalpy chart for lithium bromide solutions, Fig. 22,
determine tho enthalpy of stream 6 to be -- 76 Btu/lb. Also de-
Rg. 28 .... Basic Absorption Refrigeration Cyde for Cyde Analysis
termine enthalpy of stream 10 to be. -- 38 Btu/lb. Then deter mine the enthalpy of stream 11 at 90 F (assumption 2) to be -- 75 Btu/lb. Then by Equation 25, calculate the enthalpy of-stream-8c
?. - 8.19 (Au - Au) - 9.19 (A# -- Ay) , 9.19 A* = -- 395
A, - - 43
Then, from Fig. 22, determine tee approximate temperature df
stream 8 to be 145 F. Complete Table;3 -by filling in the last column.
Applying Equations 21,22, 23, and 24
q. - 1077 - 45 - 1032 Btu
698 - 1102 + 615 = -1185BU1
9, = 395 - 312 +.1136 - 1219 Btu . *
- g. - 67.9 - 1136
1068
.
,
From Equation 28, evaluate q, -- 0.016 Btu/unit time; tee
heat energy required to pump the solution is so
that,it can
be neglected. Therefore, the overall beat balance can be'made as
follows:
' -1"
'
. + &- 1032 + 1219' - 2251 :Btu . c - q, - - 1185 - 1068 - - 2253 Btu
The coefficient of performance for the assumed system can be evaluated thus:
(CP) 9*
1032 0.847
1219
The foregoing analysis has ignored heat losses from the system and heat leakages between various parts of the system in order
to keep the presentation relatively simple and straightforward. Such neat losses would, of course, tend to lower the value of the
CP. However, in a well designed piece of equipment, the effect of heat losses is a minor one.
Additional Reading
For those desiring more detailed information on absorption refrigeration, Reference 33 provides a thermodynamic de scription of the absorption cooling process, an evaluation of the properties and requirements of the absorbent-refrigerant combinations, a compilation of pertinent data, and a good reference list
A more extensive coverage of the subject can be found in Reference 40.
REFERENCES
1S. R. DeGroot: Thermodynamics of Irreversible Processes (Interecienee Publishers, New York, 1951).
* G. J. VanWylen: Thermodynamics (John Wiley A Sons, New York, 1959).
1 O. A. Hougen, K. M. Watson, and R. A. Rugate: Chemical Process Principles (John Wiley A Sons, New York, 1959).
4F. W. Sears: Thermodynamics (Addison-Wesley Publishing Co., Inc., Reading, Mass., 1956).
1 J. F. Lee and F. W. Seare: Thermodynamics (Addison-Wealey Publishing Co., Inc., Reading, Mass,, 1963).