Document ppjMv4wVQRGyM9wdOJYBpd2yj

18 CHAPTER 1 1965 Guide And Data Book Fig. 26 .... Basic Absorption Refrigeration Cyde with liquid Heat Exchanger and Refrigerant Precooler absorber pressure, then the work required by the pump is: (P, - P,)(144)(Af + 1) ft lbfi/uoit time (SpGrof Stream 6] (62.4) (27) The heat equivalent is thus: (P, - P.)(144)(A/ + 1) 9v Btu/unit time (778) [Sp Gr.of Stream 6) (62.4) (28) Te determine the value of M, which is defined as the ratio of the weight of absorbing solution supplied to the absorber to the weight of refrigerant supplied to the evaporator (some times called relative pumping or relative circulation), a material balance can be made around either the absorber or generator. In the absorber material balance, note that stream 5 is one pound per unit time, stream 12 is AT pounds per unit time (by definition), and stream 6 must therefore be (Af + 1) pounds per unit time, to maintain steady-state conditions. An ab sorbent balance may be set up as follows: Mxu - (Af + l)i, (29) where. xi*. - weight fraction of absorbent in stream 12. zt " weight fraction of-absorbeot in stream 6. Solving for Jfcf yields the expression: . , ** M = ---------------In -- X (30) Equation 30 can be used to determine the numerical value of Af-if the values*# and x,i are known. The 'expansion.'device in.the refrigerant stream located betwfeenipointe 2 and 3 is assumed to operate adiabatic&lly. During- the expansion' process, a part of liquid refrigerant at condition 2 will be evaporated to cool the refrigerant to the condition 3, but .the enthalpy will remain constant, Le., h, = ht. The same is true of. the flow of absorbent solution through the flow control device between points 11 and 12, exceptfchat, in the'latter case, there is no expansion'and no change, in temperature, assuming that the liquid heat ex changer is sufficiently large to cool the stream of absorbent solution to a temperature equal to or below its equilibrium temperature at the absorber pressure. In the foregoing discussion, it was assumed that sufficient date are available to evaluate the enthalpy of all the streams of fluids in the cycle. In order to design thesystem, however, it is necessary to set up specifications and make certain as sumptions regarding operating conditions' ami equipment effectiveness. Then the heat and material balances can be made; impossible or impractical assumptions will become obvious and subsequent assumptions must be modified ac cordingly. / Example 10 illustrates the application of this procedure- .Example 10: Determine the conditions in a water-lithium bromide system that might be practical for a refrigeration ma chine to be used for air conditioning, if cooling water is available at 75 F and the required evaporator temperature is 40 F. Solution: In order te be able to proceed with the calculations, certain assumptions are required. These assumptions are: 1. The absorbent solution leaves the absorber in equilibrium - with the vapor and at a temperature of 80 F. 2. The absorbent solution enters the absorber at a concentra tion of 57 percent lithium bromide, and has been cooled in the liquid neat exchanger to within 10 F of the temperature of the solution leaving the absorber. 3. The condensing temperature is 100 F. 4_ The vapor leaving the precoolcr is warmed te within 10 F of the temperature of the liquid refrigerant leaving the condenser. From the p-tr-x chart for the water-lithium bromide system, Figure 20, determine that the evaporator pressure is 6.5 mm Hg at 40 F. Next, from assumption 1, determine that tee concentra tion of the solution having a vapor pressure of 6.5 mm at 80 F is 50.8 percent lithiumbromide. Then using Equation 20, calculate Fig. 27 .... Basic Absorption Refrigeration Cyde with Rectifier Added Thermodynamics and Refrigeration Cycles Table 3 .... Conditions in Cyde of Example 10 Point 7 8 9 10 12 Temp, f 100 77 40 40 90 80 80 145 170 . 170 90 90 Pressure mwHg 51 51 6.5 6.5 6.5 6.5 51 51 51 51 51 6.5 Weight Fraction ' . UBr 0.0 0.0 0.0 0.0 0.0 0.508 0.508 0.508 0.0 0.570 0.570 0.570 nfha!pyh tht/lb 67.9 45.3 45.3 1077 1100 -76 -76 -43 1135 -38 -75 -75 TV Flow H lb/ unit time 1.0 1.0 1.0 1.0 1.0 9.19 9.19 9.19 1.0 8.19. 8.19 8.19 ..Heal Flow, Stv/uoit time. 67.9 ' " - . ,45-3 ' . - . 45.3 -- .1077. . 1102 -698 -- 698. ' -395 - 1136 -312 -615 -615 the ratio of entering absorbent liquid to refrigerant as follows: 0J508 M ------ -----------8.19 0.570 - 0.508 On the basis of &ssumption 3, determine from Fig. 20, that the pressure, and hence the generator pressure, is 51 mm Hg. Then determine that the generator temperature (the tem perature at which tee 57 percent lithium'bromide solution exerts a vapor pressure of 51 mm Hg) is 170 F. As these values are obtained, they can be placed in a table such as Table 3. Next find the enthalpy of stream 1-to be 67.9 Btu/lb (Steam Tables).? Also find enthalpy of saturated water vapor at 40 F to be 1077 Btu/lb, point 4. Determine that the enthalpy of vapor of stream 9, at a pressure of 51 mm and superheated to 170 F, is 1136 Btu/lb. : Through tho precooler, the water vapor from the evaporator is heated from 40 .to 90 F (assumption *4). At this low pressure tho value of c, for the' water vapor is essentially constant at 0.453. Therefore, the increase of vapor enthalpy is. 0.453 .(90 -- 40) -- 22.6 Btu/lb'. Thus, the enthalpy of the vapor'at point 5 is 1100 Btu/lb and the enthalpy of the liquid refrigerant stream at points 2 and 3 is 453. Btu/lb. From the Steam Tables, determine that the temperature of stream 2 is approximately 77 F. From the enthalpy chart for lithium bromide solutions, Fig. 22, determine tho enthalpy of stream 6 to be -- 76 Btu/lb. Also de- Rg. 28 .... Basic Absorption Refrigeration Cyde for Cyde Analysis termine enthalpy of stream 10 to be. -- 38 Btu/lb. Then deter mine the enthalpy of stream 11 at 90 F (assumption 2) to be -- 75 Btu/lb. Then by Equation 25, calculate the enthalpy of-stream-8c ?. - 8.19 (Au - Au) - 9.19 (A# -- Ay) , 9.19 A* = -- 395 A, - - 43 Then, from Fig. 22, determine tee approximate temperature df stream 8 to be 145 F. Complete Table;3 -by filling in the last column. Applying Equations 21,22, 23, and 24 q. - 1077 - 45 - 1032 Btu 698 - 1102 + 615 = -1185BU1 9, = 395 - 312 +.1136 - 1219 Btu . * - g. - 67.9 - 1136 1068 . , From Equation 28, evaluate q, -- 0.016 Btu/unit time; tee heat energy required to pump the solution is so that,it can be neglected. Therefore, the overall beat balance can be'made as follows: ' -1" ' . + &- 1032 + 1219' - 2251 :Btu . c - q, - - 1185 - 1068 - - 2253 Btu The coefficient of performance for the assumed system can be evaluated thus: (CP) 9* 1032 0.847 1219 The foregoing analysis has ignored heat losses from the system and heat leakages between various parts of the system in order to keep the presentation relatively simple and straightforward. Such neat losses would, of course, tend to lower the value of the CP. However, in a well designed piece of equipment, the effect of heat losses is a minor one. Additional Reading For those desiring more detailed information on absorption refrigeration, Reference 33 provides a thermodynamic de scription of the absorption cooling process, an evaluation of the properties and requirements of the absorbent-refrigerant combinations, a compilation of pertinent data, and a good reference list A more extensive coverage of the subject can be found in Reference 40. REFERENCES 1S. R. DeGroot: Thermodynamics of Irreversible Processes (Interecienee Publishers, New York, 1951). * G. J. VanWylen: Thermodynamics (John Wiley A Sons, New York, 1959). 1 O. A. Hougen, K. M. Watson, and R. A. Rugate: Chemical Process Principles (John Wiley A Sons, New York, 1959). 4F. W. Sears: Thermodynamics (Addison-Wesley Publishing Co., Inc., Reading, Mass., 1956). 1 J. F. Lee and F. W. Seare: Thermodynamics (Addison-Wealey Publishing Co., Inc., Reading, Mass,, 1963). !'c i