CHAPTER 46
1958 Guide
Process and Product Air Conditioning'1'
i
1147
Table 1. Temperatures and Humidities Applicable to Industrial Air
Conditioning--(Continued)
Table 1. Temperatures and Humidities Applicable: to'Industrial Air
Conditioning--(Continued)
Process
| Temp.* F
FOUNDRIES
Mold making: * Winter design temp.
60 to 70
60 to 70 55 to 65
40 40 to 50 55 to 65
The charging room is usually unhe&ted.
In core making fume exhaust hoods are required for oven and for cooling areas adjacent to ovens.
In mold making provide hoods at transfer points with wet collector dust removal system. Use 600 to 800 cfm per hood.
Pouring rooms require two-speed powered roof ventilators. Design for minimum of two cfm per sq ft floor area at low speed. Shielding is required to control radiation from hot surfaces. Proper introduction of air will minimize preheat requirements.
In shakeout room provide hoods with wet collector dust removal system. Exhaust 400 to 500 cfm per sq ft grate area. Roof ventilators are generally not effective.
In cleaning room provide hoods for grinders and cleaning equipment with dry cyclones or bag type col lectors.
Winter ventilation (preheated) is required to the extent of replacing exhausted air. Summer-ventilation is usually supplemented by use of pedestal fans.
Spot coolers are sometimes used in larger installations.
Rooms
| Temp, f"
R.H. %
LIBRARIES AND MUSEUMS
Museum......................................................
70-80 70-80
40-50 40-50
8.5S?9.0pH.dehUmidifierS U"d * elimiaat<! Sl Water treatment & essential to maintain between
Reheat is usually needed for refrigeration eyde due to the low sensible heat load.
-- -
In extremely cold weather a lower relative humidity is required to prevent condensation bn wallsl'
Positive high and low limit relative humidity controls are used. Do not locate water or steam piping ere leakage can cause damage.
Check Figures for Cooling Estimates:
S
Square feet floor area per person......... ................ Watts per sq ft of floor area............... Room sensible heat. Btu ner rtirUan ftb Grand total heat, Btu per (hr) (aa ft). Sensible heat factor...................... Cooling load per person, tons . cfm per sq ft of floor area................
Low 40 20
Medium
60
. .High .
" so
45 ;`75
'
; 2.io:
! fJ
|i
Process
Temp. F
R.H. %
|= FUR
1'
Drying......... ................................................................................
110
!)
Shock treatment..........................................................................
18 to 20
|?
Storage...........................................................................................
40 to 50
55 to 65
MALTING (BREWING) Steeped 24 to 72 hr in 45 to 65 F water.
Germinated six days at 55 to 75 F.
Kilned at temperatures of 120 to 175 F.
Shock treatment, for eradication of any insect infestations, requires the lowering of the temperature to 18-20 F for 3 to 4 days, then raising it to 60-70 F for 2 days, then lowering it once again to 18-20 degrees for 2 days and raising it to the storage temperature.
Furs remain pliable, oxidation is reduced and color and luster are preserved when stored at 40 to 50 F.
Mold growth is prevalent with humidities above 80 percent, while hair splitting is common where hu midity is lower than 55 percent.
vrctuuuatea twenty days at od if'. Germination produces total heat of 16.000 Btu/buabel at varying rate depending upon grain and proceaa.
___ Process
Temp. F 1 R.H. %
Process
Temp. F
R.H. %
MATCHES
LEATHER
Manufacture ...................................
....................................
72 to 74
50 40
| Drying:
70
120 50-60
75 45 40-60
50 Tl,, eJaPorated is 18 to 20 lb per million matches simultaneously with the setting of the glue.
match machine will turn out about 750,000 matches per hour.
Ij .
! After leather is moistened in preparation for rolling and stretching, it is placed in an atmosphere held at
ij room temperature with a relative humidity of 95 percent.
I1
Leather is usually stored in warehouses without temperature and humidity control. However, it
_____
Process
necessary to keep humidity below 85 percent to avoid mildew.
Temp. F
R.H. %
Air filtration is recommended for toggle machines.
-------------------------
MUSHROOMS
Process
Temp. F
R.H. %
.................................................................. |
120 to 140 60 to 75
48 to 60
nearly sat. moderate
LENSES (OPTICAL) Grinding.......................................................................................
75 80
45 80
The air must be free of dust and temperature held constant.
To acquire desired cleanliness of air a combination of impingement and electrostatic filters are Dust collectors are required for grinding operations.
As spawn starts to grow, it is necessary to abruptly cool the mushroom house by 15 deg is a 12 hr penod (approx.). Usually, this is the controlling factor in selection of refrigeration equipment, unless there is portable equipment available for such a purpose.
Ductwork is usually of wood, due to the deterioration of ferrous metals during sweating-out period.
Air filtration is essential in spawn rooms. Viscous filters are preferred, as mold spores are trapped in the *oous film. Odorless oil should be used.
Heat of emission is 4 Btu per (hr)(sq ft of growing surface).