HEATINC VENTILATING AIR CONDITIONING GUIDE 1940
Table 4. Summary Of Heat Losses Of Uninsulated Residence Heat losses given in Btu per hour
_Room ob Space
Walls
Ceiling and .Roof
Floor
DooaGlass and
Infiltration
Totals
Bedroom A 1 ' ` 5330
Bedroom B------ 3490
Bedroom C
2560
Bedroom D
2)650
Bathroom 1
670
Bathroom 2
1770
Living Room
7260
Dining Room . 3720
Kitchen .
2850 '
Lavette
3000
Entrance Hall
870
Garage
-1030*
Recreation .t:. 3850
Totals |
36,990
Percentages
40.2
6660 4400 3300 3300 1510
960
2490
22,620 24.6
960 310
--2450f : 4600
3,420 3.7
1440 1440 970 720 500 320 1800 3880 950 1100
640 3410
720
17,890
19.5
.. *WaU tieat.loss of 2110 Btu.minus .wall heat gain of 3140 Btu.
tHeat gains; 960, 310 and 1180 Btu.
v
1010 1010
500 500 500 420 1120 870 760 530 560 2700 490
10,970
12.0
14,440 10,340 7,330 8,130 3,180
3,780 10,180 8,470
4,560 4,630 4,560 2,630 9,660
91,890 -
100.0
Table 5. Summary of Heat Losses of Insulated Residence Heat losses given in Btu per hour
Room ob Space
Walls
Ceiling and Roof
Floor .
Glass and Door Inpiltbati'on
Totals
Bedroom A Bedroom B Bedroom C Bedroom D Bathroom 1 Bathroom 2 Living Room Dining Room Kitchen Lavette Entrance HaH Garage Recreation
Totals
Percentages
2670 1750 1280 1320
340 820 3580 1860 1400 1460 440 -400* 1430
17,950.
32.5
2370 1570 1170 1170
540 340
690 220
850 ------- 8,010 14.5
--2090f 1580
400
0.7
1440 1440
970 720 500 320 1800 3880 950 1100 640 3410 720
17,890
32.4
1010 1010
500 500 500 420 1120 870 760 530 560 2700 490
10,970
19.9
7,490 5,770 3,920 4,400 1,880 2,120 , 6,400 6,610 3,110 3,090 2,490 3,620 4,220
55,220
100.0
Wall* heat loss of 1050 Btu minus'wall* heat gains of 590. 320 and 540 Btu. tHeat gains; 690. 220 and 1180 Btu.
140
Chapter 8
COOLING LOAD
Conditions of Comfort, Design Outside Temperatures, Com ponents of Heat Gain, Normal Heat Transmission, Solar Heat Transmission, Sun Effect Through Windows, Heat Emission of Occupants, Heat Introduced by Outside Air, Heat
Emission of Appliances
LOAD calculations for summer air conditioning are more complicated than heating load calculations because there are more factors to be considered. Due to the variable nature of some of the contributing load components and the fact , that they do not necessarily impose their maximum effect simultaneously, considerable care must be used in determining their phase relationship so that equipment of proper capacity may be selected to maintain specified indoor conditions.
The conditions to be maintained in an enclosure are variable and depend upon several factors, especially the outside design conditions, duration of occupancy and relationship between air motion, dry-bulb and wet-bulb temperatures. Information concerning the proper effective temperature to be maintained is given in Chapter 3,. where are also tabu lated the most desirable indoor conditions to be maintained in summer for exposures over 40 min (see Table 5, Chapter 3).
Summer dry-bulb and wet-bulb temperatures of various cities are given in Table 1. The temperatures are not the maximums but the design temperatures which should be used in air conditioning calcu lations. The maximum outside wet-bulb temperatures as given in Weather Bureau reports usually occur only from 1 to 4 per cent of the time, and they are therefore of such short duration that it is not practical to design a cooling system for them. The temperatures shown in Table 1 are based on available design conditions known to be successfully applied.
COMPONENTS OF HEAT GAIN
A cooling load determination is composed of five components which are classified in the following manner:
1. Normal heat transfer through windows, walls, partitions, doors, floors, ceilings, etc.
2. Transfer of solar radiation through windows, walls, doors, skylights, or roof.
3. Heat emission of occupants within enclosures.
4. Heat introduced by infiltration of outside air or controlled ventilation.
5. Heat emission of mechanical, chemical, gas, steam, hot water and electrical appliances located within enclosures.
141