CHAPTER 36____________
1946 Guide
, used when equipment is outside of the conditioned area. The problem of securing a supply of outside air is often a difficult'one. The proper design of ducts is of major importance for good air distribution. Chapters 40 and 41. are "devoted to these subjects.
In the analysis of any large structure to be air conditioned which is divided into small spaces, such as an office building or hotel, a comparison should be drawn between the use of units and a central plant system. This study is one of economics, and should include, such factors as first cost, installation costs, obsolescence, depreciation, maintenance costs, return on investment, flexibility, time of installation and possible loss of useful space during installation.
This same , analysis should be extended to include a comparison of remote units with self-contained units. Self-contained units are possible where short term leases are involved, or where wiring can readily be brought to location or where existing water and drain facilities are adequate to handle the increased demand of water-cooled models. On
Fig. 7. Remote Floor Type Room Unit Air Conditioner
the other hand, remote type room units contain less mechanical ma' chinery, avoid the operating cost penalty of an air-cooled condenser, as
in the.case of the self-contained, air-cooled room units, and seldom require heavy wiring to handle the fan load. In general, the smaller remote units are more suitable for use with new: construction, where the units will probably remain during their useful life. This condition may change where larger, ceiling mounted units are compared with the floor mounted self-contained units. Controls are essential in unit application and range from the simple snap switch of a room unit to elaborate means of control ling temperature, humidity and air movement in laboratory and testing room application: The criterion of a well controlled, installation is one which has neither too few nor too many controls. (See Chapter 34.)
With the expansion of cities during the past decade, the problem of water supply has become a costly and ever present problem6. Con sequently, laws are appearing designed to restrict the usage of water wherever possible, particularly when substitute means tire available. . Evaporative condensers Eind cooling towers (described in Chapters 37 and 39) are means devised to save large quantities of water in: this connection.'
, ,Unit Air Conditioners Unit Air Coolers Attic Fans
63S
Tablb`1.: Standard Rating, Basis for. Self-Contained Air Conditioning Units
Functions
Types of Units
Item
Rating Condition
Description,
Value
All Cooling
All a
Water-Cooled, Air-Cooled and. Evaporatively Cooled
Condensers
b c
Water-Cooled d
e
Barometric Pressure '
29.92 in. Hg.
Unit Ambient and Air Entering Room--Air Inlet (1) Dry-Bulb (2) Wet-Bulb -
80 F 67 F
Ventilation Air
See Note
Water Temperature Entering Unit
75 F
Water Temperature Leaving Unit
95 F
Air-Cooled f Air Entering Outside Air Inlet
and Evapora-
(1) Dry-Bulb
tively Cooled
(2) Wet-Bulb
Condensers
95 F 75 F
Heating
g
All Types Provided with Heating
Function - -
h
Unit Ambient and Total Air Enter ing Unit
70 F
Heating Medium, Pressure or Temperature (1) Dry Saturated Steam
(2) Water In (3) Water Out
16.7 lb per sq in. abs.
180 F 160 F
All Types i Unit Ambient
70 F
Humidifying Humidifying Function
Total Air Entering Unit(1) Dry-Bulb (2) Wet-Bulb
70 F 53 F
Air ' Circulation
ah k Filters
New and Clean
Note: Rating shall be based on both ventilation and recirculated room air entering at 80 F dry-bulb
nd 67 F wet-bulb temperature. (The Note as given in the code has been condensed in order to remove
material not pertinent to this chapter).
^
Most manufacturers furnish equipment designed for use in combination
with these water savers.
-
Municipal plumbing, heating, electrical and refrigeration codes, as well as fire underwriter restrictions, are likewise having their effects on the application of unit, air conditioners. Meeting municipal and national code requirements should be an important item in connection with the installation of tmy unit equipment.
Ratings
There are two codes governing the rating and testing of unit air con-, ditioners. The .first code, Standard Method of Rating-and Testing Air Conditioning Equipment \ covers all types of air conditioning units except the self-contained type. The latter is covered by the second, code, The, Standard Method of Rating and Testing Self-Contained Air Conditioning Units for Comfort Cooling *. The two codes Eire necessary because of the basic difference caused by the heat given,up by the self-contained, units.