434 CHAPTER 23 1946 Guide ' tables are based on Babcock's formula, and have been used as the. basis of design for a number of years.- Capacities at other pressures may be ' computed by means of Table 1. ' The steam lines can be sized for greater pressure drops than the return piping. For a system using steam at 30 psi pressure, the total pressure drop can be 5 to 10 psi, and for 150-psi systems 25 to 50 psi. It has been observed that the maximum pressure in the returns of a 30-psi system is about 5 psi, and that of a 150,-psi system is about 20 psi. The pressure in the return mains is, of course, caused by the discharge of traps, or by leaky traps and by flashing due to the lower pressure in the return line. The total pressure drop in the returns can be approximately 2 psi for the 30-psi returns, and about 10 psi for the 150-psi returns. The usual practice in the sizing of high pressure returns has been to size on the basis of x/l psi per 100 ft of pipe for 30-psi systems, and 1 psi per 100 ft for 150-psi systems. This is an average figure which corresponds generally to several of the previously published tables for the design of high pressure return piping. . ` The returns generally discharge to a vented receiver. It is, of course, necessary to provide for the elimination of air from high pressure systems, . the same as in low pressure systems. If possible, it is desirable to design the system so as to condense some of the steam escaping through the vents by passing it through a heat exchanger. When high pressure steam is being supplied and lower steam pressures are required for heating, for domestic hot water, for utility services, etc., one or more pressure reducing valves (pressure regulators) are required. These are used in two classes of service, one where the steam must be shut off tight to prevent the low pressure building up at time of no load, and the other where the low pressure lines will condense enough steam to offset normal leaking through the valve.- In the latter case, double seated -valves may be used in a manner that reduces the work required of the diaphragm in closing the valve and consequently the size of the dia phragm. These valves also control .the low pressures more closely under conditions of varying high pressures. . Valves that shut off all steam are called dead end type. They are single seated, and some of them have pilot operation that provides close control of the reduced pressure. If a thermostatically controlled valve is installed 'after, and near, a reducing valve in such a manner as to cut off the passage of steam, the dead end type should be used. ~ , It is common practice when the initial steam pressure is 100 psi or higher tp install two-stage reduction. If the radiation served is cast-iron, the A.S.M.E. code requires two reducing valves when the inlet pressure exceeds 50 psi. This makes a quieter condition of steam flow, as it is apparent that with one reduction, as for example from 150 to 2 psi, there is a smaller opening with greater velocity across the reducing valve and, consequently, more noise. A two-stage reduction also introduces a source of safety, since if one reducing valve were to build up its discharge pressure, this excess' pressure would not be so great as the case might be in a one-stage-reduction. '.If an installation requires single seated valves and the pilot type cannot be used, it is necessary to use two-stage reduction, as single seated . valves. require sufficient diaphragm area to overcome the unbalanced . pressure underneath the single valve. In many cases the large diameter Steam Heating Systems and Piping 435 of diaphragm required would make it"impractical in construction. With a two-stage reduction the diaphragm diameter required would be reduced. If a one-stage reduction is desired, it is necessary to use a pilot controlled pressure reducing valve, where low pressures are to be maintained closely. In making a two-stage reduction, allowance for expansion of steam on the low pressure side of the valve should be made by increasing the pipe size. This also allows steam flow to be at a more nearly uniform velocity. Separating the valves by a distance up to 20 ft is recommended to reduce excessive hunting action of. the first valve. \ When the reduced pressure is approximately 15 psi or lower, the weight and lever diaphragm valve gives the best results with minimum main tenance. Above 15 psi, spring loaded diaphragm valves should be used; because of the extra weights required on weight and lever type. Pressure, equalizing lines should not be connected too close to the valve. They should be connected into the bottom of the reduced pressure steam main, to allow maximum condensation to exist in the equalizing lines, or the connection can be made into the top of the main if a water accumulator is used to reduce the variation of the head of water on the diaphragm. - Care should be exercised in selecting the size of a reducing valve. The safest method is to consult the manufacturer. It is essential that sizes of piping to and from the reducing valve be such that they will pass, the desired amount of steam with the maximum velocity desired. A common error, is. to make the size of the reducing valve the same size as that of the service, or outlet pipe size. Generally,'this will make the reducing valve oversized, and bring about wire-drawing of valve and seat, due to small lift of the valve seat. On installations where the steam requirements are relatively large and variable in mild weather or reduced demand periods, "wire-drawing may occur. To overcome this condition, two reducing valves are installed in parallel, with the sizes selected' on a 70 and 30 per cent proportion of maximum flow. For example, if 50,000 lb of steam per hour are required, the size of one valve is on the basis of 0.7 X 50,000 lb, or 35,000 lb, and the other on the basis of 0.3 X 50,000 lb, or 15,000 lb. During the mild or reduced demand periods, steam will flow through the smaller valve only. During the remainder of the season, the.larger valve is set to control at whatever low pressure is desired, and the smaller one at a somewhat lower pressureV' Thus, when, steam flow is not at its maximum, the smaller valve is closed, but it opens automatically when the maximum steam demand occurs, because this maximum demand creates a slight pressure drop in the service line. . The installation of reducing valves in pipe lines requires detailed planning. They should be installed to give ease of access for inspection and repair, and wherever possible with diaphragm downward, except in cases of pilot operated valves. , There should be a by-pass around each reducing valve of size equal to one-half the size of reducing valve. The globe valve in by-pass line should be of a better type of construction, and must shut off absolutely tight: A steam pressure gage, graduated up tp the initial pressure, should be installed on the low pressure side. Safety valves located on the low pressure side should beset 5 psi higher than the final pressure but may be 10 psi higher than the reduced pressure if this reduced pressure is that of the first stage reduction of a double reduction. Strainers are sometimes installed on the inlet to the reducing valve but are not required before a1 second-stage reduction. If a twoTstage reduction is made, it. is well to