594 CHAPTER 39 1960 Guide directly to the heat exchanger is regulated by valve V-5. All of the chilled water eventually returns to heat exchanger where it picks up heat from the warmer well water. During periods when the predominant requirement is for cooling, water from the heat exchanger is circulated through the ventilating coil and valve V-3 to the condenser where it picks up heat from the refrigerant. Depending on the simul taneous beating load that exists, some, or all, of the water pmsps through valve V-6 and is returned to the heat ex changer where it dissipates heat to the well water. At the same time cooling return water is circulated through valve V-l to the chiller and then to the cooling units. greater air temperature variation is tolerated. Storage tends to reduce the rate of temperature change and helps in some measure to reduce the peak equipment requirements. In this Bpnsft every heating and cooling system can be said to in volve heat storage in some degree. Many attempts have been made, particularly in recent years, to increase the heat-storage effect by using special heat-storage materials as part of the heating or cooling sys tem. The result is to reduce the size of the beating or cooling equipment necessary to take care of peak demands. In the case of the heat pump, a provision for heat storage pan serve not only to reduce the size of the heat pump neces sary for a given load, but also to provide a more desirable electrical load by shifting part of the load to the time of day when the cost of power is least. The off-peak electric hot water heater is a common example of such a heat-storage application. In general, there are two types of heat-storage systems that have been employed: (1) sensible heat-storage systems and (2) latent heat-storage systems. Usually the latter is actually a combination of the two, making use of some sensi ble heat storage in addition to the latent effect. Heat storage in a heat-pump system may be utilized on the high side, when heat is available at a temperature suitable for direct hearing; or on the low side as an intermittent heat source at temperatures lower than the heated space. Sensible Heat Storage Water, with the highest sensible heat storage capacity on a weight basis, is an obvious first choice and has the ad vantage of low cost, easy storage, and good heat exchange properties. The danger of freezing can be reduced by various types of antifreeze solutions. In some cases, however, freez ing may be desirable. The maximum temperature is limited by the cost of maintaining water under pressures when over 212 F, but this temperature is high enough for most heat ing systems. Rock and gravel beds have also been employed, and have a heat content per unit volume approximately 20 percent of the value for water. The earth has been utilized for heat storage, both for heating and cooling in a number of instances. A problem with most solid media such as these is one of heat transfer into and out of the medium. Table 5 lists the thermal properties of some of the com mon materials used, or considered, for sensible-heat storage. RCOULATINC VALVE Fig. 10 illustrates an air-to-air heat pump system which is similarly suited to a structure having simultaneous heat ing and cooling loads. The refrigeration subcooling surface shown is used to preheat ventilation air and thereby effect substantial economies in equipment size and operating cost. HEAT STORAGE The use of thermal storage in a heat-pump system can improve its performance characteristics. Installations of heat pumps with thermal storage have been made principally in a few large building systems.**' **' " All materials possess the property of thermal storage in greater or lesser degree. In the case of a building, the struc tural materials are almost always in the proces either of absorbing heat from or delivering heat to the interior space. This effect is more pronounced in cooling operation where The Heat Pump 595 Latent-Heat Storage Systems Because of the relatively large volumes required for all sensible-heat storage systems, many attempts have been made to utilize the latent heat of fusion of certain materials. Most materials have some capacity to absorb heat when changing from a solid to a liquid, and some materials have a large capacity to do so. Ordinary ice changing to water is a prime example of this kind and the possibility exists of utilizing it as low-side storage. For most heating applications, however, the temperature of this change is too low to be useful. Prolonged searches have been made for materials which pass through a change of state as reliably and regularly as ice and water, but at temperatures high enough to be used for direct application to space heating. In order to be much superior to water, the latent heat capacity of such materials must be high. Most organic materials are eliminated from consideration on this basis alone. Furthermore, the absorp tion and release of beat must occur in predictable fashion. Many materials which have been tried exhibit the defect of subcooling, delayed change of state, or decomposition through time and repeated cycles. A study of all materials, both inor ganic and organic, listed in chemical handbooks resulted in a list of over 100 materials having a fusion temperature be tween 72 F and 176 F. Most of these materials are extremely unpromising as heat storage media because of cost, corro siveness, instability, or unavailability. For many of them. Table 5 . Properties of Various Specific Heat Type Storage Materials Moferial Specific Heat Bfv per (lb) (co ft) (f deg) Denofy (b/cu ft Heot Capacity Bfv per lev ft) IF deg) Water Iron Concrete Brick Gravel 1.00 on 0.27 0.20 0.20 62.4 490.0 140.0 120.0 100.0 62.4 53.9 37.8 24.0 20.0 data on their heat of fusion are unavailable. All of these materials, where such data are available, have been listed in order of heat capacity per unit volume. Table 6 gives the nine materials which were highest on this list, and it is in teresting to note that there are few common or low cost materials among this group. Others, notably the first two, are academic curiosities. The material disodium phosphate is high on the list and has been used in a number of experimental installations. Re sults for the most part indicated a considerable unreliability at least in the particular form of the material which was used. Such factors as the rate of heat addition or release, size and shape of container, presence of nucleating media, and temperature gradients proved important in determining the percentage of heat storage actually available compared with the theoretical. In several small house beating installa tions employing heat pumps with condenser-side storage, the amount of disodium phosphate actually used was 3300 lb with theoretical latent heat storage capacity of 400,000 Btu. Indications were that the material was only partially ef fective in actual heat-storage performance. A method which makes use of a mixture of this material suspended in oil has been successfully tested in the laboratory, and through use of forced circulation of the oil, has exhibited high rates of heat transfer.41 Low-Side Storage With a heat-pump system, the possibility also exists of storing heat at relatively low temperature on the low side (heat source side) of the system. The freezing of water has already been mentioned as one possibility. Heat pumps with solar energy as the heat source have been studied with lowside storage." A limitation present with this type of storage system as compared to high-side storage is that the peak heating ca pacity of the system is limited to the heat-pump capacity when operating with the low-temperature storage reservoir as the heat source. In many structures, particularly in colder climates where the benefits of heat storage are potentially greatest, this is less than the peak heating load. Table 6------ Materials for l^eot Storage Listed According to Latent Heat per Unit Volume- of All Materials Haying Melting joints between 72 F and 176 F, Listed in Chemical Handbooks Alaferial Formdo Melting Point Heat Content F g-cal per g Specific Gravity latent Heot of Anion per Unit Vofuate {Theoretics/) g-cal per cc Thomand) of Btu/cv ft Nitrogen pentoxide Gallium Sodium phosphate, dodecahydrate Sodium sulfate, decabydrate Water Nickel nitrate Calcium chloride Osmium tetroxide Zinc nitrate Calcium nitrate NtO* Ga Na^P012H*0 NaiSOaOHjO H*0 Ni(NO)i6HiO CaCljSIIjO OsO Zn(NOi)t6H*0 Ca(NOt)*4H*0 85 76.7 1.63 86 19.0 6.88 94 66.8 1.52 90 57.1 1.46 83.4 9.4 32 79.1 1.00 80.0 9.0 132 36.4 2.05 74.7 86 40.7 1.68 104 13.5 4.91 66.3 7.5 98 31.1 2.06 64.3 7.2 108 33.9 1.82 61.7 6.9 * Nine auterislt hnrins casting points between 71 end 174 F listed Aocofdin* to bteat beet of fusion. Selected u highest , list of 1 arxeaie and u rttb IhM n ebembel kendkeeU