CHAPTER 18
1949 Guide
considered consistent with good practice, although there are boilers which have high efficiencies and also operate at higher transmission rates.
TESTING AND RATING CODES
- The Society has adopted four solid fuel testing codes, a solid fuel rating code, and an oil fuel testing code.
ASHVE Standard and Short Form Heat Balance Codes for Testing Low-Pressure Steam Heating Solid Fuel Boilers--Codes 1 and 2--(Re vision of June, 1929)1, are intended to provide a method for conducting and reporting tests to determine heat efficiency and performance char acteristics.
ASHVE Performance Test Code for Steam Heating Solid. Fuel Boilers --Code No. 3--(Edition of 1929)1 is intended for use with ASHVE Code for Rating Steam Heating Solid Fuel Hand-Fired Boilers*. The object of this test code is to specify the tests to be conducted and to provide a method for conducting and reporting tests to determine the efficiencies and performance of the boiler.
' The ASHVE Standard Code for Testing Steam Heating Boilers Burning Oil Fuel, (Adopted June, 1932), is intended to provide a standard method for conducting and reporting tests to determine the heating efficiency and performance characteristics when oil fuel is used with steam heating boilers.
' The ASHVE Standard Code for Testing Stoker-Fired Steam Heating Boilers4, (Adopted June, 1938), is intended to provide a test method for determining the efficiency , and performance characteristics of any stoker and boiler combination burning any type of solid fuel such as anthracite or bituminous coal.
The Steel Boiler Institute,' Inc. has adopted a Rating Code for Com mercial Steel Boilers and Residential Steel Boilers and for Testing OilFired Residential Steel Boilers (Fifth Edition as Revised Jan. 1 1948). The commerical boilers (defined as those having 129 to 2500 sq ft of heating
SBITable 1.
Net Rating Data fob Residential Steel Boilebs--Oil Fired*
Sq Ft Steam
275 , 320 400, 550
700 9Q0 1100
1300 . 1500
1800
2200 2600 . 3000
5B/ .Net Rating
. Sq Ft Water
440 510 640 880
1120 1440 1760
2080 2400 2880
3520 4160 4800
Btu
' 66000 77000 96000
132000
168000 216000 264000
312000 360000 432000
528000 624000 720000
Minimum , Furnace Volume Cn Ft
2.5 2.9 3.6 5.0
6.4 8.2 10.0
11.8 13.6 16.4
20.0 23.6 27.3
Heating Surface Sq Ft
16 19 24 32
41 53 65
77 88 106
129 153 . 177
* Stoker-fired and Gas-fired SBI Net Eating not greater than Oil-fired. Hand-fired, SBI Net Eating '(Steam) not greater than 14 times the square feet of heating surface.
Heating Boilers, Furnaces, Space Heaters
T a b le 2. SBI R a tin g s fo b C o m m er c ial St e e l B o iler s " .Oil, gas or bituminous stoker-fired coal. Mlnimum'furnace volumes for.anthracite, stoker-fired, are not specified in this code.
' b Bituminous, stoker-fired. '
0 The tapping sites shown for boilers having.120 to 600 sq f t of heating surface, inclusive are adequate for forced hot water.