Chapter 14--Automatic Control
valve to be operated directly by the water pressure in the pump discharge H automatically shuts off the steam when the water circulating pump is not in o'oL-..
10. Based on the fact that the spray water in the air washer pan has practiaif^
same temperature as the air leaving the washer, dew-point control can be accomr
by installing thermostat E in the water pan.
i'
ll. Where cold well-water is used for dehumidification, it is admitted to the through a three-way valve similar to V which is operated by thermostat E.
12. Control of steam heat is shown entirely by valves, although it is usual to ii by-pass damper around each heating unit and to operate it, either with damper over the face of the heating unit, in conjunction with the valve.
ature control be obtained in a room heated by an auto-
telUP^
fownapp?
unit. A room numiua^
------- ------------------ -------
^ibeloPiniw^humjclifier, or operating a relay on the recirculating pump motor to the
be connected in parallel with the fan motor. Humidification may be
heat is supplied and when the humidity control acts in conjunction
l^^meswitch.
-,
may humidity be controlled in a unit humidifier for a steam or hot
PROBLEMS IN PRACTICE
1 How may temperature control be obtained in a room heated by a ri with a constant steam supply?
By a thermostat handling an individual radiator valve pneumatically or electrical! by a self-contained radiator valve.
2 How may temperature control be obtained in a room heated by heater?
With constant steam supply, the unit heater motor may be started or stopped by thermostat, either directly or through a relay. With intermittent steam supply, 0p, tion of the motor by thermostat can be limited to the time that steam is available using a reverse-acting temperature or pressure limit switch..
3 How may temperature control be provided in a room heated and venti lated by a unit ventilator which includes two extended-surface units?
Operation of the unit for service during occupancy of the room may be manual, by switch, or by time clock. When the desired temperature level is reached, the outside' air intake may be controlled by a damper motor coupled with the fan motor circuit by means of a thermostat. The outside air damper will operate to a given position' either case.
Air passing through the unit may be preheated through the first heating coil to a definite temperature by a control valve on the steam supply governed by a temperature controller reacting to the temperature of the air on the outlet side of the convector. The second heating coil may provide the necessary heating capacity, and the steam supply to this coil may be modulated, either manually or automatically, in accordance with the tem perature required in the room.
4 how may temperature control be obtained iin a room heated by a system?
Air may enter the roomfrom the central fan system at a predetermined minimum tem- * perature. Heaters placed, in-the duct to bring the air up to this temperature should be ] equipped with face and b.jSjiass.dampers which may be adjusted by a positioning damper) motor to give temperatmB|pntf6f.
5 How may temperature be controlled in a room cooled by a unit cooler?
ljxbeatii>g plan1?
- required for evaporation, a temperature limit switch, preferably of the ?iSflce h.eat /IySrjie^may ibe p-lia--c-e-Jd in 4t-hkrev Uhoe-aiftininngr csnunpnplluy rriicsperr ttno pcaanuss*e* tthhee Uunniitt ttoo hbee iinn-- iinniersion^ ypv^eat -s nQt ava;iable. A room humidity control will operate a solenoid
y;,opef?t,vetjie water supply to the sprays. Both the solenoid valve and the humidity . valy? on ^ electrically wired in parallel with a fan motor, and be subject to the ^SSaWre limit switch.
Discuss a control system, including control of humidity, for the heating
: . central fan system of air conditioning.
Vi irinz the heating cycle it is necessary to vary the amount of outdoor air drawn into the wstern in accordance with the temperature of that air. It is also advisable to adjust the -.f fT?/me 0f return air when mixing it with the outdoor air so that the resultant mixture -- ?S|| 0f constant volume delivered to the preheater coils at some predetermined con-
slant temperature. > Rv placing a temperature controller in the conditioner just ahead of the preheating coil, the temperature of the air delivered at that point may be measured, and by connecting
this controller to a damper motor attached to the intake damper this damper can be operated by a temperature variation at the controller. The intake damper is so linked fothe return damper that the combined volume of air delivered through the ducts of the system is constant. At a fall in outdoor temperature, this arrangement will move the intake damper to a closed position and the return damper to an open position, whereas the reverse will hold true when there is a rise in outdoor temperature.
If conditions prevent such mechanical linkage, it is possible to use two damper motors connected so they are operated individually but in inverse ratio.
The operation of the preheating coils should be dependent upon humidity conditions in the occupied spaces, and the humidity controller should be installed where conditions are representative of the humidity throughout the section, because air leaving the pre heating coils is immediately passed through a spray where it becomes saturated with moisture. If the air is cold, it will absorb so little moisture that when it is delivered to the conditioned spaces its relative humidity will be low. When the compensated hu midity control calls for additional moisture, the steam control valve in the preheater line should be opened to allow more steam to flow through the coils.
Whenever the preheating coils are being heated the spray should be in operation, but when the coils are cut off the air is sufficiently moist and the spray should be closed down. This necessitates an inter-connection between the control valve on the pre heater and the spray pump on the water supply. Water is supplied to the spray during the heating cycle from a recirculating water tank beneath the sprays.
Practice indicates that a thermostat should provide for the automatic operation at all hours of the fan and control valve on the refrigeration source, but that there be a manual switch to enable the fan to operate continuously during occupancy.
6 How may temperature control be obtained in a room cooled by a selfcontained mechanical unit?
The reheating coil determines the dry-bulb temperature of the delivered air, so if the conditioner is equipped with both face and by-pass dampens on this coil it is obvious that these dampers should be controlled by a thermostat located at some representative position in the space being supplied with the conditioned air. If this thermostat is in turn connected with auxiliary apparatus which will vary the damper settings, it will be possible to pass more or less air through the reheater as the temperature falls or rises.
The fan operation may be controlled by a manual switch, while a room thermostat in con junction with a solenoid valve may regulate the flow of the refrigerant to the coil. The thermostatic circuit might be operative only when the fans are running; and the com
fpressor might be controlled by refrigerant pressure.
A low-limit temperature control might also be mounted in the discharge duct as a precaution against blowing cold air into the space. Such control would actuate the dampers of the reheater when the duct temperature fell below a predetermined minimum
regardless of the demands of the master controller.