ENGINEERING HEAT TRANSFER DATA
A Design Guide For Engineering Low-Cost, Low-Pressure FIRE-RESISTANT HEAT TRANSFER SYSTEMS
01A2S23
TOWOLDMON0022934 WATER_PCB-00007403
#'
TABLE OF CONTENTS
Introduction......................................................................................... Properties Important To Heat Transfer Design................................ Curves: Viscosity/Temperature; Density, Specific Gravity............. Curves: Specific Heat; Thermal Conductivity.................................. Specific Heat ofTherminol Fluids: Relationship To Density........... The Heater........................................................................................... Therminol System Components........................................................
Pumps, Piping, Valves, Rotary Joints, the Expansion Tank, etc. Testing, Cleaning, Filtering................................................................ Controls for the Therminol System................................................... Operation and Maintenance of the Therminol System..................... Typical Therminol Systems................................................................ Therminol Engineering Data.............................................................. Resistance of Valves and Fittings To Flow of Fluids........................ Pressure Drop; Hoat Transfer Rate, Heat Exchangers...................... Viscosity Conversion Chart................................................................ Engineering Conversion Factors........................................................ Typical Applications for Therminol Systems.................................... Safety of Handling Therminol Fluids................................................. Notes....................................................................................................
Page .I .3
4 6 6 8 . 11
14 15 10 18 22 29 30 38 38 45 46 47
0142524
|
TOWOLDMON0022935 WATER_PCB-00007404
Delivering High-Temperature Process Heat as a Liquid
As recently as 1941, process engineers were limited to two methods of delivering process heat: DIRECT FIRING or PRESSURIZED VAPOR. Each method had definite draw backs. Direct firing was often unsatisfactory because the heating was uneven, the tempera tures difficult to control, and the processing of combustible materials extremely hazardous. Pressured-vapor, such as steam, required costly, high pressure piping, valves, and proc essing equipment--plus constant chemical "conditioning" of boiler water. Heat energy and temperature loss were common with pressured-vapor systems because of "blowdowns," condensation, and the inevitable pressure loss with long runs of piping.
Today, non-pressurized, high-temperature, fire-resistant heat transfer systems based on Monsanto's THERMINOL FR Heat Trans fer liquids overcome practically all the de
ficiencies and drawbacks of direct firing and pressurized-vapor heating. THERMINOL FR--a series of high-boiling, heat-stable organic liquids, delivers processing heat to single or multi-users as a liquid without pres surizing. THERMINOL fluids are safe and fire resistant. Heating is uniform; and tem perature control is accurate within a range of plus-or-minus 2F.
Heat transfer systems now in use for several years have proved THERMINOL fluid heat successful in a wide variety of process heating operations . . . from food cooking to chemical processing, from distillations to drying ovens and in petroleum refining.
Design engineers and manufacturers have developed a variety of THERMINOL FR Fluid Systems ranging from small electrically heated units to giant gas or oil fired units-- all capable of delivering heat AS A LIQUID.
_____J
TOWOLDMON0022936 WATER_PCB-00007405
I
This manual explains and illustrates the fundamentals of THERMINOL fluid heat transfer systems design. It lists materials of construction and components for use with THERMINOL, and explains how each is "designed in" to make the most efficient system for safe, economical and reliable opera tion. It shows how these systems can be adapted to a wide variety of heating and cooling processes. This engineering heat trans fer data has been compiled to aid the Process Engineer in designing a safe, minimum main tenance system for delivering heat to the points of use in practically any commercial or industrial process.
HEAT TRANSFER LIQUIDS...
Monsanto THERMINOL FR heat transfer liquids are chlorinated biphenyls, manufac tured under exacting process control to pro duce fluids consistent in all properties impor tant to heat transfer. THERMINOL FR products are unique in that they are actually produced to rigid specifications for thermal stability, specific heat, thermal conductivity, vapor pressure, and viscosity.
There are three THERMINOL FR products, with a range of low temperature fluidity and boiling points that allows the user to select the best balance of fluid properties for a specific use:
THERMINOL FR 1 with lowest temperature fluidity -- excellent for processes requiring both heating and cooling
THERMINOL FR 2 with optimum balance of properties for use in most common industrial heating applications
THERMINOL FR 3 with highest boiling point for special proc essing equipment applications
oW^b
|
TOWOLDMON0022937 WATER_PCB-00007406
Properties important to neat transfer desion
...........................
^ THERM,WoU FR-1
............ - .
;:w
k Temperature. Enthalpy Specific Heal ThermO Conduct Density Viscosity Vapor Proa. mm.
BTU/Lb. BTU/Lb.--*F, BTU/Ft*, Hr.. "F./Ft. Lb./Gal. tb./Mr.--FL Hg. Absolute
JO * , 10.0
v, 100 f \*u
190 4
SW0
'
' 280
121
t 900 , 149
550 ITT
400 . 04
450 232
900 i 290
550 298
: 600
916
.650 943
:: .100 ' , 671
4*56 1669 J .92 95 4607 63.50 79.45 95.94
112.95
180.48 A
148.62 . 167.66
166.16
205.79
225.92
0.272 . MK -j 0.201 . 0.3047
,0.3151 * ' 94265 04399 0.3454 0.3568
0.3672 . 0.3778 ^ 0.3680 '
0.3965 0,4069
006096
0.06060
006021 ,
" *,osm
. 005927
005875 $ %
0.05819 v'
0.05760 , '
0.05997
1
0.05630 '
0.05560
.
005467
' 0.05409 '0.05329
`l
11.663 11.458 11.216 10.991 10.160
10.528 10.296 10.065 9.833
9.601 9470 9.188
9.906 8.675
745.86 66.144 16.972 . : . 9.2491 y 5.8270 9.4156 . 2.4759 1.6696 14026
14351 1.0428 0.60031
0.79166
0.70731
10 7 65
143 291
550
16.8 pel* 81.9 psla
THERMINOl. FR -X
' Temperature *r. . : c.
JO
100 150 200
250
900 . 950
400 r 450
900 550
600 650 700
!
104 87.6
60 W 121 149
in 204 282
too 88
916 949 871 ,
Enthalpy Specific Heat Thermal Conduct. BTU/Lb. BTU/Lb.--*F. BTU/Ft?, Hr.,, V./Ft.
4.9# 17.61 91.09 45.11 89.48
74.14 86.26 104.81 120.74
187.06 153.85 170.99
186.58 203.45
,
0.257
0.265 0.274 0.2640 0.2022
0.3003 0.3084 0.8166
0.3247
0.8328 0.8410 0.3491
0.3579 0.3654
, :
0.05861 , /
: 0,05692
0.05801
:
0.05798
005748
005703 .
005955
0.05603
0.05546
0.05488
0.05424
0.05957
;
005266 - `
0.05211
-
Density Lb./Gal.
12.225
,12.000 11.750 11.525 11.293 11.062
10.830 10.598
10.367 10.135
9.903 9.672 / 9.440 9.206
>
Viscosity U./Hr.-Ft.
7090.6 151.01 743 11.971
6.949 4.631 6.201 ' 2499 1.681 1.529 1.2795 1.0971 0.9596 9.8585
Vapor Pres. mm. Hg. Absolute
6 15 97 84 178 840 615 20.3 psla
,*
THERM I NO I- FR-3
Temperature
*F. C.
90 : ioo !' 180
S0O ; 290
900 , M0 ' 400 : 450
. 00 o
ooo MO ' 700
40.0 87.8 86 99 121 149
177 '04 '
IK . 260 ; 298 916 . 949 971 '
Enthalpy BTU/Lb.
4.28 18.87 29.06 41.95 65.96 69.20 . 63.46 "66.15 113.25 128.77 144.78 191.11 177.92 192.24
Specific Heat Thermal Conduct. Density Viscosity BTU/Lb.--*F. BTU/Ft1, Hr.j, V./Ft Lb./Gal. tb./Hr.-Ft.
0.239 ; 0.245
' ' 0.256 : - J 0.2029 04714 .
0.2799 0.2684 0.2969 04054
0.9136 0.8228 0.8906
0.3398 04479
0.05700
13.002
0.0569D '
12.760 .1626.6
005694 .1 . 12.534
101.64
005620 1
12.292 < 4462
0.05596
12.061
12.091
005556
. 11429
7.116
0.05518 ,,v
11.697
,, 4.698
0.05466 ' ' f 11466
9.906
0.05415
11.184 .
2476
0.0504# ; 10.902
. 1.937
0.05302 ..
"10471 ' 44099
O.OS241 ,
10.489 ' 44095
0.05176 ' ` 10.207
: .1186
- 0.05107
9.976
0.H76J1
Vapor Pres. mm. Hg. Absolute
9 9 4 85 114 223 413 785
01425*7
TOWOLDMON0022938 WATER PCB-00007407
.^< '' vtscoairy-ireMPERATURe chart
--
\\ V A'*'
-3, v
i L.V
4j j i ,::r
THERMlNOL PR-1 * THERMlNOL PR-S a THERMlNOL EM
ISE*
rYBTO LB/HR. FT. -MULTIIF*
pMi
TO CONVERT CENTIPC ISES
TO CENTISTOKES 01V OE BY S EC FJC GR kV TY
111 L_L
*UL
!
TEMPERATURE *F.
\
I
t
01A25Z8
TOWOLDMON0022939 WATER PCB-00007408
s p e c if ic m e a t b t u l b ., *f ./
STU/HR., rr. , "F./FT.
01A2%2<>
________
6 .1
TOWOLDMON0022940 WATER_PCB-00007409
Its Relationship to Density
Specific heat--the quantity of heat required to raise the temperature of 8 material one degree, compared to the heat required to raise a like mass of water one degree--compares the material with water, pound for pound.
When comparing specific heat values of THERMINOL FR liquids with correspond ing values of other heat transfer fluids, it is important to note that the density of THEKMINOL is much higher than the den sity of other fluids commonly used in heat transfer. In consequence, the heat capacity of THEKMINOL fluids is greater than imme diately apparent from the specific heat values.
In transferring heat, a volume of fluid is circulated to give up or absorb heat and the heat capacity of that volume of fluid is the
When a comparison is made on a volume basis (as illustrated below), THERMINOL liquids are comparable to other organic liq uids and superior to some:
SPECIFIC HEATS OF VARIOUS FLUIDS at ROOM TEMPERATURE
Pounds/ Gal.
Specific
Heat
Heat
Capacity
(BTU/ib./ (BTU/gai./
F) F)
THERMINOL FR 2 Organic Fluid "A" Petroleum Oil
12.03 8.82 7.9
0.276 0.378 0.378
3.32 3.33 2.98
*
THE FLUIDS
THEKMINOL FR liquids are unique. They permit installation of a non-pressurized sys tem operating with a liquid which has no fire point, and will not, support, combustion. THEKMINOL FR liquids are so fire-resist ant they have been listed with Underwriters' Laboratories!
Because of this extreme fire resistance and its recognition by insurance companies, impor tant savings can be made in designing a process heating system around THERMINOL FR fluids. The savings include not only the lower capital cost of non-pressurized equip ment, its simplified installation and lower maintenance; but also elimination of some of
the costly safety devices required in equip ment circulating a flammable fluid at or above its fire point. These economies show up both in the type of components needed and in the layout of the system.
Still another unique property of THERM INOL fluids is their unusual chemical inert ness. They are among the most oxidationresistant compounds known. This inertness prevents the formation of oxidation sludges if the hot fluid comes in contact with air. This extends the useful service life of the heat transfer fluid; occasionally allows economies in design, However, THERMINOL FR fluids are not intended for use in open vessels but in properly vented, closed systems.
TOWOLDMON0022941 WATER_PCB-00007410
Chemically, THKRMINOL FR fluids are resistant, to strong acids, mild alkalies, and dilute solutions of strong alkalies.
THERMAL STABILITY
THKRMINOL FR fluids are thermally stable. They are manufactured to meet strict thermal stability specifications. Each produc tion run is tested in Monsanto's laboratories with special equipment developed by Monsanto to assure that these fluids meet the high standards of thermal stability. Any material which does not meet these standards is rejected.
If is characteristic of almost all organic mate rials to undergo chemical change when ex posed to high temperatures for long periods of time. The type of chemical change depends upon the molecular structure of the fluid; the degree of change depends on the temperature, and the length of time of exposure.
THKRMINOL FR fluids resist chemical change up to temperatures of 600F. and show no measurable change after years of exposure to such temperatures. Exposure to temperatures above 600CF. -- even localized overheating will only cause some formation of "high boilers": molecules of THERMINOL FR will join together to form larger molecules quite similar to the original material, but higher in viscosity and in boiling point. These high boilers are soluble in the fluid up to reasonable concentrations; so overheating only increases the fluids* room temperature viscosity slightly. When a concentration of approximately 5-10 percent "high boilers" has been formed, however, the viscosity begins to rise quite sharply.
With this change, small but measurable amounts of dry hydrogen chloride gas are evolved. This should be removed from the system by appropriate venting. When THERMINOL FR fluids operate at high bulk temperatures, or, where some local over heating may occur, the Bystem should be designed to prevent moisture from condensing in the vapor spaces where this hydrogen chloride gas is being vented.
When the hydrogen chloride is dry, it has little or no effect on metals in the system. However, if the hydrogen chloride dissolves in moisture, an acid corrosive to certain metals is formed. A properly designed heater and distri bution system operated at or below 600F., will allow use of the same fluid for many years.
While THERMINOL FR fluids normally are operated to a maximum temperature of 600F. --systems specially designed for operation at higher temperatures have proved successful. At higher temperatures--"high boiler" forma tion with attendant viscosity increase is, of course, accelerated and a shorter service life must be expected. However, side stream dis tillation can be employed to constantly re move higher boiling materials while the sys tem is in operation. Periodic make-up is added to replace the quantity of the high boiler material removed.
An alternate procedure for higher tempera ture operation, which is sometimes more suitable for smaller installations, is periodicreplacement of the THERMINOL charge, reclaiming the used fluid by straight, take over distillation. (Monsanto should be con tacted for details regarding this procedure.) On systems containing only 50-100 gallons of THERMINOL, it is usually most economical to periodically discard the entire charge and replace it with new fluid.
THERMINOL SYSTEM DESIGN
When designing a THERMINOL FR system it is important to remember this fact: THE FLUID CAN BE NO BETTER THAN THE SYSTEM! THERMINOL FR liquids are ideally suited for high temperature precision heating and temperature control applications, but only if the heater and distribution system are properly designed, constructed and operated. While there is nothing profoundly different or complicated about a THERMINOL system, certain design parameters must be rigidly observed if the system is to operate trouble-free, efficiently, and with realization of the full benefits of heat de livered by a liquid,
j 1
; ? : . j i < i i
01*2531
TOWOLDMON0022942 WATER_PCB-00007411
J
[
!
Two basic heater designs for THEHMINOL fluide are available: the liquid tube and fire tube types. In liquid tube heaters, the THEHMINOL is pumped through the tubes at a definite flow rate as it is heated; in fire tube types, THEHMINOL flows through the "shell" of the heater surrounding the fire tubes,
When operating temperatures of 500F. (or higher) are required, a liquid tube type heater is to be preferred ... unless a specific design is devised to force a steady flow over the heat donor surfaces.
Since THEHMINOL fluids transfer heat in liquid form, they do not form vapor to ac celerate convection circulation. To avoid hot. spots in a THEHMINOL heater, the fluid should be pumped over the heating surfaces so that no area of stagnant fluid occurs.
Fluid velocities over the heat donor surfaces should be relatively high; generally 4 to 10 feet per second. This helps avoid both exces sive fluid film temperatures and also reduces the quantity of fluid in the high temperature film that is in direct contact with the heat donor surface,
The illustration shows the effect of fluid velocity on film temperature and indicates the importance of this design requirement.
EFFECT OF LIQUID VELOCITY ON FILM TEMPERATURE DURING HEATING
High Liquid Velocity
Low Liquid Velocity
Importance of Fluid Velocity and Film Tem perature through Heater
A bulk fluid temperature of 600F. and a maximum film temperature of 640F. assures long service life of THEHMINOL FR fluids. Note the significance of "maximum" film temperature: heating is not uniform in fired
0
oW"2
I
:I
TOWOLDMON0022943 WATER_PCB-00007412
healers, and maximum conditions--not aver age-must be used to determine the recom mended 640F. ceiling.
Example:
The film coefficient for THERMINOL in a given heater is 250 BTU/hr. sq. ft., F., and the fluid temperature is 570F.
The average radiant absorption rate is 9,000 BTU sq. ft., hr. The maximum ra diant absorption rate is 17,000 BTU/sq. ft., hr.
The average film temperature is then 570 + 9;00 = 606F.,
250
but the maxmium film temperature is
Bast experience shows that when purchasing a heater, the buyer should insist that, design and capacity provide optimum film tempera ture for the fluid.
The method of Lobo and Evans0 is useful in calculating film temperatures in radiant heaters.
When electric heaters are used-heat, flux is more even. However, it is important to re member that, all of the heat from the electric element passes into the fluid. The watt-density on the surface of the heater tube and the fluid velocity past the tube should be in proper
balance to avoid excessive THERMINOL film temperatures. Watt-densities in the range of 8 to 10 watts per square inch with a minimum velocity of 4 feet per second are suggested. However, watt-densities in the 18 to 22 watt per square inch range have proved satisfactory in properly designed installations.
Heaters for THERMINOL should meet local code requirements. However, the fire resist ance of THERMINOL FR fluids will often permit important, economies in the design and placement of fired heater equipment. With gas-fired heaters, the THERMINOL unit need not be placed outside of the building or isolated in a fireproof structure unless the use process requires such precaution. Steam or inert gas smothering devices can generally be eliminated and a vapor tight, firebox to retain smothering gases is not necessary.
The fuel for THERMINOL heaters is purely optional. Gas- or oil-fired heaters, and elec tric resistance heating are all used with success. Coal-fired heaters are generally not recommended because of their slow response to change of load at the heat source.
The over-all thermal efficiency of a fired heater will generally be comparable to steam boilers of similar size. Efficiencies of 75 to 80 percent can be expected when convection sections are added. Efficiencies of 60 to 70 percent are achieved with only a radiant section.
(i> Lobo, W. E., and J. E. Evans. Trans. AlChE, 35. 743 (1939)
Several types of heaters which have
operated successfully in THERMINOL
systems are illustrated on the
following page.
OL72533
9I
TOWOLDMON0022944 WATER_PCB-00007413
TOWOLDMON0022945 WATER_PCB-00007414
I
&T
Vi
: \.......
pumps for the
thermi
FLUID HEAT SYSTEM...
]n selecting pumps for a THERMINOL system, it is important that the pump ca pacity and pressure head be sufficient to circulate the fluid at the rate demanded by the particular installation. For large flow rates, the fluid circulating pump should gen erally be the centrifugal type and any one of a number of brands of standard high tem perature centrifugal pumps designed for hot liquid service is suitable. Dean Brothers, Worthington, Ingersoll-Rand and Chempump for example, are all used satisfactorily. For most THERMINOL systems, cast steel pumps are best. Bump manufacturers usually specify that above 450F. fluid temperatures, a water jacketed, deep stuffing box or me chanical seal and water-cooled bearings be used. Mechanical seals are used widely today.
It is suggested that with a stuffing box, eight rings of packing be provided. Durametallic No. D-1I0, Garlock No. 736 and equivalent packings are satisfactory for the pump, and an open, non-overloading impeller is desirable to handle the cool, relatively viscous liquid at start up.
When a new system is first put into operation, a slight leakage may be noticed at the pump packing. It is not advisable to tighten the pump gland, however, until the system has heated up close to the temperature of operation.
Canned pumps such as Chempump Series T require no seal and have proved very service able in THERMINOL systems. Small gear
pumps are also used successfully in THERM INOL FR service because the fluids have good high temperature lubricating properties. However, gear pumps characteristically de crease in pumping capacity after extended use. When gear pumps are used, care should be taken in selecting the capacity so there is a margin that will assure adequate flow through the heater. Regardless of the type of pump selected, the flow rate should be checked regularly against its performance when new.
To avoid shaft trouble and leakage at the seals, it is important to provide adequate expansion joints and to support the piping in a way that avoids stresses on the body of the pump. Direct-connection pumps driven by 1,750 rpm. motors are most commonly used. Each pump should be fitted with a control to switch off the burner in case of pump failure.
If expansion loops are used in the pump suction piping, they should be horizontal or vertically downward. They should not be vertically upward, for in such a position they form a trap which can collect air and non condensibles, and seriously hamper the pump's performance,
PIPING...
The most important factors in the piping layout for a THERMINOL FR system are; (A) Proper sizing for the required flow rate and (B) minimizing pressure drop. Because the system will undergo temperature changes,
I
01*2535
TOWOLDMON0022946 WATER_PCB-00007415
adequate expansion joints and loops to relieve expansion and contraction stress are essential.
Generally, Schedule 40 seamless steel pipe is used with THERMINOL FR systems. It is characteristic of most, organic fluids (includ ing THERMINOL) to have a tendency to leak through joints and fittings at high tem peratures unless these fittings are very tight. Therefore, flanged joints should be used sparingly to minimize potential leak points.
Threaded connections are used with THERMINOL FR up to a one-inch maxi mum size. Care is required in cutting the threads to assure a proper fit; a clean, new die is recommended. Careful attention to threading procedure should provide a good threaded connection. It is not wise to rely upon the use of pipe dope to eliminate leak age. However, pipe dope should be used. Q-seal (Quigley Company, Inc.); Plastiseal (Johns Manville); and Crane's No. 425 are all used successfully in THERMINOL FR systems.
In larger size pipes, welded connections should be used wherever practical. Careful layout and use of curved sections of pipe can mini mize the welded or flanged connections re quired. When a flanged connection is made, 150 pound raised face flanges are recom mended. The flange should be backwelded to the pipe and proper gasketing used. Spiral wound (Spiralabc or Flexitallic) asbestos and stainless steel gaskets are good. Small lip spiral wound gaskets are preferred over the wide lip type, because they allow better compression with the 150 pound flange. Oarlock short fiber, pre-cut and cured as bestos gaskets have also proved satisfactory.
It is recommended that high temperature bolts, such as Crane Triplex steel bolts, which do not stretch, be used.
All high points in the piping system should be provided with vent valve connections.
VALVES...
One hundred and fifty pound cast steel valves with deep stuffing boxes are satisfactory for TlIERMlNOLsystems. Cast steel ball valves
designed for high temperature (such as offered by Hills McCanna have also proved very effec tive, particularly where quick open-and-close action is desired.
ROTARY JOINTS...
It is wise to take particular care in the in stallation and maintenance of rotary joints in order to assure long service life and mini mum leakage. Install such joints with proper flexible connections to assure alignment at all times. Rotary joints should not be operated in a new system until the system has been thoroughly cleaned of abrasive particles which could score the sealing faces and cause leak age. Rotary joints such as those manufac tured by the Johnson Corp. and Perfecting Service Co. are satisfactory with THERM INOL FR.
THE EXPANSION TANK...
Proper design of the expansion tank for the THERMINOL system is quite simple, but is also very important to proper system operation.
Characteristic of most organic liquids, THERMINOL expands in volume about A percent for every 100F. temperature rise In heating THERMINOL from room tem perature (70F). to 600F., the fluid in the system expands about 20 percent. Therefore, the expansion tank should be large enough to accommodate about 20 percent of the total volume of the entire system, including the fluid content of the heater, piping and ail heat users. The tank should be sized so it is about one quarter full when the system is cooled to 70F. and three quarters full when the system is at a maximum operating temperature. The expansion tank should be fitted with a sight glass at the "full" range and with a float operated, low-level switch to shut off the burner in case of accidental fluid loss in the system.
Place the expansion tank in the circuit on the pump's suction side --above the highest point in the system.
The expansion tank also serves as the major venting point of most THERMINOL sys-
0142**6
TOWOLDMON0022947 WATER_PCB-00007416
terns. The temperature of the fluid in the expansion tank is much lower than the bulk fluid temperature in the system. Connect the expansion tank to the system with a small diameter line to avoid thermal recirculation. However, make this line large enough to readily pass the flow caused by expansion and contraction in the system and to permit recirculation of fluid for moisture removal as explained below.
Rccause THERMINOL Fit fluids are fire resistant, the vent need not be isolated from potential sources of ignition. However, the vent should be out of doors, particularly away from working areas, to eliminate pro longed or repeated contact with the vapors.
Care should be taken to prevent the entry of atmospheric moisture into the system as the expansion tank `breaths' air. The vent can be equipped with an air dryer, such as a calcium chloride pot or other desiccant.
An alternate procedure would be to blanket the expansion tank with nitrogen. However, if this is done, the THERMINOL system should be dried thoroughly before the system is scaled with nitrogen.
In systems using TH KRMINOL above 600F. (or in systems where accidental high film temperatures may occur in the heater) some provision must be made for venting any hydrogen chloride gas formed in the system and to assure that the system remains dry, Gas or water vapor will not escape readily through the "cold seal" connecting the ex pansion tank to the THERMINOL system. It is advisable to provide a pipe to feed a small side stream of hot THERMINOL through the expansion tank as illustrated at right to allow hydrogen chloride and water vapor to flash from the fluid. A small stream of hot. THERMINOL from near the pump discharge should be piped directly into the vented expansion tank, so it enters the tank above the highest liquid level. A globe valve should be installed in the line to permit throt tling the flow to the desired rate.
Experience shows this simple procedure to be extremely effective and completely satisfac
tory for removing hydrogen chloride and moisture from the THERMINOL system. Analysis of samples drawn from systems operating with such a device show that the THERMINOL fluid maintains minimum acidity and holds moisture at the low levels equivalent to newly manufactured fluid, even after prolonged periods of operation. Provision should be made to prevent moisture from condensing in the vapor space above the liquid level in the expansion tank and in the vent. It is advisable to trace and insulate the expansion tank and the vent so that any moisture accidentally entering the system will remain as a vapor and will not condense. This will prevent corrosion of steel and elimi nate the need for higher cost alloys. The use of non-metallic vent pipe is also recom mended. Polyester piping (available from Fibercast), resin lined steel piping or other non-metallics resistant to THERMINOL vapors and to hydrogen chloride are com mercially available and have been used with great success.
NOTES... The expansion tank and vent should be traced and insulated. If steam is not available at the site, hot THERMINOL fluid can be passed through steel tracing tube.
0142537
TOWOLDMON0022948 WATER_PCB-00007417
TESTING FOR LEAKAGE...
When a new system has been installed, it is important to test for leaks. Probably the most widely used technique is to check for leaks with ammonia gas. In this method, the system must be relatively dry and sealed. All vent valves should be closed and a tem porary pipe cap or slip blank installed at the expansion tank vent and at other points where there is no valve.
Ammonia gas is fed into the sealed system followed by air under pressures up to ten pounds per square inch. Any leakage areas can be readily detected by the escape of ammonia. Tiny amounts of ammonia vapors can be made visible as white smoke by directing a small stream of hydrogen chloride gas over each joint or fitting, and around each welded connection. Any leakage points can he marked, tightened, and then the system purged free of ammonia with plenty of air.
A satisfactory alternate procedure is Halogen Testing: in this procedure, introduce one pound of Freon F-32 or Freon F-22 for each fifty cubic feet of volume of the system. Carefully introduce air not exceeding 10 psig of pressure. At this air pressure, the con centration of Freon will be sufficient to give a sensitive test.
Attach a halide torch to an acetylene tank and light it. Using the M inch flame as a probe, explore for leaks by passing the end of the flame along seams and joints. If a leak is present, the escaping Freon will be drawn
into the acetylene flame turning it green. A large leak will produce a violet color.
Leak testing with water is not recommended. Though effective, it creates a problem of introducing a large amount of water into the THERMINOL system which will be hard to remove.
CLEANING THE SYSTEM...
After testing for leaks and making any re quired adjustments, the system must be thoroughly cleaned.
A new system will contain dirt, weld and mill scale and other foreign particles. Unless re moved, these particles will be carried in sus pension by the circulating THERMINOL. They may "lodge" in valves, controls, mechancial 6eals, rotary joints and other mechan ical equipment, causing faulty operation or component failure.
When purchasing the heating equipment, the supplier should be requested to clean the equipment as thoroughly as possible using brushes, wiping rags and suitable solvents, such as tri- or perchlorethylene.
When completed, fill the system with the operating charge of THERMINOL. Bring the system up slowly to approximately 200F. At this temperature, the viscosity of THERMINOL will be very low. The turbu lence from this low viscosity, plus the excel lent solvent action of THERMINOL fluid, will further clean the system. Circulate the warm THERMINOL through the system without operating rotary joints (if they are installed in the system).
FILTERING.
Install a strainer, made of ordinary fine mesh screen backed up with H" screen, in the pump suction of the new system. As foreign material collects, this screen should be peri odically removed and cleaned. When, after several days during which the strainer col lects no material, remove it permanently from the line. The system should be heated and cooled for a minimum of t wo cycles with the suction screen in place, since the resultant expansion and contraction will loosen mill
01*2536
||
TOWOLDMON0022949 WATER_PCB-00007418
scale. The screen may be placed in the main stream line, gasketed between two flanges.
It is advisable, when operating where solids and contaminants might enter the system, to permanently install a high temperature filter on a by-pass line that can be isolated with valves for periodic cleaning.
CONTROLS...
Controls for heating systems using THERM1NOL should be installed both on the heater itself and on the heat-using units. A wide variety of thermal-operating controls are available, and any reliable standard equip ment is satisfactory.
Install heater controls to regulate the firing mechanism in direct proportion to the re quired output. These controls should increase or decrease the heat in-put to maintain the THERMINOL at the operating temperature required by the heat-demand of the user. Small units may be operated satisfactorily by relatively simple "on-off" or "high-low" con trollers; larger units will operate more uni formly if equipped with modulating tem perature controls.
Install user controls to regulate the flow of the heat transfer fluid in proportion to the heat-consumption of the heat-using equip ment, In a multiple-user system, separate controls should be installed on each consum ing unit, to assure the proper heat-delivery.
Safety Controls. In addition to activating controls, the heater must also be fitted with the proper safety controls to meet the local code requirements. Safety controls should include:
a. High temperature cutoff at the heater outlet ... to shut off the burner in the event of an excessive temperature rise.
b. High tube wall temperature cutoff. A thermocouple sensing element should be installed in contact with the radiant heated surface at the highest temperature point in the heater and protected as much as possible from direct, or reflected radiation. Such a controller is usually of the on-off tyj>e with the switch wired into the flame
safety circuit bo that the burner is shut down when the switch opens, Aside from protecting the tube bundle, this safety con trol protects the THERMINOL fluid from overheating.
c. Low flow cutoff. This control will shut down the burner should flow rate drop below design rates, or if a loss of flow occurs due to pump mal-function or failure.
Equip burners with regular automatic ignition controls and flame failure controls. In wide range firing operations, an over-fire draft con trol will increase the economy of the opera tion. Electric power failure and instrument air failure safety controls are also desirable. In general, the practice of "fail-safe" instru mentation and control is essential: use good quality indicating and recording gauges, with scales calibrated for the particular limits of operation for best reading accuracy.
(I t|
r
0142539
TOWOLDMON0022950 WATER_PCB-00007419
OPERATION AND MAINTENANCE OF THE THERMINOL SYSTEM... f
The following recommendations are intended
the Bystem through the expansion tank
only as guides. These suggestions are sup
valve until the tank is almost empty.
plemental to the equipment manufacturer's
Close the valve and again fill the tank.
i
recommendations as they relate to the par
Open the valve allowing the fluid to enter
ticular heater or the user equipment in the
the system and repeat until it no longer
installation. The following comments on
flows by gravity.
, I
start-up, shut-down, power failure precaulions, and periodic fluid check-ups apply generally to all sizes and types of equipment.
b. Open all valves then start the main circulating pump in accordance with the manufacturer's recommendations. Observe
NEW SYSTEM START-UP...
For a new installation, or an existing system that has been drained and is idle:
the liquid level in the expansion tank re peating "a" above until the system has been filled. The thermal expansion of THERMINOL must be allowed for in
1. Check the safety and control devices..
determining the cold charge level. (A 20%
Check the safety and control devices for
expansion can be expected when heated to
proper installation, proper range settings
600F.--as a guide, the expansion tank
for the operation, and actual operation (by
should be 70-75% full at the hot operating
manually activating the instrument).
condition.)
For protection of the over-all system and for predictable long fluid life, it is vital that all instruments and controls perform properly.
2. Check for leaks (see section on leak testing, page 14.)
3. Pull Vacuum on System.
c. Circulate the THERMINOL fluid through the system for about 3 to 4 hours to eliminate air pockets and to assure com plete fill of the system.
BEFORE FIRING HEATER, BE SURE THAT THERMINOL IS CIRCULATING FREELY.
0
a. The vacuum should be pulled from a point of high elevation in the system; usually at a point just below the expansion tank. Prior to drawing a vacuum, close all valves to the expansion tank; close all valves and vent connections to the atmos phere; close all valves to non-pressure equipment in the system (such vessels may collapse under vacuum) and open all valves in the interconnecting piping of the system.
b. Turn on vacuum equipment and evacu ate the entire system (including the "users") to 26-27 inches of mercury vacuum (if possible), or until the absolute pressure of the system has reached the limit of the available vacuum equipment.
c. Shut off vacuum equipment.
4. Charge fhe System with THERMINOL.
5. Fire Heater.
a. On new installation start-up, or after prolonged shut-down, bring the system up to temperature slowly --about 100F. per hour. This will prevent thermal shock to heater tubes, tube header joints, refrac tory materials, etc., and allow operators to check the functioning of instruments and controls and become familiar with the equipment's operation. The slow heat-up will also allow any moisture trapped in the system to escape as a vapor.
b. Bring system to operating temperature and put "users" on the line.
DAILY START-UP ... when equipment has been shut down overnight or for week ends, follow this procedure:
a. Fill the expansion tank with THERM INOL, and introduce the fluid slowly into
1. Start the circulating pump and check the expansion tank level to see that the
0142540 1C
TOWOLDMON0022951 WATER_PCB-00007420
THEKMINOL is at the proper cold-start level 0^-full).
2. Start burner at the "low" flame setting and continue full circulation until the THEKMINOL bulk temperature reaches 180F.
3. Turn heater up to full heat.
SHUT-DOWN ... should be performed as follows to avoid overheating:
1. Shut, off burner completely with circulating pump still operating. Continue to run the pump at full capacity for at least 30 minutes to dissipate residual heat in the combust ion chamber of the burner.
2. Shut off circulating pump after F6 hour, and switch off all heater electrical controls.
COLD WEATHER PRECAUTIONS...
When the THEKMINOL system is exposed to low ambient, temperatures, it is often most practical to leave the system "idling." Turn the burner to "low" position, and allow the fluid to circulate continuously at about 200F. The unit, will then be "at ready" for imme diate high-temperature operation, and the viscosity of the fluid will remain low and workable.
IN CASE OP POWER FAILURE...
The burner circuit should be shut down by the heater controls. When the power comes on, run the circulating pump for a few moments to eliminate any vapor pockets that might have been formed by the fluid remain ing static in the hot combustion chamber. If there is no knocking in the piping system, full-fire may be resumed immediately if the fluid temperature is above 180F.
PERIODIC CHECK-UPS...
The regular maintenance inspection schedule should include the manufacturer's recom mendations, as well as inspection of the THEKMINOL. Following is a listing of in spection check-points:
1. Lubrication of moving parts.
2. Operating fidelity and accuracy of readings
of safety controls and temperature limit controls.
3. Inspection of heater tubes, burner, refrac tory linings.
4. Periodic inspection of heater surfaces.
5. Inspection of water cooling at the circu lating pump.
6. Repacking of stuffing boxes (according to manufacturer's specifications).
7. Semi-annual or annual sampling and anal ysis of TIIERM1NOL.
Under normal operating conditions, it should not be necessary to check on the condition of the fluid more than once or twice annually. The analysis for fluid condition is a simple test of fluid viscosity. The exact viscosity limits will be affected by the specific mode of operation and can vary somewhat from sys tem to system. Monsanto should be contacted to determine specific values for the intended operation. Most users do their own testing; some have the viscosity determination made by an outside laboratory. A simple test kit for in-plant testing of THEKMINOL is available at a low cost.
Customers can have their fluid tested by Monsanto free of charge. For sampling con tainer and application data form, write to:
MONSANTO COMPANY FUNCTIONAL FLUIDS MARKETING ORGANIC CHEMICALS DIVISION ST. LOUIS, MISSOURI 63166
Analysis results will be returned to the cus tomer with complete recommendations for improving or continuing the performance of THERMIN.OL heat transfer liquid.
01*2^1
it |
TOWOLDMON0022952 WATER_PCB-00007421
typical --rhRrm 1 Jihi m U FR SYSTEMS
I
! I
"__I
0142542
TOWOLDMON0022953 WATER_PCB-00007422
I ''' **'
*
i
` '-rV-I 1at ,*..^.
$K,5 * ,?s^t4'' ^ \
t
*w *ywv'#'* ^ L' * >v<''t?9*?v* 4* / r <*
, '" '
' v'jJ-J,' ,
HEATING MULTIPLE USERS: V-s y.-v" 1*
I,
* FK5. $ *v v'/n^ v / jMlU tiOW UMIT CUTOFF TO BURNER |
, ` fttfe (hat each ueer an *>e oontrolled *t different temptmtofft i# control i the ftow of THERMWOL end therefore he .rate of flo* jtf;haat>fferad
is * v"jii/ t^tt**1*
fete
`Vf
i^ .u.i,
,
ui&iBsimiiJi, > (t
01^443
___________________ .1 TOWOLDMON0022954
WATER_PCB-00007423
,..rri,........ HEATJNC* Of COOUNO .........
jBCVeRAL MSERS ^IMULTANEOOSLY
V\v>
*.* .,*. ^ J*
*
....................... " ........'*?$/* ;[........... ......... . ` '
filV.i, .mV
, '-,v OUTopr neater-
'ml 1 *S
'
#LET
'*
' '
t}--L
ra-1
,-PUMP
Igpff -i USER
'',,\, !l V1`V'i( ` .K
1 "
''
tn i
-> f FRC-FLOW RECORDER CONTROLLER WITH I.OW LIMITCUTOFf TO
%L
HEATING COOLING
Tift
HEAT
EXCHANGER -------------- T.
USER
c
OH20AA
|
TOWOLDMON0022955 WATER_PCB-00007424
I!
i!
FLOW RECORDER CONTROLLER WITH LOW LIMIT CUTOFF TO BURNER Single heater system provides varying THERMINOL temperatures to users . .. finds application for processing heat-sensitive materials.
01*2545
TOWOLDMON0022956 WATER PCB-00007425
T
f>!
"thermJLrLo
FR ENGINEERING DATA
The design and installation of THERMINOL indirect, heating systems requires a heat balance between the uBer(s) arid the heater. The amount of heat which will be absorbed by the user in a given time depends upon the over-all heat transfer coefficient, the heat transfer area of the user, and the mean temperature difference between THERMINOL and the process or area being heated.
In processing most organic chemicals, oils, food cooking --the rate of heat transfer is usually dictated by the process and not by the heating medium. However, in designing a system --it is important to know the heal transfer coefficient of THERMINOL. This is affected by a number of variables, probably the most important of which is flow rate.
The following curves provide engineering data on THERMINOL heat transfer coefficients as a function of flow rate . . . and pressure drop as a function of flow rate ... in various common sizes of pipes and tubes.
NOTE: The following charts depicting heat transfer coefficients and pressure drops for various sizes of pipes and tubes are available in full page reproduction for greater accuracy in inter pretation. Write to;
Monsanto Company Organic Chemicals Div. 800 N. Lindbergh Blvd.
St. Louis, Mo. 63166
0l*25',b
22 1
TOWOLDMON0022957 WATER_PCB-00007426
THERMINOL FR-1 * HEAT THAHlll^dfMCWil<TlilJN*IOg *OMEDUL( -SO *IF*
10
to to 00 00 TO 100
too too COO 1000 2000 MOO 6000
FLOW-6.P.M.
HEAT TRANSFER COEFFICIENTS INSIDE TUBBS
0142547
|
TOWOLDMON0022958 WATER_PCB-00007427
THERMINOL FR-2
<1
TOWOLDMON0022959 WATER_PCB-00007428
THERMINOL. FR-3
-.ViV** 1
I 'A / ntfp ' v> +./r? *
wW <>
<.
< . - `
HBAT TRANSFER COEFFICIENTS INSIDE SCHEDULE 40 RIPE
I
HEAT TRANSFER COEFFICIENTS INSIDE TUBES
TOWOLDMON0022960 WATEFLPCB-00007429
THERMIINOL FR-1
0W550
26 |
TOWOLDMON0022961 WATER_PCB-00007430
THERMINOL FR-2
0 ` ,
m SO 40 50 ft) 100 COO 300 300 1000 FIOW-6.MII. '
1000 4000 <000 WOO
.' PRESSURE DROP IN TUBES
0142^1
|
TOWOLDMON0022962 ' WATER_PCB-00007431
THERMINOL FR-3
28 |
TOWOLDMON0022963 WATER_PCB-00007432
kesiSTANOB or valves and nniNos to plow or n-uios
' ^ -^A -4 Globe Valve, Open.
......., .
.
>** ' \ l Aslmpt way to account for the resistance
/fferodtofloWby valves end fittings is to
add to the length of pipe In the tine a
. length which Will fllve a pressure drop
equal to that which occurs in the valves
end fittings In the line. ,
>1000 Lspoo
Example: The dotted line Shows that the resistance of a 6-Inch Standard Elbow Is equivalent to approximately 16 feet of 6-Inch Standard Steel Pipe.
Angle Valve, Opei Jk
>1100
1!00 ` \ t
-
Swing Chech Valve, Fully Open
Close Return Beni
Standard Tee Through Side Outlet
f
rIJsS-_. Borda Entrance
Ifnrmo
-s
|
tJ t
r
ISudden Enlargement I--P/P-M.
y.----- --
" .10'
' VT'-
`
Em.. 't* S
a
S
*tv%.-----
Standard Elbow or
run <of Tee reduced H 1' ^
^Ordinary Enhance pp> ,,
i
* $s
I
*a<, -*
Isudden Conlractlon L--.d/D--X , -- J
,
.
fldedlumSweep Elbowor,
.run ot Tm reduces y,
i" > aYr
# f*
t, .fcoiipwimipSlbowtiUri*..',^'-"'
0142553
TOWOLDMON0022964 WATER PCB-00007433
PRESSURE DROP AND HEAT TRANSFER RATE FOR HEAT EXCHANOERS
7
,j
toobtaiS Mat transfer hate
: i. EWrtt..rt
ith 6PM
?. (. ChirfSiS W[- `
ft/sec. average
4. Correct h--(8 bove)-Jof temperature and
tube diameter.
, ->
Example:
`
THERMiNOL fR-2 WO*
80" Shell Ton 1#"
Baffles
10" Pitch
350 GPM 1
4. Correct h for temperature and tube diameter. . 825X0*1 048" **121 An*.
Fart All
NOTES:
` '
a. Tubes to be on trlanoular pilch %" 7>b*j . Von1)".
AH baffles cutl row oftubp* past horizontal
oentadi^f. ^ ?*
r
vS* w^s5+
. Chart* have base condition--on 'ft*"; Baffles at 8" pitch. THERMINOL FR-2 at
,, *50f. ? ,!
*
Vf^V '
it sw.'#**'
014255*
TOWOLDMON0022965 WATER PCB-00007434
0H2bbb
I
TOWOLDMON0022966 WATER_PCB-00007435
CHART NO. 1
7
t)>
w-
|
TOWOLDMON0022967 WATER_PCB-00007436
0142557
TOWOLDMON0022968 WATER_PCB-00007437
:i
CHART No. 3 i-j" * *
"j c-.-.
'ivVrtV-' , -itS \ . !,, J'*' --\
<'
''
t:
gejflyil^WmW* IJROP SHKL1. SIDB
"SwW'n'wiW*''' *`f-" ....... }*......... ..........
....
_____ i-j Lij j . i XT
TUBE DIAMETER CORRECTION
'
iw 1 .,-4 w i.
r)
; Afl j*,
../
./.ji
% INCH O.D. ON HL (NOHA
dFet ' B.67 .
M INCH O.D. ON % INCH A 140.
1 INCH O.D. ON WINCHES*' CM
TUBE LENGTH CORRECTION
FT, If FT. 16 FT.
'
fi 0.8
1.0 .
148
84 FT. ... *.00
-V
Hi X
*
jv `n -i
, .. / .
ntL4'
Ja .
A/ Z
WtFFLE CORRECTION
AVERAGE FLUID TEMPERATURE CORRECTION Te
..... 300
4D0
TEMPERATURE--V.
Ig
O <u.
1.0 Z
0.8 2
0.6 y 0.S O'
tc 04 O
A*1 . r/. 7 s
J6 til JO ... 15
BAFFLE PITCH-INCHES
IIHil
wMWdr/mmmm JBSELJL,
' ** * .\- < .
f/f\ f7 r i . ' CORRECTED VELOCITY-CHART No. 1 READING x Be
STEP t
rh i PRESSURE DROP-CHART 8 READING x Tc i Fc * Ft
m jj -- -............... - - 8 7 8 * 10
CORRECTED SHELL SIDE VELOCITY-FT./Sf:C.
E6 80 40 80 80 70 80 00 100
^^
l
5r. > .
`,
;
01425*8
TOWOLDMON0022969 WATER_PCB-00007438
(COSiTV ^ON^CRSION chart
I. T V` * >', I^nvortfn# Klpamatlc and $ayboH Viacoalty to Abaolute Viacoalty)
I <V^-".-a.; 'A', a" v - i'"
fe* j "*#. E,S^ / , ~ , W-
. ' Vx 'Vh*
* v?< ^^
it, i .&*. 1 1 , '1
'
h;t 1 7''' *$U*Y >.
>4,000
..... =........ ---r:-
Wt-Mco,
:^ooa;,-'.,. J/S't-I**:
-**< < ** . ... f-100 .l,S00 S ... f-*00
fi-w
MO-J ^V.,: ...........
' i-780 1 160-^ : '-.
M
I*
, s&
m r. ,
a1* ` ' ^ 1 (^
m
t '.' :
_,.......... *>< P*
|f * =-**
'*
i"-- > _ f -v> ; {% tFw . ri.V f .< v-
i*
V>W ?j
1 v. * ;, 4
j" '** "*' >
", ' VK` '
' > >'J -X {<-i
.s ,
tfc. :r M J&F*m 1* r
I'-. --
?:F-i.&i...... >______ _
. in1 ;-.
1.1 0 ^ CUOJ
1.0 10 -0
# Q > 0.0
'.*< . .. 1-00 1~' y o.a -
0.6
0H255<)
TOWOLDMON0022970 WATER PCB-00007439
ENGINEERING CONVERSION FACTORS
MULTIPLY
ATMOSPHERES
ATMOSPHERES
ATMOSPHERES
ATMOSPHERES
ATMOSPHERES
ATMOSPHERES
British thermal units
British thermal units
British thermal units
British thermal units
British thermal units
British thermal units
British thermal units
Btu/cu. ft.
Btu/hr.
Btu/hr. sq. ft.
Btu/|hr. sq. ft. F.)
Btu/(hr. sq. ft. F.)
Btu/(hr. sq. ft. F.)
B+u/(hr. sq. ft. 0 F.)
Btu/[hr. sq. ft. F.)
(Btu/hr. sq. ft.|/( F./in.J
(Btu/hr. sq. ft.)/( F./in.)
(Btu/hr. sq. ft.)/!0 F./ft.J
(Btu/hr. iq. ft.)/( F./ft.)
(Btu/hr. iq.
F./ft.)
Btu/min.
Btu/min.
Btu/min.
Btu/lb.
Btu/lb. mol.
Btu/lb. o F.
BY
14.70 2116.8 760 29.92 33.90 1.033 x 10' 778.2 107.6 1055 0.2520 3.930 x 10-* 2.930 x I0~J 0.5556 e.9o 3.927 x I0-1 2.712 4.882 1.0 1.356 x I0~4 5.68 x I0-J 2.035 x 10 s 12.4 3.445 x I0-4 4.13 x I0'3 0.0173 14.88 12.97 0.02358 0.01758 0.556 0.556 1.0
TO OBTAIN
Ib./sq. In. Ib./sq. ft. mm. Hg. in. Hg. ft. of water Vg./sq. meter
ib. kg.-meters joules kg.-eal. hp. hr. kw. hr. P.C.U.* kg.-cal./cu. meter hp. kg.-cal./hr. sq. meter kg.-cal./[hr. sq. meter C.) P.C.U.*/(br. sq. ft. C.) gram-cal./sec. cm.2 0 C. watts/cm.s 0 C. watts/sq. In. 0 F. (kg.-cal./hr. sq. meter)/(c C./cm.) (gram-cal./sec. cm.2)/( C./cm.) (gram-cal./sec. cm.2)/( C./cm.) (watts/cm.J)/( C./cm.) (gram-cal./hr. cm.2)/( C./cm.) ft. Ib./sec. hp. kw. gram-cal./gram gram-cal./gram mol. gram-cal./gram 0 C.
Pound-Cantigrad* Unit
01560
TOWOLDMON0022971 WATER_PCB-00007440
h-
t
MULTIPLY
Btu/sec.
Btu/sec. Btu/sec.
Btu/sec. Btu/sq. ft. Btu/sq. ft, CALORIES CENTIMETERS CENTIMETERS
cm. Hg. cm. Hg. cm. Hg. cm. Hg. cm. Hg. cm. Hg. cm./0 C. cm./sec. cm./sec. cm./sec. cm./sec. cm./sec. CENTIPOISES CENTIPOISES CENTIPOISES CENTIPOISES cubic centimefers cubic centimeters cubic centimeters cm.*/sec. cm.*/sec. cm.'/sec. cm.*/sec. cm.'/gram cm.`/gram mol.
CUBIC FEET CUBIC FEET
ENGINEERING CONVERSION FACTORS
BY
778.2
1.4147 1.0549
107.6 0.2712 2.712 See gram-cal. 0.3937 0.032(1
0.01316 0.1934 27.85 136.0 5.353 0.4461 0.2187 1.969 0.03281 0.036 0.60 0.02237 0.01 2.42 6.72 x 10" 3.60 0.06102 3.531 x 10-6 2.642 x I0-* 2.119 * I0"8 0.0864 0.01585 3.6 0.01602 0.01602
0.02832 7.481
TO OBTAIN
ft. Ib./sec. hp. kw. kg.-meter/sec. gram-cal./cm.* kg.-cal./sq. meter
in. . atm. Ib./sq. in. Ib./sq. ft. kg./sq. meter in. of water ft. of water in./ F. ft./min. ft./sec. km. /hr. meters/min. mph poises lb./ft. hr. Ib./ft. sec. kg./meter hr. cu. in. cu. ft. gel. cu. ft./min. cu. meter/day gal./min. liter/hr. cu. ft./lb. cu. ft./lb. mol. cu. meters gel.
0142S61
TOWOLDMON0022972 WATER_PCB-00007441
ENGINEERING CONVERSION FACTOFJS
T k
MULTIPLY
sum BY
TO OBTAIN
CUBIC FEET CUBIC FEET cu. ft. gas (60 F. at 1 atm) cu. ft./lb. cu. ft./min. cu. ft./min. cu. ft./sec. cu. ft./sec. sq. ft.
CUBIC INCHES CUBIC INCHES CUBIC INCHES CUBIC INCHES CUBIC METERS CUBIC METERS cu. meters/day
degrees/sec. degrees/sec. ERGS FEET FEET ft. of water ft. of water ft. of water ft. of water ft. of water ft. of water ft./min. ft./min. ft./min. ft./min. ft./sec. ft./sec. ft./sec. FOOT POUNDS
FOOT POUNDS
FOOT POUNDS FOOT POUNDS
318.32 62.43 2.636 x 10 62.43 472.0 0.1247 448.8 0.0305 16.39 .787 x 10 0.01639 4.329 x 10 "8 35.31 264.2 11.57 2.778 x I0-S 0.1667 1.0 x I0-7 30.48 0.3048 0.0295 2.242 0.8826 304.8 62.43 0.4335 0.508 0.01667 0.01829 0.01136 1.097 18.29 0.6818 1.285 x 10-* 3.239 x 10-4
3.766 x 10 "7 5.05 * I0-7
Uteri lb. of water lb. mol. cm.*/gram cm.8/sec. gal./sec. gal./min. liters/sec. cm,8 cm.8 cu. ft. liters gal. cu. ft. gal. cm.8/sec.
rev./sec. rpm joules cm. meters atm. cm. Hg. in. Hg. kg./sq. meter Ib./sq. ft. Ib./sq. in. em./sec. ft./sec. Icm./hr.
mph km./hr. meters/min. mph Btu kg.*cal.
lew. hr. tip. hr.
A
I [ I | 1 ! 1 i
'Pound-Ctntigrad* UnH
MmaBsas^jmse:\ V
o\^bl
||
TOWOLDMON0022973 WATER_PCB-00007442
!
'T"
4;"
j ( 1 | j
\
fi
' k
i,
MULTIPLY
(ENGINEERING CONVERSION FACTORS
_ i_ _ _ t
nr
'
TO OBTAIN
ft. lb./min. ft. Ib./min.
ft. Ib./sec. ft. Ib./sec. ft. Ib./sec. ft. Ib./tec. GALLONS (imperial) gal. (U.S.) gal. (U.S.) gal. (U.S.) gal. (U.S.) gal./hr. gal./min. gal./min. gal./min. gal./min. of water GRAMS GRAMS
gram mole gas gram-cal. grem-col./gram gram-cal./gram mol. gram-cal./gram C. gram-cal./cm.2 (gram-cal./cm.2)/cm. gram-cal./(tec. cm.2 C.) (gram-cal./sec. cm.2)/( C./cm.) gram-cm. gram-cm. gram-cm. gram-cm. grams/cm. grams/cm.8 grams/cm.8 grams/cm.8 grams/cm.2 grams/cm.2 grams/cm.2
3.03 x I0"s 2.26 x 10-' 0.0771 1.818 x I0's 0.01943 1.356 x I0-8 1.201 231 0.1337 3785 3.785 3.71 x I0-8 2.228 x I0-' 0.227 0.06304 500.8 980.7 2.205 x I0-8 2.24 x 10* 3.968 x I0-3 1.8 1.8 1.0 3.687 1.452 7.373 >t 10s 2.903 x I0? 9.294 )i 10- 980.6 7.233 >i 10 -8 2.342 x I0-8 5.60 * I0~ 1.0 62.43 0.07355 10 0.394 0.03281
hp. kw. Btu/mrn. hp. kg.-cal./min. lw.
gal. (U.S.) eu. in. cu. ft. cm.8 liters cu. ft./sec. cu. ft./sec. cu. meters/hr. liters/sec. Ib./hr. of water dynes ib. cm. gas (0 C. end 760 mm.)
Btu Btu/lb. Btu/lb. mol. Btu/lb. 0 F. Btu/sq. ft. (Btu/sq. ft.)/in. Btu/(Kr. sq. ft. 0 F.) (Btu/hr. sq. ft.)/( F./in.) Btu ergs ft. lb. Itg.-eal. Ib./in. specific gravity at 4 C. Ib./cu. ft. cm. Hg. itg./sq. meter in. of water ft. of water
mamsaBB-
TOWOLDMON0022974 WATER_PCB-00007443
ENGINEERING CONVERSION FACTORS
MULTIPLY
grams/cm.s grams/cm.* grams/cm.1 HORSEPOWER HORSEPOWER HORSEPOWER HORSEPOWER HORSEPOWER hp. (boiler) hp. (boiler) hp. hr. hp. hr. hp. hr. hp. hr. hp. hr. hp. hr. hp. hr. INCHES in. Hg. in. Hg. in. Hg. in. Hg. in. Hg. in. of water in. of water in. of water in. of water in. of water in. of water in./0 F. KILOGRAMS KILOGRAMS KILOGRAMS KILOGRAMS kg.-meters kg.-meters kg.-meters kg.-meters
BY
9.478 x 100.01422 2.046 42.41 3.3 x I04 550 10.7 0.7457 3.3479 x I04 9.804 2.545 x 10s 1.98 x 10 2.484 x 10s 441.2 2.737 x I05 0.7457 1.414 x 10s 2.54 0.03342 1.133 0.4912 70.73 345.3 2.458 x 10"' 0.07355 0.1849 25.40 0.03613 5.202 4.572 9.807 x 10* 70.93 7.205 1.102 x 10 "8 9.302 x 10-8 7.233 2.344 x IO- 2.724 x IO-
TO OBTAIN
atm. Ib./sq. in. Ib./sq. ft. Btu/min. ft. Ib./min. ft. Ib./tec. kg.-cal./min. kw. Btu/hr. kw. Btu ft. lb. joules kg..cal. kg.-meters kw. hr. P.C.U.* cm. atm. ft. of water Ib./sq. in. Ib./sq. ft. kg./sq. meter atm. in. Hg. cm. Hg. kg./sq. meter Ib./sq. in. Ib./sq. ft. cm./ C. dynes poundals lb. tons (short) Btu ft. lb. kg..cal. kw. hr.
#
01*256'.
TOWOLDMON0022975 WATER_PCB-00007444
(ENGINEERING CONVERSION FACTORS
[
| t !
^
W
1 '
MULTIPLY
kg.-meters kg./cu. meter kg./cu. meter kg./meter kg./tq, meter kg./iq. meter
kg./tq. meter kg./tq. meter kg./tq. meter kg./tq. meter KILOMETERS KILOMETERS km./hr. km./hr. km./hr. km./hr. KILOWATTS KILOWATTS KILOWATTS
KILOWATTS KILOWATTS KILOWATTS kw. hr. kw. hr. kw. hr. Lw. hr. tw. hr. kw. hr. LITERS LITERS LITERS LITERS LITERS liters/gram mol. liters/hr. liters/kg. liters/min. liters/min.
BY
5.165 x 1C'8 1.0 x IO-> 0.062431 0.6720 9.678 x I0-S 7.355 x I0~3 3.281 x I0-* 2.896 x I0-8 0.2048 1.422 x I0-8 3.281 x 10s 0.6214 27.78 54.68 0.9113 16.67 56.92 4.425 x 10* 737.6 1.341 14.34 1 x 10* 3.413 x 10s 2.655 x 10s 1.341 3.6 x 10 860.5 1.895 x I08 1 x 10 0.0353 61.02 0.2642 1.057 16.02 0.2778 0.01602 6.0 x 10* 5.885 x I0-J
Iir. "OTriMSu.!:?
TO OBTAIN
P.C.U.* gram/cm.8 Ib./cu. ft. lb./Et. atm. cm. Hg. ft, of water In. Hg. !b./tq. ft. Ib./tq. in. ft. ml. cm./sec. ft./min. ft./tec. meters/min. Btu/min. ft. Ib./min. ft. Ib./sec. hp. kg.-cal./min. watts Btu ft. lb. hp. hr. joules kg.-cal. P.C.U.* cm.3 cu. ft. cu. in. gal. (U.S.) qt. |liq.) cu. ft./lb. mol. em.Vsec. cu. ft./lb. cm.3/hr. cu. ft/tec.
Pound-Centigr*d* Unit
01*2565
TOWOLDMON0022976 WATER PCB-00007445
ENGINEERING CONVERSION FACTORS
` MULTIPLY
--
BY
TO OBTAIN
liters/min. liters/min. liters/sec. cm.* METERS METERS meter*/0 C. meters/min.
meters/min. meter*/min. meters/min. meters/sec. meters/sec. meter*/sec. OUNCES OUNCES OUNCES (fluid) OUNCES (fluid) ox./sq. in. POISES POUNDS POUNDS POUNDS lb. mol* gas lb. of water lb. of water lb. of water/hr. lb. of water/hr. Ib./cu. ft. Ib./cu. ft. Ib./cu. in. Ib./ft. Ib./ff. hr. Ib./ft. hr. Ib./gal. Ib./in. Ib./tq. ft. Ib./iq. ft.
15.851 4.403 x I0'J 32.8 3.281 39.37 1.824 1.667
0.05468 0.06 0.03728 196.8
3.6 2.237 28.35 0.0625 1.805 0.02957 1.732 l 4.448 x 10s 453.6 32.17 379.4 0.01602 0.1198 2.669 x I0-* 1.997 x I0-S 0.01602
16.02 27.68 1.468 1 4.13 x I0-3
1 0.413 1 0.1198
I 178.6 0.01602
4.882
, gal./hr. gal./tec. cu. ft./tec. *q. ft. in. ft./0 F. cm./sec. ft./sec. km./hr.
1 mph 1 ft./min.
km./hr. mph
grams lb. cu. In. liters in. of water gram/cm. sec. dynes grams poundals 1 cu. ft. gas (60 cu. ft. j gal. cu. ft./min. gal./min. 1 grams/cm.3 kg./cu. meter 1 grams/cm.3 kg./meter | grams/cm. sec. centipoises grams/cm.3 grams/cm. ft. of water kg./sq. meter
* S \ \A A
Ol425<t>
TOWOLDMON0022977 WATER_PCB-00007446
ENGINEERING CONVERSION FACTORS
MULTIPLY
BY
TO OBTAIN
Ib./sq. ft. Ib./sq. Sn. Ib./sq. in. Ib./sq. in. Ib./sq. in. Ib./sq. in. Ib./sq. in. REFRIGERATION--STD. TON SQUARE CENTIMETERS SQUARE CENTIMETERS SQUARE FEET SQUARE FEET SQUARE FEET SQUARE INCHES SQUARE INCHES SQUARE INCHES SQUARE KILOMETERS SQUARE KILOMETERS SQUARE METERS temperature 0 C. 273 temperature C. 17.8 temperature 0 F. 460 temperature c> F. --32 TONS (long) TONS (long) tons (metric) tons (metric) tons (short) tons (short) tons (short)/sq. ft. tons (short)/sq. ft. tons (short)/sq. in. tons (short)/sq. in. tons of refrigeration WATTS WATTS WATTS
6.944 x I0-3 0.06804 2.307 2.036 51.7 703.1 144 200 1.074 x I0-" 0.1550 929 144 0.0929 6.452 6.944 x 10- 3 6.452 x I0< 1.076 x I07 0.3861 10.76 1.0 1.8
1.0
0.5555 1.016 x 10* 2.24 x 10" 1 x 10' 2.205 x 10" 907.2 2 x 10" 9.765 x I01
13.89
1.406 I0*1 2 x 10" See refrigeration 0.05692 1 x 10 44.26
Ib./sq. in. atm. ft. of water in. Hg. mm. Hg. Icg./sq. meter Ib./sq. ft. Btu/min. sq. ft. sq. in. sq. cm. sq. in. sq. meters
cm.z sq. ft. sq. meters sq. ft. sq. mi. sq. ft. abs. temp. K. temp. F. abs. temp. 0 R. temp. C. kg.
lb. kg. ib. kg. ib. kg./sq. meter Ib./sq. in. kg./sq. meter Ib./sq. in.
Btu/min. ergs/sec. ft. Ib./mln.
JB*-
01*2567
TOWOLDMON0022978 WATER PCB-00007447
ENGINEERING CONVERSION FACTORS
MULTIPLY
WATTS WATTS WATTS WATTS WATT HOURS WATT HOURS WATT HOURS WATT HOURS WATT HOURS WEEK WEEK WEEK YEARS (common]
BY
0.7376 11.341 x I0-5 0.01434 1.0 X 10 3 1.413 ;.655 x 10* 11.341 x I0-3 0.8605 367.1 1166 11.008 x 106.048 x 10* 8.76 x I03
TO OBTAIN
ft. Ib./sec. hp. kg.-cal./min. kw. Btu ft. lb. hp. hr. kg.-cal. kg.-meter hr. min. tec. hr.
STEEL PIPE DIMENSIONS--CAPACITIES AND WEIGHTS*
Nominal Outside
Wall
pipe dlam.. Schedule thick
alia. in.
In.
no. ness, In.
W
0.510
40
94 0.675 40
Vi o.bio 40
K
1.050
40
1
1.315
40
IV.
1.600
40
1H
1.990
40
7.
7.315
40
m 7.815 40
3
3.500
40
m 4.000 40
4
4.500
40
5
5.563
40
6
6.625
40
8
8.625
40
10 10.75 40
1? 12.75 40
088 091 109 113 133 140 145 154 .203 .216 .226 237
258 .280 .322 .365 .406
Basad cm A. S. A. Standards B36.I0-
diain.
in.
.364 .493 .622 .824 1.049 1.380 1.610 2.067 2.469 3.068 3.548 4 026 5.047 6.065 7.981 10.020 11.938
Cross sectional
area metal. s<|. In
Inside sectional
area. sq.ft.
.125 .167 .250 .333 .494 .669 .799 1.075 1.704 2.221 2.680 3.173 4.304 5.586 8.396 11.90 15.77
.00072 .00133
.00211 .00371 .00600 .01040 .01414 .02330 .03322 .05130 .06870 .08840 .1390 .2006 .3474 .5475 .7773
Circumference, ft., or surface sq. ft. per ft., of
length
Outside Inside
.141 .177
.220 .275 344 .435 .498 .622 .753 .917 1.047 1.178 1X56
1.734 2258 2814 3338
.0954 .1293 .1630 .2158 .2745 .362 .422 .542 .647 .804 .930 1.055 1.32?
1.590 2.090 2.620 3.13
Capacity at 1 tt. per sec. velocity
11. S. lb. per hr. gal. per water
min.
.323 .596 .945 1665 2.690 4.57 634 10.45 1492 23.00 30.80 39 6 62 3 900 155 7 246 0 349.0
161 5 298.0 472 5
832 5 1,3450 2,285.0 3,170.0 5,225.0 7,460 0 11,500.0 15.4000 19,8000 31,1500 45.000.0 77,850.0 123,000 0 174,500.0
Weight Of pipe per ft.
lb.
.43 .57 .85 113 1.68 2.28 2.72 366 5.80 7.58 9.11 10.8 II 7 19.0 28.6 40.5 53.6
01*2*68
||
TOWOLDMON0022979 WATER_PCB-00007448
TYPICAL APPLICATIONS FOR
fhOPITlijinlk
n LIQUID HEATING SYSTEMS...
Indirect liquid heating with THERMINOL FR systems is recommended wherever lowpressure, high-temperature proc essing-requiring safe, uniform delivery of heat--is needed. Here are a few typical applications.
)
CHEMICAL PROCESSING .. . especially where flammable materials are handled.
VARNISHES AND RESINS PROCESSING . . . where a single "circuit" with multiple users and varying temperatures is desirable.
PLASTICS AND RUBBER MOLDING .. . where uniform heating, rapid temperature flux, and pin-point control is essential.
BITUMINOUS MATERIALS HEATING . . . for maximum safety where explosive gases and volatile fumes occur.
FOOD PROCESSING .. . for controlled, quality "cooking" of potato chips, pre-cooked soups, other foodstuffs.
MATERIALS CONVERSION ... to heat corrugating rolls, crimping presses, calenders.
METALS TREATING OVENS ... for heat-treating metals such as titanium and vanadium; for "seasoning" weldments, castings and forgings.
MAILT COOKING AND LIQUID DISTILLATION . . . for efficient indirect heating of distillation equipment.
____J12569
I
TOWOLDMON0022980
WATER_PCB-00007449
--thermJLtTLoIk fr
SAFETY OF HANDLING
E
m
I
On the basis of animal toxicity studies, THERMINOL FR may be considered only slightly toxic from the standpoint of acci dental massive skin exposure or accidental ingestion. Similarly, single exposures to high concentrations of vapors (when heated suffi ciently to volatilize) or high concentrations of decomposition products (if the fluid is accidentally discharged into the fire chamber) ate not serious hazards because the irritating character of such concentrations preclude vol untary exposure.
Repeated or prolonged skin exposure should be avoided since THERMINOL FR acts as a solvent for fats and oils of the skin. Re moval of these natural, protective barriers can lead to drying and chapping such as occurs with exposures to paint thinnere. More important, THERMINOL FR may be ab sorbed if it is allowed to remain on the unbroken skin. For these reasons, we recom mend that the skin be washed with soap and water if there is contact. A skin burn resulting from accidental contact with hot fluid should be treated in the normal manner for any thermal burn due to hot oils.
Because of its low vapor pressure, there is no significant vapor inhalation hazard when THERMINOL FR is at room temperature. For example, there is no vapor exposure prob lem while transferring the fluid from its ship ping container to the heat transfer system. On the other hand, the vapors emitted by THERMINOL FR heated to elevated tem peratures are injurious on prolonged exposure. It is indicated that the "threshold limit value" or atmospheric vapor concentration which cannot be safely exceeded (on a daily basis) is 0.6--1.0 milligrams of THERMINOL FR vapor per cubic meter of air in the workroom. In 'heat transfer installations, the fluid must be used in a closed system free from leaks with the expansion tank vented to the out doors. Accordingly, there should be little or no opportunity for workers to come in con tact with vapors.