CHAPTER 46
1948 Guide
- Further, the velocity contours are identical for similar hood shapes when the hoods sire reduced to the same basis of comparison. Theise facts are applicable to all hood problems .so that when the velocity contour
distribution is known, the air flow required can be determined. . Fig. 1 shows the contour distribution in two axial planes perpendicular to the sides of a rectangular hood with a side ratio of one-half. The distribu
tion shown is identical for all openings with a similar side ratio provided the' mapping is as shown in the figure. The contours, of course, are expressed as percentages of the velocity at the opening.
Low Velocity Systems
On multiple installations of the same operation it is often possible to institute a great saying, in power cost by designing an exhaust system
. Velocity at the Opening
using low velocities in the main ducts. Such a' system for use in grinding and shaping porcelain has been described *. In these operations, the separate machines are grouped around a central plenum chamber and exhausted by means of a low pressure fan connected to the plenum. In this case a power saving of: over 90 per cent was obtained. A similar design technique10 has been described for use in ventilating plating tanks.
Large Open Hoods .
Large hoods, such as may- be used for electroplating and pickling tanks, should be sub-divided, so the' area of the connecting duct is not less, than one-fifteenth of the open area of the hood. ` Frequently, it will be found necessary to branch the main duct in order to obtain a uniform distri-
Exhausting and Conveying Systems
833
bution of flow. Canopy hoods should extend 6 in. laterally-from the tank for every 12 in. elevation, and wherever possible they should have side and rear aprons so as to prevent short circuiting of air from spaces not directly over the vats or tanks. In most cases, hoods of this type- take advantage of the natural tendency of the vapors to rise, and air velocities may be kept low. Cross drafts from open doors or. windows disturb the rise of the vapors and therefore provision must be made for them. The air velocities required also depend-upon the character of the vapors, given off, cyanide fumes, for example, requiring an .air velocity of approxi mately 75 fpm on the surface of the . tank- and acid and-steam vapors requiring velocities as low as 25 to 50 fpm. The total volume .of air .flow necessary to obtain these velocities may be approximately determined
from the equation:
Q = IAPDV
(4)
where
Q = total volume of air handled by hood, cubic feet per minute.
P = perimeter of the tank, feet. "
1
D = distance between tank and hood opening, feet.
V = air velocity desired along edges and surface of tank, feet per minute.
Lateral Exhaust Systems
The lateral exhaust method, as developed for chromium plating ", is applicable in many instances in preference to the canopy type hoods. The method makes use of drawing air and fumes laterally across the top of vats or tanks into slotted ducts at the top and extending fully along one or more sides of the tanks. The slots are 1 in. wide mid for effective ventilation a 2000 fpm exhaust air velocity at the slot, face is advisable. In addition, the duct should not be required to draw the air laterally for a distance of more than 18 in. and the level of the solution should be kept 6 to 8 in. below the top of the tanks. If width of tank is over 18 in. a double lateral exhaust may be used with Slots on both sides.
It has also been determined that a similar control may be used for tainks wider than 3 ft when the same velocity (2000 fpm) is maintained through a slot which is increased J4 in. for every foot of width greater than 3 ft. When these slots must be extended more than 6 ft in length, some method of spreading the flow is necessary to provide even air flow distribution through the entire slot length. This can be accomplished by tapering the slot, which incidentally will add to the resistance of the system. A more economical approach is to place properly spaced vanes in the side ducts, or to branch the side ducts
y The flexible exhaust tube method may be advantageously used for \ removing dust or fumes. Flexible tubes having one end connected to an
exhaust system and a slotted hood attached to the other end may be shaped at will to fit in with industrial processes without affecting the ease of operation. Efficient dust or fume removal may -be had with use of relatively small exhaust volumes. This type of system may be used on swing grinders, portable grinding wheels, soldering operations, stone cutting, rock drilling, etc.
Spray Booths
In the design of an efficient spray booth, it is essential to maintain an even distribution of air flow through the opening and about the object being sprayed. While in many instances spraying operations can be