Document peqKLvaqBJRbe3kVGeEYmy83a

396 CHAPTER 27 1960 Guide Table 1 .... Unit Steam Consumption of Process Equipment* Kitchen AppfioncM (exdwtfue of water hoofing) Cormunpffon,* lb Pressure, par Hr pda Hospital Equipment Consump tion,* ib Pnsvrs, par Hr pa'0 Stock and vegetable kettles (per 5 gal) Vegetable steamers (per compartment) Steam tables (per sq ft) Bain-Maries (per sq ft) Coffee urns (per gat) 20.0 40.0 1.7 3.4 3.4 Water urns (per gal) Soup warmers (30 x 30 x 28 in.) Egg boilers (3 compartments) Clam, lobster, and potato steamers (per com- partment) Oyster pots 5.0 100.0 18.0 40.0 18.0 Plate and cup warmers (per 20 cu ft) Food-warming ovens (per 20 cu ft) Silver burnishes and washers Dishwashers (per tray) 35.0 35.0 69.0 60.0 7-20 7-20 7-20 7-20 7-20 7-20 7-20 7-20 7-20 7-20 7-20 7-20 7-20 7-20 Sterilizers, for bottles or pasteurization (per bottle) Sterilizers, for water, (per gal) Sterilizers, for instruments and utensils 8 x 9 x 18 in., water depth 3H in. 9 x 10 x 20 in., water depth 3K in. 10 x 12 x 22 in., water depth 4 in. 12 x 16 x 24 in., water depth 4 in. 10 x 12 x 36 in., water depth 4 in. 16 x 15 x 20 in., water depth 10 io. 20 x 20 x 24 in., water depth 24 in. Sterilisers, for instruments @ 240-250 F 12 x 20 in. 14 x 22 in. 16 x 24 in. laundry Equipment Tumblers 40 x 94 io. 30 x 36 in. Washers, (per gal water heated) Flatwork ironers. 100 to 120 in. ehest type (per roll) 50 to 100 in. cylinder type (per machine) Standard presses Large shirt body presses Cuff and neckband presses Sleevers Steam-electric irons Woolen pressing machines Large---electric vacuum Small--electric vacuum Large--steam vacuum Small--steam vacuum Feather cleaning and sterilizing 15 pillows per hr 360 225 j 60 60-120 105 190 15 12 8 25 12 35 20 175 100 100 15-100 100 100 100 100 100 100 100 65 65 65 65 100 Sterilizers, for surgical supplies 10 x 20 in. 12 x 20 in. 14 x 22 in. 16 x 24 in. 16 x 36 in. 20 x 28 in. 20 x 36 in. 20 x 48 in. 20 x 60 in. Sterilizers, (autoclave) (240-250 F) 15-5 x 24 in. 17.5 x 26 in. 21.5 x 30 in. 24 x 36 in. Disinfector, mattress 30 x 42 x 84 in. 60 x 66 x 108 in. Blanket warmers 18 x 24 x 72 in. * From DUtriet Stating Handbook (Nation*! District Westing Association, Third Edition, ttSl). b Tfaeaa vataea rapnaent approximate requirements alter warm-op period. 1 12 27 30 39 60 66 92 144 48 60 72 10 22 28 38 54 60 78 98 124 24 32 40 42 42 318 4 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 35-60 35-60 35-60 in the district heating industry because of their relatively high first cost as compared with smaller conduits uniea they are re quired to accommodate miscellaneous other services or to pro vide underground passage between buildings. 4. Overhead piping on poles or structures is generally less expensive than underground lines, especially in some institu tional and industrial areas and may be a means of eliminating buried conduit in areas where underground installations would be expensive or undesirable. Thin corrugated aluminum sheets or asphalt-saturated asbestos felt are available for covering the insulation on lines exposed to the weather. Such lines may introduce freeze-up problems, higher heat lasses and, in many locations, would be considered unsightly. 5. Higb-pressure transmission feeders may be employed where the plant is remote from the distribution area, or where it is desirable to augment the capacity of an istiog system Design of such feeders and of distribution systems for various load conditions is covered fully in District Heating Handbook, 3rd Edition* 6. Piping routed in loops with suitable valves to provide alternate feeds for major loads, allows service to be maintained despite trouble in any one feeder.4 7. It is desirable to estimate as far as possible the probable growth and change in load centers. Since character of the dis trict served is almost certain to change with time the distribu tion system must be planned so that it can be adapted to accommodate changes. It is helpful to provide a master dis tribution plan which can be revised from time to time to suit conditions as the system grows. Steam Distribution Pressure The pressure at which the steam is to be distributed will depend upon that available at the plant and pressure re quirements of apparatus to be served.* The advantages of low-pressure distribution (2 to 50 psig) compared with high pressure are: (1) lower heat loss per square foot of pipe surface; (2) lower losses from leakage, trap discharge, and venting; (3) less trouble with traps and valves; (4) less trouble from flash steam at drain age points; (5) simplified problems in pressure reduction at the buildings; (6) suitability of standard fittings; and (7) general reduction in maintenance costs. Some heating companies find that the overall losses in relation to steam delivery are higher with high-pressure dis tribution. With distribution pressures not exceeding 50 peig, there is less danger if the full distribution pressure should build up in the radiators or heaters through the faulty operation of pressure-regulating valves. With pressures District Heating Table 2 .... Annual Steam Consumption for Water Heating for Various Types of Buildings, per Cu Ft of Volume*'* Type of Buddmg CoAOUBptioO, Ib/IVr) (Cu ft) Consumption tb/lYr) (Cu ft) (100 F dag Tamp. Rita of Water) Residence club Apartment house 3.20 2.56 2.41 2.66 2.11 1.99 Department store Theater Parking garage 0.95 0.85 0.57 0.46 0.79 0.71 0.48 0.38 Baaed a attalyuss by fourteen district beatific companies bom metered coosumptions. Building volume is approximate croaa volume. b From District Utatxn* Handbook (National District Heating Association, Third Edition, 1851, p. 847). 397 Table 3 .... Load Duration for Typical District-Heating System (Comvfotswu Howrv r,f Pt&+ Sesd'Cft par Year at Various Loads Exprauud m htwit el ledi Hourly load*) Plant Output % of Rook Hours par Year Want Output %ofPaak Hour* pur Year 100 5 55 1800 95 40 50 2200 90 90 40 3100 85 150 30 4100 80 300 20 5150 75 500 15 5700 70 750 10 6400 65 1050 6 8760 60 1400 * Baaed on curve oo pace 89, District HtaSin* Handbook, Third Edition, 1951. Note: A plant having a peak aend-oet of 200,000 lb per hr will send out 80,000 (80 percent at 100,000) lb per hr or mar* for 800 hr per jrr. higher than 50 psig, or the safe working pressure of heating or process equipment, a second pressure-reducing valve or some form of emergency relief is required to prevent exces sive pressures in the radiators or other equipment.* Pressure reducing valves are more fully described in Chapter 26 (Steam Hearing Systems). The installation of reducing valves on district steam installations, however, may present specific problems that are not normally encountered in building steam hearing applications. Utility companies in some instances must ^imp greater responsibilities in their operation and maintenance and are often under regulations that are different for various cities. The advantages of high-pressure distribution are: (1) smaller pipe sizes; (2) availability of the steam for various other operations requiring higher pressures than the build ing heating system; and (3) wider flexibility in allowance for maximum pressure drop. Where distribution pressures are not as high as desired, higher pressures can be obtained by use of a steam compressor.* It is sometimes desirable to install a separate high-pressure fine from the boiler plant for steam supply to laundries or other high-pressure equipment rather than to operate the entire distribution system at higher pressures. Pipe Sizes In district heating work it is common practice to design the piping system on the basis of pressure drop. The initial pressure and the minimum permissible terminal pressure are specified, and the pipe sizes are so chosen that the required amount of steam, with suitable allowances for future in creases, will be transmitted without exceeding this pressure drop. The steam velocity is therefore almost disregarded and may be very high. Velocities of 35,000 fpm are not considered high for pipes in conduits. Where pipes pass through build ings, however, consideration should be given to the pos sibility of objectionable noise due to high velocity. By the use of permissible pressure drops with high velocities, after allowance has been made for future increase in load, the pipe sizes may be kept to a minimum with consequent savings in investment. Some lines in a loop system may need to be in creased in size in order to handle reverse-direction flow in emergencies.4 The steam flowing through any section of the piping can be computed from a study of the hourly steam,requirements of the several buildings served. In this connection, allowance should be made for the diversity of the load, that is, the ratio of the coincident maximum demand of all of the group of buildings served by the main, to the sum of the individual muTimum demands of each of the buildings served. This ratio is known ss the Coincidence Factor and varies from 0.50 in some institutional groups to 0.90 in areas where loads are principally for heating and heat is turned on at about the same time each morning. Consideration should also be given to the net total load on a line, based on a study of the loads in the various buildings, in order to determine the relative merits of providing one or more separate supply lines to serve all-year loads. Such lines will permit turning off the mftirw that supply strictly seasonal space-heating loads during the summer months. When lengths of pipe, steam quantities, and initial and terminal pressures have been chosen, the pipe sizes can be calculated by means of Figs. 22 to 26 of Chapter 26. The district-heating industry, however, uses Unwin's formula for determining pipe sizes because pressure drops can be de termined simply and directly from a chart. This formula has been checked by tests, and found correct within ranges of velocity used in district heating. A convenient chart de veloped from this formula is available from the National District Heating Association.' Conduits for Piping Conduits for underground steam pipes are used to pro tect the pipe and insulation from external damage and to provide a space in which the pipe is free to expand or con tract while held in proper alignment. The conduit should be constructed of non-corrosive materials, or, if of metallic content, should be suitably protected against corrosion. It must be of adequate strength to withstand the earth and traffic forces to which it will be subjected. The conduit should be reasonably waterproof and in many cases provirion should be made to drain seepage from its inride. With any form of conduit unless it is actually below water level, provirion should be made to completely exclude water or to carry away ground water and prevent it from collecting around the conduit. This is often accomplished by placing & layer of coarse gravel or stone underneath and partly surrounding the conduit with one or two lines of tile having open joints which serve to carry the water to a sewer or other suitable