Document peRq93dqwB5RLyJJ366JnoRYw
FSSA ECHA Science
25 September 2023
Executive Summary
FSSA supports rational, science-based efforts to eliminate sources of harm to humans and the environment. Eliminating all PFAS materials due to an unnecessarily broad classification of compounds creates a high risk to society. Because of this, we advocate for a scientific approach that distinguishes Persistent, Bioaccumulative and Toxic PFAS (PBTs) compounds from those that are not known to be PBT or are less so, based upon the best available science. Current science supports that clean extinguishing agents used in fire and explosion protection applications are generally safe when used in accordance with current codes and standards. Any proposed regulation of the sale or use of PFAS should exclude Clean Agents.
Treating all PFAS compounds as a single regulatory group is an approach that is inappropriate and unnecessary. PFAS is a large, diverse group of chemical compounds. All PFAS are not the same - their properties vary widely. Chemical and structural differences among different types of PFAS result in vast differences in physicalchemical properties. Their striking differences, both chemically and physically, must be considered in any effort to understand and address potential health and/or environmental risks.
Implementing broad regulations that ban all PFAS compounds without first considering the scientific evidence and carefully assessing what impact such a ban could have on society, could result in unintended consequences. Furthermore, banning all PFAS compounds is likely to hamper the ability of businesses and consumers to access essential products and obtain replacement parts that are needed to keep mission-critical operations functioning.
Clean extinguishing agents are components recognized and approved for use in listed and/or approved fire suppression systems. They are neat agents or blends of neat agents and are not designed with water as a functional component. Clean extinguishing agents have no affinity to water, nor do they partition to groundwater. They are not PFOA nor PFOS. They are non-ozone depleting and their use has been highly regulated for decades.
A risk assessment for halocarbon clean extinguishing agents (herein referred to as clean extinguishing agents) meeting the definition of per and polyfluoroalkyl substances (PFAS) allows these fire suppression alternatives to be used safely and responsibly in a manner to the satisfaction of the Authority Having Jurisdiction (AHJ) and to comply with regulatory restrictions in force. In addition, other important stakeholders are typically included in the risk assessment process. All involved contribute to an informed protection decision so a proper approval can be promulgated and an effective protection system implemented.
Those stakeholders normally are:
a. Registered professional engineers experienced in fire protection and life safety system design and risk assessment.
b. The owner or owner's representative. c. Insurance Authority. d. Representatives of the authority having jurisdiction. e. Representatives of emergency response entities. f. Building design professionals (architectural, structural, civil, mechanical,
plumbing, and electrical design professionals).
Systems using clean extinguishing agents are designed for fast detection and extinguishment, leaving no residue or contamination. Using sustainable, clean agent protection reduces costs from potential fire damage or remediation due to non-clean agent system discharges while minimizing installation, ongoing inspection, testing and maintenance costs.
There are multiple clean extinguishing agents currently in commercial use today. They protect data and telecommunications centers, power facilities, aircraft, museums, archives, and military installations and equipment -- all hazards with high damageability should they be left unprotected or exposed to foam or water. Systems using clean extinguishing agents have been installed in hundreds 100s of thousands of applications globally since the early 1990s and are subject to current and future regulatory mandates to assure their responsible use.
For the sake of example, we will focus in detail on one clean extinguishing agent that meets the definition of PFAS, FK-5-1-12, recognized for its versatility in a broad spectrum of critical applications.
Environmental and Regulatory Considerations
FK-5-1-12 is listed by the USEPA under the Significant New Alternatives Policy (SNAP) program as acceptable for total flooding end use for both normally occupied and unoccupied spaces as well as streaming applications. Excerpted from the final rule promulgated in 2002i:
"EPA has reviewed the potential environmental impacts of this substitute and has concluded that, by comparison to halon 1301 and other acceptable substitutes, C6perfluoroketone [FK-5-1-12] significantly reduces overall risk to the environment. With no ozone-depletion potential, a global warming potential value of less than 100, and an atmospheric lifetime of less than three days, C6-perfluoroketone provides an improvement over use of halon 1301, hydrochlorofluorocarbons (HCFCs) and hydrofluorocarbons (HFCs) in fire protection. We find that C6- perfluoro ketone is acceptable because it reduces overall risk to public health and the environment in the end use listed."
FK-5-1-12 complies with all relevant, global regulatory requirements. Table 1 below is a list of the agencies for which FK-5-1-12 has gained chemical registry approvals:
2
Chemical Registry Approvals Chemical: dodecafluoro-2-methylpentan-3-one (FK-5-1-12) CAS#:756-13-8
USA (TSCA)
Listed
Canada (CDSL)
Listed
EU (ELINCS)
EC# 436-710-6
Australia (AICS)
Listed
Japan (METI)
METI# (2)-4024
Korea (KECI)
KECI# 2002-3-2022
China (IECSC)
Listed
Philippines (PICCS)
Listed
Table 1: Global Chemical Registry Approvals for FK-5-1-12
PFOA and PFOS
FK-5-1-12 is a neat (pure, single component) agent. Industry end users recognize the dangers of PFOA and PFOS as the environmentally and biologically dangerous molecules subject to current regulatory scrutiny. FK-5-1-12, like all other clean extinguishing agents, has no affinity with PFOA or PFOS, functional components in AFFF (Aqueous Film Forming Foam). Unlike AFFF, which may partition to the groundwater in end use, FK-5-1-12 will quickly become a gas when discharged from a properly designed fire protection system, and it partitions to the atmosphere breaking down within about one week. Thus, FK-5-1-12 is not considered persistent in the environment.
Clean extinguishing agents like FK-5-1-12 have been extensively evaluated for their suitability in the intended applications and their safety in the intended uses. Important information regarding responsible use of clean extinguishing agents can be found at:
US Government:
Strategic Environmental Research and Development Program (SERDP) Environmental Security Technology Certification Program (ESTCP) Phone 4800 Mark Center Drive, Suite 16F16, Alexandria, VA 22350-3605 https://www.serdp-estcp.org/Featured-Initiatives/Per-and-Polyfluoroalkyl-SubstancesPFASs
Industry Fire Fighting Foam Coalition
The environmental voice for users and manufacturers of AFFF
1001 19th Street, Suite 1200
Arlington, VA 22209
comcast.net
Phone I
Fax
https://www.fffc.org/
3
Atmospheric Chemistry of FK-5-1-12
A study conducted by MITii examined the atmospheric loss mechanisms for C2F5C(O)CF(CF3)2 commercially known at the time as 3MTM NovecTM 1230 Fire Protection Fluid commonly referred to as FK-5-1-12. The authors of this study determined that this compound does not react with hydroxyl radical (OH), but that substantial decay occurs when exposed to UV radiation. The authors measured the UV cross-section for FK-5-1-12 finding a maximum wavelength of absorbance at 306 nm. Since this compound shows significant absorbance at wavelengths above 300 nm, photolysis in the lower atmosphere will be a significant sink for this compound. The authors conclude that "In fact, the absorption spectrum is similar to that of acetaldehydeiii, a species whose lifetime against solar photolysis is about 5 daysiv.
The absorption cross sections of L-15566 (the experimental product designation at the time for FK-5-1-12) are somewhat larger; hence, we expect the atmospheric lifetime of L-15566 against solar radiation to be of the order of 3 to 5 days".
Subsequent 3M laboratory measurements of the photodissociation rate of FK-5-1-12 found it to be equivalent to that of acetaldehyde, within experimental errorv. Hence, an atmospheric lifetime of 5 days is appropriate for FK-5-1-12. The potential for FK-5-1-12 to impact the radiative balance in the atmosphere (i.e., climate change) is limited by its very short atmospheric lifetime and low global warming potential (GWP). The quantitative IR cross-section of FK-5-1-12 was measured in accordance with section 4.6 of the US EPA FTIR Protocolvi. The IR measurements were made with a 0.5 cm-1 spectral resolution at 293K on a MIDAC (Model I2001) FTIR spectrometer which employs a mercury-cadmium-telluride infrared detector maintained at 77 K. The experimental setup used a nominal 4 m pathlength which was calibrated using certified ethylene gas standards.
Using the measured IR cross-section and the method of Pinnock et alvii the instantaneous radiative forcing for FK-5-1-12 is calculated to be 0.50 Wm-2 ppbv-1. This radiative forcing value and a 5-day atmospheric lifetime results in a GWP value of 1 using the WMO 1998 methodviii and a 100-year integration time horizon. Clearly, compounds with such short atmospheric lifetimes are of no concern with respect to potential climate change.
FK-5-1-12 is expected to rapidly degrade in the atmosphere to fluorinated alkyl radicals (CF3CF2, CF3CFCF3) similar to those produced by other fluorochemicals. Studies of the atmospheric chemistry of these radicals and their degradation products have concluded that they have no impact on stratospheric ozoneix. This, combined with its very short atmospheric lifetime, leads to the conclusion that FK-5-1-12, like other fluorinated compounds, has an ozone depletion potential of zero. The degradation products resulting from the atmospheric decomposition of FK-5-1-12 (CO2, HF, CF3COOH) are similar to those produced by other fluorochemicals and are not expected to pose any significant environmental hazard.
4
See Table 2 below of environmental properties of FK-5-1-12 compared with other gaseous clean agents in use:
Properties
FK-5-1-12 Halon 1211 Halon 1301 HFC-125 HFC-227ea
Ozone Depletion
0.0
4.0
12.0
0.0
0.0
Potential (ODP)1
Global Warming
0.114
Potential (CO2 = 1) IPCC2
Atmospheric Lifetime 0.019
(years) IPCC2
1930 16
7200 72
3740 30
3600 36
US EPA SNAP listed
Yes
N/A
N/A
Yes
Yes
1 World Meteorological Organization 1998, Model Derived
2 Intergovernmental Panel or Climate Change (IPCC) 2021, 6AR Method, 100 Year integrated time horizon
Table 2: Environmental Properties Comparison of Clean Extinguishing Agents
Toxicity Assessment FK-5-1-12 has been independently tested for required toxicological endpoints at Huntington Research (UK and USA) and NOTOX (NL). The results included in Table 3 are:
Properties
FK-5-1-12
4-hour Acute Inhalation
Practically Non-Toxic (LC50 >10,000 ppm)
Cardiac Sensitization
Not a Sensitizer (NOAEL = 100,000ppm)
Acute Dermal Toxicity
Low Toxicity (LD50 > 2000 mg/kg
Ames Assay
Negative
Primary Skin Irritation
Non-Irritating
Primary Eye Irritation
Minimally Irritating
Acute Oral Toxicity
Low Toxicity (LD50 > 2000 mg/kg
Skin Sensitization
Not a Skin Sensitizer
Chromosomal Aberration
Negative
Table 3: Toxicity Test Results of FK-5-1-12
The no observable adverse effect level (NOAEL) of FK-5-1-12 for any end point of acute toxicity has been determined to be 10 volume percent (100,000ppmv) in air. With a NOAEL of 10%, there is consensus that FK-5-1-12 is safe for its intended end use and provides a large margin of safety relative to the typical design concentrations of fire protection systems. Typical design concentrations in the range of 4.5 to 6.0 volume percent result in safety margins of 67% to 122%, giving FK-5-1-12 the widest margin of safety amongst commercially viable clean extinguishing agents. See Table 4.
5
Agent Use Concentration(1) NOAEL(2) Safety Margin(4)
FK-5-1-12 4.5-6% 10%(3) 67-122%
Halon 1301 5% 5% Nil
HFC-125 8.7-12.1% 7.5% Nil
HFC-227ea 6.7-8.7% 9% 3-34%
1Adjusted per 2012 NFPA 2001 requirement for minimum values (excluding halon) paragraph 5.4.2.4 and Table A.5.4.2.2(b) 2 NOAEL for cardiac sensitization 3 NOAEL for acute toxicity, including cardiac sensitization 4 Safety Margin = (NOAEL - Use Concentration)/Use Concentration
Table 4: Safety Margin Comparison of Halogenated Clean Extinguishing Agents
Products of Thermal Decomposition
The following background discussion and references can be found in a WPI thesis paper by Ditchx, with a focus on FK-5-1-12, referred to in the Thesis as the experimental product designation L-15566. References also include voluminous data on other clean extinguishing agents.
Human safety can arguably be the most important consideration when dealing with any fire extinguishing agent, with two toxicological aspects to consider for clean extinguishing agents: a toxicity assessment of the agent itself and that of the thermal decomposition products (TDP) generated when a halocarbon clean agent is discharged under fire conditionsxi.
The TDPs are those compounds produced due to an agent's exposure to a fire. The TDPs of halocarbon clean agents like FK-5-1-12 have been extensively investigated. When halocarbons thermally decompose upon exposure to a fire. the TDPs of most concern are hydrogen halides (HX) and carbonyl halides (COX2)xii.
Concerns over the effects of exposure to acid gases have led to several studies on the effects of the concentrations of these exposure levelsxiii xiv xv xvi. Studies have shown that acid-gas production by in-kind halocarbons in total flooding applications is between two and 10 times greater than that of halon 1301. It has also been shown that the three key factors resulting in thermal decomposition production are the fire size-to-volume ratio, the agent volumetric concentration, and the discharge time.xvii
To illustrate, a composite of Peatross and Ditch work is shown in the following graphic excerpted from the thesis (Figure 3). It shows plotted HF produced as a function of a normalized fire size/room volume ratio. Peatross examined fires ranging from 0.1 kw to greater than 8.0 MW size fires conducted at and numerous laboratories, including, for example, the NRL, USAF, USCG, Hughes Associates, NMERI, agent, and OEM equipment manufacturers.
6
28-Day Inhalation Study NOAEL of this study: 4,000 ppm
Figure 3: Comparison of TDP for halon alternatives (Peatross et alxvii plus Ditchxv data for L-15566. were L-15566 = FK-5-1-12) The key takeaway here is to understand the thermal decomposition reality, that the fire size to room volume ratio is important. One must design to keep the fire small relative to room volume. The smaller fire size to room volume ratios results in a lower less chance to develop high thermal decomposition concentrations. Figures 4 and 5 excerpted from Ditch show the resultant TDP when the fire size/room volume is LARGE and when it is SMALL.
7
Figure 4: Data from Master's Thesis - Ditch, BD, WPI, 2002
TDP extrapolated to "Hangar" sized rooms-SMALL kWfire/m3room
Figure 5: Data from Master's Thesis - Ditch, BD, WPI, 2002 Ditch and other researchers referenced in the thesis also confirmed that increases in agent concentration and shortening the extinguishing time dramatically reduces TDP, in some tests by 50% or more. Bottom line, a properly designed system using clean extinguishing agents, like FK-5-112, with advanced detection technology currently in industry use, can minimize TDP by
8
detecting and extinguishing a fire rapidly in a protected space before it gets large, keeping the fire size/room volume ratio small.
Conclusion and Final Assessment
A risk assessment involving all the stakeholders provides confidence that to the best of their ability, the design team has considered and determined this to be the best approach operationally, regulatorily, environmentally, and with consideration of life safety.
Clean extinguishing agents are generally safe in end use protecting both people and assets when properly designed and engineered in advanced fire suppression systems. Designed for fast detection and extinguishment, the clean extinguishing agent systems can readily be engineered to minimize thermal decomposition to very low levels.
The FSSA is concerned that a "total ban" approach to PFAS compounds could impact society's ability to protect mission-critical applications that keep people safe without a more comprehensive safety risk cost analysis. The FSSA strongly urges ECHA to use methodical, data-driven methods with respect to PFAS rulemaking for clean agents in critical fire and life safety applications. Any regulation restricting the manufacture, import, distribution, sale, or use of PFAS should exclude Clean Agents when used in fire and explosion protection applications.
References
i Federal Register/Vol. 67, No. 245/Friday, December 20, 2002/Rules and Regulations 77931-77932 ii Guschin, A.G., Molina, L.T., and Molina, M.J., Atmospheric Chemistry of L15381, L15566 and L14703 and Integrated Band Strengths of L14374, L14375, L14752, L13453 and L 14703, Report prepared for 3M Company, July, 1999. iii FinlaysonPitts, B.J. and Pitts Jr., J.N., Atmospheric Chemistry: Fundamentals and Experimental Techniques; John Wiley & Sons, New York, 196, 1986. iv Seinfeld, J.H. and Prandis, S.N., Atmospheric Chemistry and Physics, John Wiley & Sons, New York, 288, 1998. v Plummer, G., "Laboratory measurements and calculations related to the photodisassociation of L15566 in the Earth's lower atmosphere," 3M Environmental Laboratory Report Number E010549, 2001. vi Addendum to Method 320 - Protocol for the Use of Extractive Fourier Transform Infrared (FTIR) Spectrometry for the Analyses of Gaseous Emissions from Stationary Sources (40 CFR Part 63). vii Pinnock, S., Hurley, M.D., Shine, K.P., Wallington, T.J., Smyth, T.J., J. Geophys. Res., 100, 23227, 1995. viii WMO (World Meteorological Organization), Scientific Assessment of Ozone Depletion: 1998, Global Ozone Research and Monitoring Project - Report No. 44, World Meteorological Organization, Geneva, Switzerland, 1999. ix Wallington, T.J., Schneider, W.F., Worsnop, D.R., Nielsen, O.J., Sehested, J., Debruyn, W.J., Shorter, J.A., Environ. Sci. Technol., 28, 320, 1994. x Ditch, BD, WPI Thesis, Thermal Decomposition Products Testing With 1,1,1,2,2,4,5,5,5 nonafluoro4 trifluoromethyl pentan3one (C6 Fketone) During Fire Extinguishing, December, 2002. xi J.Z. Su, A.K. Kim, J.R. Mawhinney, "Review of Total Flooding Gaseous Agents as Halon 1301 substitutes," Journal of Fire Protection Engineering, 8 (2), pp 4564, 1996
9
xii P.J. DiNenno, E.W. Forssell, M.J. Peatross, M. Maynard, "Evaluation of Alternative Agents for Halon 1301 in Total Flooding Suppression Systems - Thermal Decomposition Product Testing," Halon Options Technical Working Conference, Albuquerque, NM, 1993 xiii M. Meldrum, "Toxicology of Substances in Relation to Major Hazards: Hydrogen Fluoride," Health and Safety Executive, ISBN 11 882100 8, 1993 xiv A.H. Mann, "Possible Health Risks From Exposure to Hydrogen Fluoride Generated From the Use of Fluoride Containing Fire Extinguishing Agents," Robens Institute of Industrial and Environmental Health & Safety, University of Surrey, Guildford, Surrey, United Kingdom, 1996 xv D.P. Kelly, "A Review of the Inhalation Toxicity of Hydrogen Fluoride," Halon Options Technical Working Conference, Albuquerque, NM, 1998 xvi W.J. Brock, "Hydrogen Fluoride: How Toxic is Toxic? (A Hazard and Risk Analysis)," Halon Options Technical Working Conference, Albuquerque, NM, 1999 xvii M.J. Peatross, "A Review of Thermal Decomposition Product Testing of Halocarbon Fire Suppression Agents," Halon Options Technical Working Conference, Albuquerque, NM, 1998
10