orating solvent and is independent of the volume of the oven From the following table Lower explosive limit for n-heptane = 12 percent Vapor volume = 22 cu ft/gal Exhaust rate _ 22 X 100 required to dilute -- 12 vapors to the lower explosive limit = 1833 cu ft/hr = 30 6 cfm This rate is normally multiplied by a safety factor of about 5 to allow for imperfect mix ing Therefore 30 6 X 5 = 153 cfm exhaust rate For more precise calculations, see NFPA Standard No 86A, Ovens and Fur naces Explanation of Table Headings Column headings of the table (pages 12121231) are explamed as follows Listing of substances The "chemical hazards" table lists those physical properties associated with the fire and health hazards of common industrial chemicals (For tables of threshold limit val ues and maximal acceptable concentrations, see Chapter 38, "Industrial Toxicology ") Data in the table have been taken from the following principal references Standard 49, Hazardous Chemicals Data, and Standard 325M, Flammable Liquids, Cases, and Vola tile Solids, both published by the National Fire Protection Association, 470 Atlantic Ave , Boston, Mass 02210, and Handbook of Or ganic Industrial Solvents, published by the Amencan Mutual Insurance Alliance, 20 N Wacker Dr, Chicago, 111 60606 Be sure to check latest editions of these standards and booklets Other information is contained in Chapter 46, "Safety Engineering Tables," Table 46-0, "Explosion Characteristics of Various Dusts " Check the Cross Index for names of chemi cals and compounds that may be listed under another name (See pages 1208-1211 ) Column 1 Flash point is the lowest temperature at which the liquid gives off vapor within a test vessel in sufficient concentration to form an igmtable mixture with air near the surface of the liquid The flash point is used by OSHA and NFPA to define and classify the fire haz ard of liquids (see Chapter 42, "Flammable and Combustible Liquids") A standard closed container is used to de termine the closed-cup flash point of a liquid and a standard open-surface dish is used for the open-cup flash point determination, as specified by the standards of the Amencan Society for Testing and Matenals (ASTM) Unless otherwise specified, the flash point values in the table are dosed-cup determina tions Column 2 Flammable or explosive limits are those concentrations of a vapor or gas m air below or above which propagation of a flame does not occur on contact with a source of igni tion The lower limit is the minimum vapor concentration below which the vapor-air mix ture is too "lean" to bum or explode The upper limit is the maximum vapor concentra tion above which the vapor-air mixture is too "rich" to bum or explode Flammable or explosive limits are given in the Table in terms of percentage by vol ume of gas or vapor m air, and, unless other wise noted, at normal atmospheric pressures and temperatures Increasing the tempera ture or piessure lowers the lower limit and raises the upper limit Decreasing the tem perature or pressure has the opposite effect Column 3 Vapor volume is the number of cubic feet of solvent vapor formed by the evaporation of one gallon of a liquid at 75 F Column 4 Severtty and type of hazard Each haz ardous substance presents a distinct problem and must be treated individually m the light of its own characteristics Conclusions regard ing the hazards of a product cannot safely be drawn either from the properties of the ma tenals from which it is formed or by analo gies based upon chemical structure Mixtures of two or more chemicals may have properties that vary in kind or degree from those of the individual components Impunties may con- 1201