June 1, 1971 AROCLOR 1016 SPECIFICATIONS
J. R. Savage
W. R . Richard R . McCutchan - WGK W. B . Papageorge D . R . Cova O . DeGarmo P. G. Benignus J . Fallon R . Kuster R. A. Baxter/H. A. Vodden
Ruabon A. F. Reagan - Newport F . MacDonald - Newport P. J . A. Marsh - Brussels J . Durland - Tokyo D . Danna
It has been suggested that specifications be set for Aroclor 1016 to be produced by Monsanto as a replacement for Aroclor 1242.
The guiding principles to be used in setting the specifications for Aroclor
1016 are as follows: The electrical specifications, specifications for
appearance, color, acidity, water content, inorganic chlorides, sulfates,
and stability will be the same as those for Aroclor 1242. Specifications
for properties such as pour point, viscosity,specific gravity, refractive
index, distillation range and fixed chlorine content will be changed to
compensate for the higher homologs removed.
,,
One new specification must be added. That is penta and hexachlor obiphenyl content. This is essential because our reason for producing Aroclor 1016 is to produce a product with a minimum content of higher homologs which are more persistent in the environment.
The ratio of penta and hexa content in Aroclor 1242 to that of Aroclor 1016 is our one readily quantifiable measure of the improvement achieved by going to Aroclor 1016. The penta and hexa content of Aroclor 1242 ranges from 6 to 7.2%. That for Aroclor 1016 produced so far has been less than 0.3%. On this basis, Aroclor 1016 can be said to be about 20 times better than Aroclor 1242.
The suggested specification for penta and hexa homologs is 0.4% max. to have some margin for analytical error and less efficient operation in the plant than in the pilot plant.
IN- IO REV. 11-ftS
DSW 552856 STLCOPCB4091273
2- -
One other change is suggested. Current specifications call for a dielectric constant of 4. 7 to 4. 9 measured at 1000 Hz and 100C and power factor of 5.0% measured at 60 Hz and 100C. It is suggested that the dielectric constant be determined at 60 Hz and 100C so that measurements will not have to be made at two frequencies. The dielectric constant does not change with frequency in this range so the specification range will not change. The 1000 Hz power factor is often too low to measure accurately and should therefore be omitted as a specification. The attached table compares the proposed specifications for Aroclor 1016 with the current specifications for Aroclor 1242. These specifications for Aroclor 1016 are proposed to serve as a starting point for develop ment of final specifications acceptable to all interested groups in Monsanto and to our customers. Your comments are invited.
R. H. Munch js
DSW 552857
STLCOPCB4091274
A COMPARISON OF PROPOSED SPECIFICATIONS FOR AROCLOR 1016 WITH CURRENT SPECIFICATIONS FOR AROCLOR 1242
Unr estricted Information
Aroclor 1242
Aroclor 1016
(R) Color (APHA)
.
(R) Condition
(R) Sp. Gr. @ 25/15. 5C
(R) Acidity (mg. KOH/g.)
(R) Moisture
(R) Refractive Index @ 25C
(R) Inorganic (Free) Chlorides
(R) Pour Point
(R) Dielectric Constant
(1000 Hz @ 100C)
(R) R e sistivity (500 VDC @ 100C. 0. 1" Gap.)
(R) Hydrolosi s Stability Test (As Chlorides)
(R) Monsanto Stability Test (As Chlorides)
(R) Distillation Range (ASTM D-20 corrected)
10% Distilled by Wt.
90% Distilled by Wt.
(R) Penta and Hexachloro Biphenyls*
Sulfates
Dielectric Strength
@ 25C KV
Flash Point F
Fire Point
Corrosion Test (6 hrs @ 210C
with brightAl foil)
Change in wt. of A1 %
A. C. Color (APHA)
A.C. Condition
A.C. Acidity (mg. KOH/G)
A.C. Inorganic (Free) Chlorides
Vise. @ 100F (SUS)
40, max.
Clear
*
1.381-1. 392
0.010 max.
35 ppm, max.
1.6240-1.6260
0.05 ppm, max.
-14C or lower
4.70-4.90
.
500, min.
40, max. Clear . 1.362-1.372 0.010 max. 35 ppm, max. 1.6215-1.6235 0.05 ppm, max. -14C or lower 4.70-4.90 60 hz @ 100C
500, min.
0. 5 ppm, max.
0. 5 ppm, max.
0, 4 ppm, max.
0.4 ppm, max.
325C min.
^
360C max. .
^ - 6-7%**
-' None
"" '
' 35 min. 338-392 None to B.P.
0.0 60, max. Clear 0.010, max: 0.05 ppm, max. 82-92
323C min. 356C max.
0. 4% max. None
35 min. 338 min. None to B. P.
0. 0 60, max. Clear 0. 010, max. 0. 05 ppm, max. 71-81
Ta. By Physical Chemistry Method 71- 11, Job No. 1348522. Disc integrator is standard. Electronic integrator s may be used after proper standardization against a disc integrator.
** Range of typical values, not a specification for Aroclor 1242.
...... OS***868
STLCOPCB4091275
General Information
Specific Heat @ 25C Coefficient of Expansion
(25-65C) CC/CCC Fixed Chlorine P.ower Factor @ 100C Typical Values 60 Hz
1000 hz
Special Customer Requirements
General Electric
Thermal Chemical Chlorides
Westinghouse
Hydrolizable Chlorine
'
(Westinghouse Stability Test)
Aroclor 1242
0.30 0.00068
43 t . 5%
5 0.30
Aroclor 1016
0. 30 0. 00068.
41.3 .5%
5
0.65 ppm, max
0. 65 ppm, max.
1.0 ppm, max.
1.0 ppm, max.
(R) Routine Analysis; all others by request only.