CHAPTER 42
1946 Guide
as well as Equation 6, show that the attenuation in decibels is directly proportional to the length of duct lined, and that the larger the duct the greater will be the length which must be lined in order to obtain a given noise reduction.
If the length of duct from the main duct to a grille is shorter than the length of lining indicated by the calculations, this duct may be sub divided into smaller ducts, as shown in Fig. 4. The increase in noise reduction thus obtained may be calculated from Equation 7, provided the^splitters are installed parallel to the long side of the duct:
Rs = R
where Re = reduction with splitters, decibels. Ro = reduction in same length of duct, without splitters, decibels. a = -dimension of short side of duct, inches or feet. b = dimension of long side of duct, inches or feet. = number of channels formed by splitters.
(7)
Sound Control
773
Solution: Case T. (No splitters), From Equation 6,
60
Ro = 12.6 x 12 X ~ X 0.401-* = 12.6 db
CaseS. (Two splitters, three channels), From Equation 7,
Rs = 12.6 X
10 + (20 X'3) 10 +20
= 29.6 db
AIR SUPPLY OPENING NOISES
When air is introduced into a room through a grille or register at a constant velocity, sound energy is being introduced into the enclosure at a constant rate12. Due to partial reflection at the boundaries of the en closure, the intensity of sound at any point in the space builds up to some maximum value. In a large room at a point remote from the source of sound (the supply opening) the intensity can be shown to be,substantially proportional to the rate at which sound energy is generated and inversely proportional to the number of sound absorption units (sabines) in the
Fig. 4. Diagram of Branch Duct Treatment Where Length is Insufficient for Adequate Absorption
Example 1. An air conditioning installation is to be installed in a small theater. Determine the necessary sound treatment for the air distribution system to provide a satisfactory noise level in the theater utilizing these conditions:
Fan tip speed 4000 fpm, total pressure 1.25 in____________________ 77 db Acceptable room noise level (Table 1).......................... ................ :40 db
Required attenuation..______________:37 db
Solution: Natural attenuation of supply duct.
Sheet metal duct 50 ft long 48 in. x 36 in. (Table 2) 50 x 0.01:__6.5 db
Elbows, two size 48 in. x 36 in. (Table 3)-2 x 12.0 db Attenuation grilles to theater air change 10 min (Table 5) outlet
velocity 1000 fpm.__________ _______________________________ .22.0 db
Total natural attenuation___ !_______ _.24.5 db
Difference between required and natural attenuation, 37 minus 24.5, is 12.5 db. This
attenuation must be supplied by sound treatment in the duct, either in the form of duct
lining or plate cells.
'
A similar analysis of the return duct system shows that 15 db attenuation are to be furnished by absorptive material. An inspection of the installation shows that the lining of the plenum on the suction side of the fan would prove the most economical,
where.it would secure the dual function of heat insulation and sound absorption.
Example 2. A10 x 20 in. duct is connected to a private office space in a quiet location, Determine the length of lining necessary to attenuate average fan noise satisfactorily, using a lining material of a type to which Equation 6 applies, and having an absorption coefficient of 0.40 at 256 cycles. Assume that the duct is only 12 ft long as shown in Fig. 4, and that a 30 db reduction is required in this length.
room. It would thus appear that doubling the sound absorption of the room would- halve the intensity and result in a noise level decrease of 3 db.
Grille noise is similar in character to fan vortex noise. Knowing the noise level at the face of a grille for a given grille blade setting, the noise will vary as given-in-Equation 8 where' V is the velocity, of the'air through the grille.
db (change) = 55 login
)
(8)
For a change in blade setting Equation 9 applies arid in this case the total pressure is measured directly behind the face of the grille. For a typical air conditioning grille the noise level at the grille face may be approximately 48 db with a total pressure behind the grille of 0.1 in.
The resultarit room noise level can be approximated by Equation 10. ;
Room Level = TN`se Level at Face"] _ jq . Total Room Absorption in Sabines . ..
L of Grille J
10
Total Grille Area
*'