Document pDKVkwmynYk7XLj6ryo6Q6Xk
HEATINC VENTILATING AIR CONDITIONING CUIDE 1944
gular. Stokers in this class are made for burning anthracite, bituminous, semi-bituminous, and lignite coals, and coke. The U. S. Department of Commerce has issued commercial standards for household anthracite stokers1.
Units are available in either the hopper type, as shown in Fig. 1 or in the bin-feed type as shown in Figs. 2 and 3: Some stokers, particularly those designed for use with anthracite automatically remove ash from. the ash pit and deposit it in an ash receptacle as shown in Fig.-3. Most
Fig. 1. Underfeed Stoker; Hopper Type, Class 1
CHAPTER 10. AUTOMATIC FUEL BURNING EQUIPMENT
Class 2 and 3 Stokers
Stokers in this class are usually of the screw feed type without auxiliary plungers or other means of distributing the coal. They are used exten sively for heating plants in apartments and hotels, also, for industrial plants.
They are of the underfeed type and are available in both the hopper type, as illustrated in Fig. 5, and the bin feed type, shown in Fig. 6. These units also are built in plunger feed type with an electric motor or a; steam or hydraulic cylinder coal feed drive.
Stokers in this class are available for burning all types of anthracite, bituminous and lignite coals. The tuyere-and retort design varies ac
Fig. 2. Underfeed Stoker, Bin Feed Type, Class 1
of the bituminous models, however, require removal of the ash from the fuel bed after it is fused into a clinker:
Stokers in this class feed coal to the furnace intermittently in accor dance with temperature or pressure demands. A special control is used to insure sufficient stoker operation to maintain a fire during periods when no heat is required.
Stoker-Fired Boiler and Furnace Units
Boilers, air conditioners, and space heaters especially designed for stokers are available having design features closely coordinating the heat absorber and the stoker. Although effidentand satisfactory performance can be obtained from the application of stokers-to existing boilers and furnaces, some of the combination stoker-fired units. (Fig. 4) are more . compact and attractive in appearance.
' tDomraUc Burners for Pennsylvania Anthracite (Underfeed Type). (U. S. Detartmeni of Commerce
National Bureau of Standards, Commercial Standard No. CS48-40).
TM'
202 ,
cording to the fuel and load conditions. Stationary type grates are used on bituminous models and the clinkers formed from the ash accumulate on the grates surrounding the retort.
Anthracite stokers in this class are equipped with moving grates which discharge the ash into a pit below the grate. This ash pit may be located on one or both sides of the grate and on some installations is of sufficient capacity to hold the ash for several weeks' operation.
Class 4 Stokers
Stokers- in this group vary widely in details of design and several methods of feeding coal are employed. The underfeed stoker is widely used, although a number of the overfeed types are used in the larger sizes. Bin-feed, as well as hopper models, are available in both under feed and overfeed types.
Class 5 Stokers-
The prevalent stokers in this field are: (1) underfeed side cleaning, (2) underfeed rear cleaning, (3) overfeed flat grate, and (4) overfeed inclined grate.
Underfeed side cleaning stokers are made in sizes up to approximately 500/boiler horsepower. They are not so varied in design Us those in the
203