CHAPTER 14
1951 -Guide
should not be judged from the value of the CO% in the flue gas without reference to the ultimate COi obtainable. Practical values of C02 will usually be from 8 to 14 percent, depending on the gas used.
Ratings, for Gas Appliances
Input rating for a gas appliance is established by demonstrating that the appliance can meet the Approval Requirements of the ASA. The tests are conducted at the A.G.A. Laboratories. Output rating' is deter mined from the approved input and an average efficiency stated in the Approval Requirements, and is the heat available at the outlet:
Sizing Gas-Fired Heating Plants
Although gas-burning equipment' usually is completely automatic,
Table 1. Capacity op Gas Piping
Nominal Diameter of Pipe in Inches
Length of Pipe' -
in Feet
1
I
H
8
Capacity--Cu Ft Per Hr with a 0.6 Sp Gr Gas and Pressure Drop of 0.3 * Water Column
15 , 30
, 45 60 76 90 105
120 150 180
172 345 750
120 241 535 850 .
99 .199 435 700
86
173
380 ,
610
77 155 345 545
70
141 :.
310
490
65
131
285 . 450
920
120 270 420 860
109 242 380 780
100 225 350 720
maintaining the temperature of rooms-at a predetermined .figure, there are some manually controlled installations. In order. to. overcome effec tively the starting load and losses in piping, a manually^controlled gas boiler should' have an output as much as 100 percent greater- than the equivalent standard radiation which it is-.expectedito serve.
Boilers under thermostatic control-, however, are. not subject to such severe:pick-up loads and consequently, it is possible to use a' lower selec tion factor. For a gas-fired boiler or furnace under thermostatic control, a factor of 20 to 25 percent is usually sufficient for pick-iip:allowance.
In those installations, in mild climates where 100 percent outside air is used, furnaces should be of larger size in order to provide adequate capacity and quick pick-up under intermittent heating conditions.
The factor to be allowed for loss of heat from piping will vary somewhat, the proportionate amount of piping , installed being greater'for small installations than for large ones. For-selection factors to be added to installed radiation under thermostatic control, see ChapterT5.
. Appliances used for heating with gas should bear the' approval seal of the A.G.A. Laboratories on the manufacturer's nanieplate, together with the official input and output ratings. " It is^not permissible to operate a gas heating unit above its stated rating. It may .be necessary to operate, below this rating at elevations above 2000 ft, unless,the appliance has been tested and approved for operation at Altitudes'up to 5200 ft, in which case such approval will be shown on the manufacturer's nameplate.
Automatic Fuel Burning Equipment
,
363
Installations should be made in accordance with recommendations shown in the publications of the7 American Gas Association:.
Controls
.
r- -
Temperature controls for gas burners. are described in Chapter. 38. Some central heating plants are equipped with push-button or other manual control. The main gas valve may be of either the snap action or throttling type: . Automatic electric ignition is available.
Sizing of Gas Piping
Piping for gas appliances should be of adequate size, and so installed as to provide a supply of gas. sufficient to meet the maximum demand without
Table 2. Multipliers Fob Various Specific Gravities -. - For Use With Table I
Specific Gravity >
Multiplier
Spccifio Gravity .
Multiplier
.35
1.31 -
1.00
.40
1.23
-1.10
.45 . 1.16
1.20
.50
1.10
1.30
.55 . 1.04
1.40
.60
1.00
1.50
.65
.962
1.60
.70 .926 1.70
.75 . .895 1.80
.80
.867
1.90
.85 .841 2.00
.90
.817
2.10
.775 .740 .707 .680 .655 .633 .612 .594 .577 .565 .547 .535
. :
undue loss of pressure between the point of supply (the meter) and the burner. The size of gas-pipe^ required depends upon the following:
1. Maximum gas .consumption to be provided. 2. Length of pipe and number of fittings. 3. Allowable loss in pressure from the outlet of the meter to the burner. 4. Specific gravity of the gas.
To pbtain the cubic feet per hour of gas required by the burner, divide
the Btu input at which the burner will be adjusted, by the average Btu heat
ing value per cubic foot of the gas. '
;
Capacities of different sizes and lengths of pipe, in cubic feet per. hour, with a pressure drop of 0.3. in. of water 'column for a gas of 0:60 sp gr, are shown in Table 1. -In adopting a 0.3 in', pressure drop, due allowance for an ordinary-number of fittings, was made.
To convert the figures given in Table 1 to capacities for another gas of
different specific gravity, multiply the tabular values by the multipliers
shown in Table 2. - -
FUEL BURNING RATES
The burning rate for automatic fuel burning devices is determined by, the gross heat output required oftheboiler, or fumace, to carry the'net heating load, plus allowances * for system losses and{ pick-up. General