Document pBrqVEDz9m9bdYJeJG6geZ81j

BULLETIN NO. IC/FF-38 TRANSFORMER TOWOLDMON0036812 WATER_PCB-00021281 T8T SECTION A TRANSFORMER ASKARELS............................................1 I. Introduction............................................................. 1 II. History of Trade Name Types............................... 1 Table I -- The Composition of Transformer Askarels ............................................2 III. Interchangeability ................................................. 2 IV. Tabled --Official Transformer Adcarel Shipping Specifications..........................................3 V. Ordering Instructions ............................................ 2 VI. Stability.....................................................................2 VII. Precautions When Handling Drums, Tank Cars and When Opening Transformers..........................4 A. Keep Dry During Handling ............................ 4 Table Ml - Handling and Pumping Temperatures.................................... 4 B. Use Ordinary Personal Precautions .............. 4 C. Precautions on Opening an Askarel Transformer..........................................5 VIII. Avoid Environmental Pollution............................ 5 1. Labeling Askarel Transformers.......................6 2. Disposal of Liquid and Solid Wastes ............6 3. Conditioning of New or Recycled Askarel .6 4. Teardown of Transformers for Repair or Scrap ..........................................7 6. Transformer Disposal....................................... 7 IX. Expected Service Life............................................ 7 X. General Characteristics of Transformer Askarel Fluid.............................................................7 XI. Sampling Transformer Askarel Fluid ................. 8 XII. Evaluation of Adcarel Received in New Equipment..................................................8 XIII. Dielectric Breakdown Voltage Moisture Relationship............................................ 9 Table IV -- Relation of Dielectric Breakdown Voltage to Amount of Dissolved Water in Askarel and Mineral Oil..........................................9 Table V - Approximate Solubility of Water in Transformer Askarel and Mineral Oil .... 10 XIV. TuibkJity ................................................................ 10 XV. Check Points for Maintaining Atkaral Insulation ................................................10 A. General Considerations.................................. 10 B. Modern Sealing Procedures .......................... 11 C. The Older Sealing Arrangements.................. 12 -XVI. Periodic Fluid Inspection and ' , Whet Checkpoints Mean ......................................12 A. Visual Inspection..................... ....................^3 B. Dielectric Breakdown Voltage ............. '^3 XVII. Inspection Checklist........................................'^3 XVI11. Contamination in Transformers.....................* 14 Table VI - Effect of Common Insulation Materials on Power Factor and Dielectric Strength............................................ .. Table VII - Effect of Common Insulation Materials on Volume Resistivity of Askarel..............................................................14 XIX. ASTM Method for Investigating the Compatibility of Transformer Insulation arxKtonstruction Materials in Askarals............15 XX. Refining Askarel for Re*Use..............................15 A. Filtering Through Dry Blotter Paper to Remove Moisture and Extraneous Particles..................................... 16 Table VIII -- Water Removal by Filtering Askarel Through a Paper Press ....................... 16 B. Disposal of Solid Wastes .............................16 C. Solid Insulation Requiring Drying............. 16 D. Earth Treatment for Maximum Improvement of Power Factor and Volume Resistivity .....................................16 Table IX -- Effect of Power Factor and Volume Resistivity ....................... 17 XXL Cleaning Arced Transformers............................ 17 XXII. Sampling Askarel................................................. 17 SECTION B ASKAREL FILLED SWITCHES AND TERMINAL CHAMBERS .....................................19 I. Introduction......................................................... 19 II. Sources of Contamination .................................19^^ III. Sealing Switches and Terminal Chambers . . .20^^ IV. Askarel Used Under Mild Arcing Conditions .20 V. Maintenance for Askarel Filled Switches .... 20 VI. Askarel Under Excessive Temperature or Fault Conditions .......................................... 21 SECTION C ANALYTICAL SERVICES ON TRANSFORMER ASKAREL AVAILABLE FROM MONSANTO ................................22 Types of Analyses Available: ...........................................22 1) Routine Maintenance Check..................................... 22 2) Complete Analysis..................................................... 22 3) Analysis After Earth Refinement .......................... 22 Appendix A -- Askarel Stability and Composition of Arc Formed Gas...................................23 Appendix B -- Solubility of Gas in Transformer Askarels ..................................................... 23 Appendix C - Effect of Temperature on Dielectric Breakdown Voltage of Askarel .................. 23 Appendix D -- Comparison of the Approximate Viscosity in Saybolt Universal Seconds of Transformer Askarels and Mineral Oil...........................24 Appendix E -- The Density of Inerteen 54201 KA 7336-9 and Transformer Pyranol A13B3B-3........................................................... 24 Appendix F -- Thermal Conductivity Values of Transformer Pyrarol A13B3B-3................................ 24 Appendix G -- Heat Capacity...........................................24 Appendix H -- Coefficient of Expansion........................ 24 Appendix I -- Fire Resistance........................................... 24^^ Appendix J -- Seals, Properties and Procurement ............................................................. ^5 Appendix K - Caution Label . . . ...................................25 TOWOLDMON0036813 WATER PCB-00021282 Transformer Askarel I. Introduction THe term "askarel" as defined by IEEE, ASTM and the National Electrical Code generally describes a broad class of non-flammable synthetic chlorinated hydrocarbon insulating liquids widely used in transformers, reactors and accessory equipment operated at power frequencies, Askarels of various compositional types are in use, (For the general properties and types see ASTM D-2283.) Under arcing conditions the gases produced, while consisting of predominantly non-combustible hydrogen chloride, can contain varying amounts of combustible gases dependi ng upon the askarel type. This manual describes the operating characteristics of transformer askarel liquid insulation and how it differs from mineral oil. Appropriate handling and disposal procedures for both scrap askarel liquid and impregnated solid materials are given in accordance with the guidelines recommended by the American National Standards Institute. The information is based on facts gathered by Monsanto over 40 years as a producer of askarel, plus knowledge gained from the experience of transformer manufacturers and users. This guide outlines the very simple maintenance required for askarel fluid in ''modern" transformers and offers suggestions for sealing and maintaining askarel in old units. By following this guide, we believe users will obtain maximum service from askarel insulation with a reasonable minimum of maintenance. If questions arise relating to the designing and building of transformers, these should be referred to regular transformer suppliers. Monsanto gratefully acknowledges the assistance, guidance and the contributions of certain data by the following, Edward L. Raab -- General Electric Df. T. K. Sloat - Westinghouse Electric II. History of Trade Name Types "Askarel" is the generic name for the non-combustible liquid insulation and coolant first used by General Electric Company in 1932 for their Pyranol* brand name fire-resistant transformers. Westinghouse Electric Corporation uses their brand name, Inerteen,** Whatever the trademarked brand, the askarel contains chlorinated biphenyl - one of the best liquid insulations developed by science. This inert material is chemically stable, fire-resistant, heat stable, non-corrosive, and has high dielectric strength under the operating conditions encountered in transformers. In addition to manufacturing Aroclor6 (chlorinated biphenyl), Monsanto also mixes this dielectric fluid with chlorobenzenes to produce the presently used Inerteen and Pyranol blends described in Table l. Trademark of General Electric Company Trademark of Westinghouse Electric Corporation ^Registered trademark of Monsanto Company 0565121 TOWOLDMON0036814 WATER_PCB-00021283 Table I The Composition of Transformer Askarel* Method ASTM D2283 Type D Type E Type G* /<* inerteen 70-30 Inerteen 10042 Pyranol A13B353 Ingredients {% by wt.) Aroclor 1254, pentachlorobiphenyl 70 Aroclor 1242, trichlorobi phenyl trichlorobenzene tri-tetrachlorobenzene 30 - phenoxypropene oxide scavenger 0.18 to 0.22 diepoxide scavenger 'Method ASTM D-2283 pending - 100 - - 60 .40 0.18 to 0.22 0.115 to 0.135 ASTM Method D-2283, titled "Chlorinated Aromatic Hydrocarbons (Askaretsj For Transformers", also lists the composition of all transformer askarels used at various times since 1932. Monsanto manufactures similar transformer askarel fluids in England where the trade name Pyroclor is used, III. Interchangeability In general all transformer askarels are interchangeable. However, it is suggested that the transformer manufacturer be consulted prior to mixing in significant proportions or total substitution. IV. Official Transformer Askarel Shipping Specifications The officii1! shipping specifications for the three modern transformer askarel fluids are shown in Table II. V. Ordering Instructions Monsanto's current policy is to sell askarel transformer fluids only to transformer manufacturers. Others interested in these fluids should contact the manufacturers of askarel transformers and not Monsanto. The transformer name plate indicates the transformer maker and usually gives sufficient data to identify the specific askarel fluid used. VI. Stability Askarel liquid insulation is highiy pure, fire-resistant liquid made under close chemical control to meet the exacting specifications as shown in Table II. It does not vary in composition like the commercial range of mineral oils. Askarel insulation must never be mixed with mineral oil. Over two percent of mineral oil by volume in askarel begins to lower its fire resistance. Askarel does not deteriorate when exposed to air, heat, hot metal; it does not break down over long use to form conducting or corrosive chemicals; it does not oxidize or sludge. Askarel will remain perfectly stable year after year unless broken down by severe electrical discharge. In modern transformers, the only real "enemy" of askarel is contamination by water. Keeping askarel water-free will insure long-time service. ^ .< Askarel is heavier TOWOLDMON0036815 WATER PCB-00021284 Table 11 Official Transformer Askarel Shipping Specifications Specification Properties Color, APHA Condition Water content, ppm (ASTM D1533-60) Acidity, mg KOH/g (ASTM D974-55) Dielectric Strength, 25C, 0.1 in. gap (ASTM D877-49) Dielectric Constant, 100C, 60 Hz (ASTM D924-49) Volume Resistivity, 100C, 500 volts DC 0.1 inch gap, 109 ohm-cm (ASTM D1169) Inorganic chlorides, ppm (ASTM D1821 and G.E. Method E4C41B) Refractive index, 25C (ASTM D1807) Viscosity at 37.8C (ASTM D88-56) Saybolt Universal Seconds Pour Point C (ASTM D-97-57) Specific gravity 25/15.5*C (ASTM D1810} Burn point (ASTM D92) Distillation range (ASTM D20-56) corrected for stem and barometric pressure General Electric Co. T ransformer Pyranol A13B3B 3 ASTM D2283 Type G* 150 max. Clear 30 max. 0.014 max. 35 KV, min. 4.2 to 4.6 1.6110 to 1.6120 44 to 48 -38 or lower 1.495 to 1.510 None to boiling 1st drop 20CTC min. 40% max. below 270C 90% 379 to 394 Westinghouse Transformer Inerteen 70-30 ** ASTM D2283 Type P 150 max. Clear 30 max. 0.014 max. 35 KV, min. 4.2 to 4.5 100 0.10 max. 1.6153 to 1.6173. 56 to 61 -30 or lower 1.518 to 1.528 None to boiling 1st drop 200C min. 35% below 270C 90% 379 to 394 Westinghouse Transformer Inerteen 100-42** ASTM P2283 Type E 60 max. Clear 35 max. 0.01 max. 35 KV, min. 4.7 to 4.9 0.05 max. 1.6240 to 1.6260 82 to 92 17 or lower 1.381 to 1.392 None to boiling 10% 325C min. 90% 360 max. Fixed chlorine Corrosion test Color, APHA Acidity, mg KOH/g Inorganic chlorides ppm Condition Scavenger content Typical Properties Coefficient of Thermal Expansion (ASTM D1903), cm2/cm2/C Arc formed gases Method ASTM D2283 pending for Type G. 56.4+0.5% 55.6% min. 43 + 0.5% After heating with aluminum for 6 hrs. at 200 to 220C, the aluminum must not be corroded on either visual or weight inspection and the askarel should meet $he following specifications: 200 max. 0.014 max. 0.15 max. Clear 0.115 to 0.135% Diepoxide 200 max. 0.014 max. 2.0 max. Clear 0.18 to 0.22% phenoxypropene oxide 200 max. 0.01 max. 0.15 max. Clear 0.18 to 0.22% phenoxypropene oxide 0.0007 0.0007 0.00068 Askareis of various compositional types are used. Under arcing conditions the gases produced, while consisting predominantly of non-combustible hydrogen chloride, can include varying amounts of combustible gases depending upon the askarel type. Insulation systems incorporating these askarels and cellulosic or other organic materials may, when arced, produce gaseous mixtures which are moderately flammable. As a precaution, such gases should be removed from the askarel by bubbling dry nitrogen through the askarel and flushing the gas space with dry nitrogen before any work is performed on the apparatus. e number Inerteen 54201KA for Inerteen 70-30 and their private number Inerteen 54201CM for Inerteen 100-42. TOWOLDMON0036816 WATER_PCB-00021285 $ tiny amount (approximately 125 ppm) dissolves -- the rest floats on top. Askarel is very insoluble in water, only about 200 parts per billion of askarel dissolve in water, at normal temperatures. VII. Precautions When Handling Drums, Tank Cars, and When Opening Transformers The Ameiicar. Institute of Electrical and Electronic Engineers Guide No. 76, December, 1958 has been revised to give more detailed instructions and guidance "For Acceptance and Maintenance of Transformer Askarei in Equipment". This guide is published by the Institute of Electrical & Electronics Engineers, Inc., 345 East 47th Street, New York, New York 10017. The following are significant precautions: A. Keep Dry During Handling: In handling, storing, sampling and inspecting askarel -- and in operating askarel transformer - take every precaution to guard the askarel insulation from exposure to high humidity and moisture contamination. Keep 5 or 55 gallon drums of askarel dry; lay stored drums on their sides with the bung at the highest point from floor to keep water off the drum head (which can be sucked into the askarel by the drum "breathing"). This precaution is not necessary when drums are stored indoors, which is the preferred place for storage. To avoid leakage the drums used tor askarel are of heavy construction. Sixteen gauge metal is used, with special rim seal and bung construction. The drums should be drained as completely as possible and then flushed twice with kerosene type solvent to remove all of the askarel. Accumulated liquids and washings should be collected and should be incinerated at high temperatures, e.g., about 2000T, to destroy the polychlorinated biphenyls (PCBs) See Section A, VIII. Tank cars used to transport askareU are in exclusive service and not used interchangeably for other i-;oducts. All cars must be unloaded through the top (dome fitting) either by pumping or with controlled pressure using dry air or dry nitrogen. If nitrogen has (seen used for unloading it is necessary to advise the shipper so thin v. . . itsc car returns the nitrogen can be replaced with dry air brloi. . v one may enter the car. If the car is to be unloaded by pun11.: ii vv II be necessary to use a dryer on the air intake line to reriiuv-. moisture. All tiinl. cats are fitted with steam coils, which are available foi unloading under extreme low temperature conditions. Convenient handling and pumping temperatures and the related approximate viscosity ranges are given in Table III. Use Ordinary Personal Precautions: Transformer askarel has been made, handled, and used for over 40 years. Ii can be handled safely with recommended precautions. If accidentally spilled on hands, no serious skin irritation will occur. However, liquid askarel has a solvent action (similar to paint Product Table III Handling and Pumping Temperatures Unloading, Handling and Pumping Temperature C Pyranol A13B3B-3 Incrteen 70-30 Inerteen 100-42 20-55 20-55 35 - 75 4 TOWOLDMON0036817 WATER_PCB-00021286 thinner) on the fats and oils of the skin and prolonged contact may lead to drying and chapping of the skin. In case of contact, wash the skin with soap and water; remove and dry clean saturated clothing. Clean up spills with rags, sawdust and absorbent clay. Eye contact may result in painful irritation but no permanent damage to tissues. If askarel gets in the eyes, flush with large amounts of water. As with all eye first aid, refer to a physician. To relieve irritation, physicians have used an opthalmic anesthetic solution as well as opthalmic cortisone acetate solution, or castor oil. Infrequent exposure to askarel vapors will not cause ill effects. However, prolonged-exposure to high vapor concentrations should be avoided. If hot askarel must be handled in a closed or confined area, provide the area with mechanical exhaust ventilation - or wear an organic cartridge respirator approved by the U.S. Bureau of Mines. C. Precautions On Opening an Askarel Transformer: Askarels of various compositional types are used. Under arcing conditions the gases produced, while consisting of predominantly non-combustible hydrogen chloride, can yield varying amounts of combustible gases depending upon the askarel type. Insulation systems incorporating these askarels and cellulosic or other organic materials may, when arced, produce gaseous mixtures which are moderately flammable. As a precaution, such gases should be removed from the askarel by bubbling dry nitrogen through the askarel and flushing the gas space with dry nitrogen before any work is performed on the apparatus. Vlil. Avoid Environmental Pollution Transformer askarels contain polychlorinated biphenyls (PCBs) which have been used in the United States and elsewhere over the past 40 years for many industrial and consumer applications. During the past several years evidence has accumulated to indicate that PCBs are widely dispersed throughout the environment and that they can have adverse ecological and toxicological effects. The United States Government's Interdepartmental Task Force on PCBs, Com-72-10419. in their March 20, 1972 report titled, "Polychlorinated Biphenyls and the Environment", recommended restricting PCBs to use in capacitors and transformers. This report is distributed by the National Technical Information Service, U.S. Department of Commerce, Springfield, Virginia 22151. A document titled, "Guidelines for Handling and Disposal of Capacitor and Transformer Grade Askarels, Containing Polychlorinated Biphenyls", has been prepared and is available from the American National Standards Institute, Committee C107, 155 East 44th Street, New York, New York 10017. The scope, objectives and the composition of this committee are: ANSI Committee C107 Scope: Procedures and guides for safe use, maintenance and disposal of askarel and askarel-soaked materials used in electrical equipment. Objectives: 1. Source of technical information and advice for Federal, State, local authorities and all others concerned. 2. Encourage development of suitable disposal facilities and keep all concerned informed. 3. Serve as the advisory group for United States participation in international organizations: CEE, IEC, CIGRE. 0565125 TOWOLDMON0036818 WATER_PCB-00021287 Composition; Organizations active in or represented by this ANSI committee include; National Electrical Manufacturers Association, Electronic Industries Association, Institute of Electrical and Electronic Engineers, American Society for Testing and Materials; Electric Light and Power Association; Certified Ballast Manufacturers Association; Environmental Protection Agency; Office of Environmental Affairs; General Services Administration; National Bureau of Standards; Department of the Army; Rural Electrification Administration; Division of Environmental Research, TVA; American Public Power Association, Water Pollution Control Federation; Food and Drug Administration; National Fire Protection Association; Underwriters Laboratories; and several sections of the U.S. Department of Interior. The following are pertinent excerpts taken from the ANSI Guidelines for askarel transformers: 1. LABELING ASKAREL TRANSFORMERS "All new askarel transformers should be labeled: The Insulating Liquid In This Transformer Contains Polychlorinated Biphenyls (PCBs). Care Should Be Taken To Prevent Entry Into The Environment. In Case Of Malfunction Or Leaks, Consult The Instruction Manual Or The Manu facturer, The transformer manufacturer should make similar warning labels available for use on previously installed transformers." DISPOSAL OF LIQUID AND SOLID WASTES "Disposal of askarel fluid and askarel-soaked materials must be accomplished by means in which there is no significant release of askarel to the environment. At present, disposal is accomplished by carefully controlled high temperature incineration of liquids and soaked software; and by controlled dry land-fill burial of apparatus and other hardware from which askarel has been previously drained and washed. "Present knowledge indicates that proper incineration should involve a suitable balance between dwell time and tempeiatuie in the incinerator plus oxygen availability and finally suitable scrubbers to remove HC1 formed; e.g., (1) two-second dwell time at approximately 2000F and 3% excess oxygen in stack gas; (?) 1-1% second dwell time at 2700F and 2% excess oxygen in stack gas," The ANSI Guide lists the locations of facilities that conform with the above requirements. Monsanto has such an incinerator at the W. G. Krummrich Plant, Department A 246, Sauget, Illinois 62201, where arrangements can be made for scrap askarel liquid disposal for a modest fee, currently 3 cents per pound. For disposaf of solid scrap a controlled dry land-fill can be used where permitted by Federal, State and local regulations, CONDITIONING OF NEW OR RECYCLED ASKAREL Conditioning ol new askarel oi recycled askarel requires Fuller's earth treatment. The spent Fuller's earth in cartridges or bags when replaced should be allowed to thoroughly drain over drip pans to remove as much liquid askarel as possible. The cartridge units of steel mesh construction should be placed in the "Steel Contaminated with Askarel" container for disposition. Cloth bags filled with Fuller's earth should be placed in the "Scrap Burnable Askarel Waste" container for disposition. TOWOLDMON0036819 WATER PCB-00021288 g|j&j 4. TEARDOWN OF TRANSFORMERS FOR REPAIR OR SCRAP a. Drain all askarel from the unit either into a holding tank for reuse or into the drum labeled "Scrap Askarel" for disposition, then allow sufficient time for all the askarel to drain from the core and coils. b. Remove the core and coil assembly from the transformer and place it on the floor. Sufficient absorbent material should be placed on the floor to absorb any askarel fluid that still drips from the transformer. c. Place all materials in the appropriate salvage containers during the dismantling for later disposition. d. All used materials, including rags, sawdust, tape, etc., regardless of quantity, should be put into the appropriate containers for disposition. 5. TRANSFORMER DISPOSAL The ultimate disposal of an askarel-filled transformer may be accomplished in either of two ways. a. Complete drainage and dismantling with the proper disposal of the askarel liquid and askarel-soaked components as described above. b. Disposition of askarel transformers by means of junk or scrap dealers should be avoided unless a transformer is first drained, followed by soaking of the interior with a suitable solvent, such as kerosene. Accumulated liquids and washings are to be disposed of as described earlier. IX. Expected Service Life Manufacturers indicate that properly designed and installed askarel transformers are expected to give trouble-free service for at least 30 years. Since their introduction in 1932, the manufacturers report finding the overall failure rate to be less than 0.5% for all units under test and service conditions. The Edison Electric Institute's report 11956-1958) on their member utilities publishes the failure rate for askarel transformers as 0.13 per hundred banks per year. Mr. Frank M Clark, who invented transformer askarels at the General Electric Company in the early 1930s, made the highly pertinent comment based on his many years of experience with G.E. Pyranol (askarel type) transformers that -- "The important thing is to keep them dry -- otherwise leave them atone". These words of wisdom became especially applicable in more recent years when welding shut rather than gasketing became the main method of sealing askarel transformers. These units are sold with the understanding that the liquid is in a normally hermetically closed system. X. General Characteristics of Transformer Askarel Fluid Appreciation of the following characteristics, as given in the IEEE Guide, leads to understanding the reasons for selecting dielectric breakdown voltage and moisture as the prime practical tests to judge the quality of transformer askarel fluid. Also, due to these characteristics the power factor of transformer askarel will be normally much higher than the corresponding values for mineral oil. In comparison to mineral insulating oil, askarel is a relatively polar material; i.e., its molecules are dipoles, free to rotate around their axes and responsive to orientation by electrical forces. Askarel also exhibits a much higher dielectric constant and capacitance than insulating oil, and these differences must be kept in mind when interpreting electrical test data. Because it is relatively polar, and possesses high solvency power, askarel is much more electrically sensitive than mineral oil to traces of extraneous soluble polar materials, and consequently TOWOLDMON0036820 WATER_PCB-00021289 wntltivitv <TMtlected or%S*#' v ?,r 'wm*'*e\ -tw it is important to note that, with the exception of water, the dielectric breakdown voltage ofaskarel it not genefally^yersely affected by ' many of the soluble polar materials to, which, jttfpower factor end ^resistivity (specific resistance) are so sensttive.fn fact.ihe dielectric ^breakdown -voltage of askarel is somewhat greeter ijhanthat of insulating oil. Therefore, the values assigned these dielectric fluids in ;.v e newly supplied transformers are 30 KV min.arfd 26 XV min., respectively. " ' 1" ,/ ... ' ` . As with insulating oil, askarei must be kept dry. It can pick up moisture v4-;> from exposure to humid atmosphere. Under similar conditions of , exposure, askarel can pick up nearly twice as much moisture when measured on a parts per million weight basis. ".-..y. ^V'XI. Sampling Transformer Askarel Fluid y^r.; ; 'The following precautions about sampling are quoted from the IEEE Guide. , "Representative samples, whether of the complete contents or only parts thereof, are extremely important from the standpoint of .evaluation of the quality of the product sampled. Obviously careless . . sampling procedure or contamination in the sampling equipment will . result in a sample that is not truly representative. This generally leads to V erroneous conclusions concerning quality and incurs loss of time, " effort, and expense involved in securing, transporting, and testing the V sample. It is strongly recommended that all of the procedures and precautions outlined in the latest revision of ASTM D 923 (Sampling " Electrical Insulating Liquids) be followed. "Because of the high specific gravity (relative density) of askarel (greater than 1), water and some other impurities are most likely to be found at or near the surface. The top sample, therefore, is considered to represent the worst condition." XII. Evaluation of Askarel Received in New Equipment Some users of askarel equipment find it desirable to make "as received tests" on all equipment. It is quite common to use the dielectric breakdown voltage test and visual appearance as the most significant tests. If suitable equipment and trained personnel are available additional information may be obtained from the power factor, color, and moisture content tests. In sampling askarel contained in apparatus extreme care must be exercised in order to obtain a representative sample. ASTM Method D 923 should be followed. New equipment with askarel exhibiting the following characteristics is considered acceptable: Dielectric Breakdown Voltage Color Condition Visual Water Content Power Factor at 25 C 30 KV min. 300 max. (Straw color) Clear 35 ppm max. ASTM Methods D 877 D 2129 D 1702 D 1533 D924.D 150 `The power factor of askarel taken from new transformers, reactors and accessory equipment can reflect the presence of moisture, dissolved polar compounds, or other contaminants and may vary with the type of equipment from which the sample was taken due to the different ratios of liquid*to*SOlid insulation and to the high solvency power of the askarel. Given an acceptable water content and dielectric breakdown voltage bf The askarel as indicated above, a high power .-factor'seldom impairs the serviceability of the askarel withip rather broad Jimits and is TOWOLDMON0036821 WATER PCB-00021290 indicative of the degree of extraneous soluble-polar jnateriels present. Recognizing the possibility of a wide range of pcwver factors being recorded for askarel in new equipment, it is difficult to establish a single limit which would be acceptable to both suppliers and users for all applications. However, as abroad guide, power factors up to about 10% at 25"Cand 60 cycles per second (hertz) do not in general indicate any abnormal contamination providing that the other criteria (water content, dielectric breakdown voltage, etc.) are met. Much higher power factors may indicate excessive contamination or the misapplication of the solid materials used in manufacture in contact with the askarel and should be investigated. XI11. Dielectric Breakdown Voltage -- Moisture Relationship The dielectric breakdown voltage of askarel is highly sensitive to excess 'moisture; not sensitive to ordinary dissolved polar materials. While the dielectric breakdown voltage can also be lowered by severe arcing, askarel turns noticeably black or has particles of sooty carbon floating in it if arcing has occurred. Then the transformer should be repaired and the askarel replaced. If the dielectric breakdown voltage is checked periodically and decreases significantly -- this indicates moisture pick-up, arcing, or both. When the dielectric breakdown voltage has dropped to 26 KV or less, an analysis for water is necessary. If water is found in excess of 40 ppm at room temperature, its source should be located and corrections made. When the moisture content approaches 125 ppm (saturation level at room temperature), the dielectric breakdown voltage of askarel drops below the value required for efficient insulating. The moisture content should not be allowed to rise over 70 ppm, sampled at operating temperature. If the moisture content is found to be in a satisfactory range and the dielectric breakdown voltage is low, the transformer manufacturer should be consulted. Table IV shows the relationship of dielectric breakdown voltage vs. moisture and Table V indicates the approximate water solubility limits in askarel and mineral oil. Table IV Relation of Dielectric Breakdown Voltage to Amount of Dissolved Water in Askarel and Mineral Oil Water Content (PPM) Breakdown Voltage (ASTM D877) Askarel Mineral Oi 0 70 KV 50 KV 20 55 39 40 47 30 60 40 26 80 38 22 110 10 - 6 TOWOLDMON0036822 WATER PCB-00021291 Table V Approximate Solubility of Water in Transformer Askarei and Mineral Oil Amount of Water (PPM) Dissolved Askarei Mineral 30 22 20 4 10 14 0 32 10 50 20 68 30 86 40 104 8 16 28 41 65 94 128 170 8 10 13 20 33 58 85 130 XIV. Turbidity ... may be the visual sign of undissolved water, or may indicate dirt. Cloudiness may also result from cold precipitation of tin tetraphenyl "scavenger" that was used in the earlier Pyranol transformers. This scavenger begins to come out of solution around 15F above zero. To redissolve it requires heating to 150-200F and agitation. High dielectric breakdown voltage will quickly indicate that any turbidity present is not moisture; that the insulating efficiency of the askarei is still excellent. However, if the dielectric strength is below 26 KV, moisture should be determined, using the Karl Fischer method (ASTM D1533-60). The dielectric breakdown voltage test for askarei serves primarily as an indicator tor moisture. It is by far the most important maintenance test for transformer askarei XV. Check Points for Maintaining Askarei Insulation A. General Considerations: Modern askarei transformers with welded construction or silicone or Viton* gaskets (hand hole-cover, switch and terminal compartment covers) and with properly constructed bushings require little or no maintenance. With properly constructed transformers, annual or semi-annual visual inspection and dielectric breakdown voltage test of the askarei fluid should suffice foi loutine maintenance checking over many years of service. However, many askarei units were installed in the early 1930s -- before the development of some of the better modern gasketing materials and before improved designs were developed for sealing out moisture. Such early units should be, and can be, modernized. Leaky or deteriorated gaskets should be replaced. If the askarei has become contaminated, it should be reconditioned. At the same time, a general clean-up of the unit and possible refinishing may be desirable. If it is not convenient to take an old transformer out of service for general repairs, leaky gaskets can be sealed temporarily by painting over the leaky area with epoxy cement. A survey of users indicates a good number of early-built askarei transformers (over 20 years old) are kept in continuous service in critical installations by the following steps (instead of modernization). The operating units are equipped with compound pressure gauges for reading pressure above and below atmospheric. Positive 'Trademark of E. I. DuPont DeNemours & Company, Inc. 3I TOWOLDMON0036823 WATER PCB-00021292 ^Tpjr. plained on the shell by introducing nitrogen at 2 to __ pourKfrjlbove atmospheric, Regular workmen in the area daily ^fcord the temperature and pressure. If a sudden pressure drop is "''led more httrogen is introduced and the gaskets are checked for -5-^aks wlth eoap solution. Leaks are sealed by applying epoxy -(Segment. '25Modern1Sealing Procedures: Transformer ^purchasers should specify the following modern 'techniques forsealing: 'vl, Weidrpg Construction: Covers, radiator connections, switch And terminal housings, instrument connections, etc. should ` i be welded. .'Bushing Connection: A number of bushings have been developed to obtain e proper teal for thejeHectrlcal connection through the tank wall. They are classified-s?. follows: ` v- . 1) Welded Type (Bushing flange welded to tank wall) ? ^v a. Cist resin bushing with a molded seal to The . : * Vbushfflglstud nd external etainless steel or copper ^-:-fianges^^ "" Rolled flange bushing with the metal to porcelain seal at the cap and flange made by being rolled into grooves in.the porcelain over silicone rubber rings. . The. seat between the cap and stud is made by welding. c. Porcelain or glass bushings with metal to glass or -metal to porcelain seals. Bolted Type (Bolted to tank wall) k . '/.'a. Cast resin bushings with either cast or metal flanges containing recessed gasket grooves, b. Porcelain or glass bushings with flanges containing recessed grooves or gasket stop. The gaskets may be either of rectangular or circular cross-section, usually V* inch thick. Bushings with recessed grooves are suitable to use with cork, cork-nitrile rubber combinations or nitrile rubber as well as gasket materials such as silicone or Viton. Small Size Connections: When not possible to weld, small size connection seals should be made with Flexitallic* stainless steel rings. The surfaces must be machined end parallel. The filler between the steel laminations of the Flexitallic ring should be either silicone or Viton. Gaskets for Hand-Hole Covers: Modern design specified silicone gaskets. Such gaskets must be retained in a groove. The groove preferably is machined into the flange or cover. However, it can also be formed by welding concentric steel strips to the flange or the cover. Generally the gaskets should be 5/16 to 1/2 in. thick for covers, depending on the depth of the groove or stop. A rectangular cross-section is usually used. The silicone material should be Dow Corning No. 60 Silastic** or equivalent. This is a low compression set material. For best sealing 20-25% compression is recommended, with ample clearance in the groove or stop to allow for this compression. No cement it required. With reasonable care the gasket is removable without damage and is reuseable. - , Silastic 50 is slightly swelled by askarel which contributes to the tightness of the seal, it is not deteriorated by 4|Skt<Al!f|*iid or vapors. It resists weathering and it Is thermally^a**!** * radamark of FsexitelliO'GeiKat Company `Powjporrii TOWOLDMON0036824 WATER_PCB-00021293 ;& Jiv flaxIMe^tWlttOpift multure barris^,' v^x excellent m NOTEiOow Cornfng>^liiar^/M*S^?fifUPPS'fi list of: . Silastic 50 gaskef fabricators^!) 'transformer `i r ' manufacturers or users. Theywht-alspfurnish technical data. See Appdhdix properties and Procurements. ,;S\r. ^ 'The Older Sealing Arrangements Yj*. !^k>^ r* The older type gaskets consist of either node or odrkoltriie rubber combinations or straight nitrile rubber. :,,.: v;jg4fj-. 1. Cork-Nitrile Combinations: Covers tforvShe mam tank,: hand-holes, switch and 4erminaKchambenrVftlief diaphrams, i etc., are held in place by studs welded f&the flange or by bolts. The gaskets are cut with openings Jhd pleoed over the bolts. Often Shellac (Westinghouse tityfe^No. \ 160419, or General Electric Company's Glypt&t1* :1276|" Is used to cement the cork to the flanges. ' 1` '* The following is recommended for terimg with the cork ^ nitrile rubber combinations: ; - Use Armstrong NC-757 cork-nitrile material or equivalent. The gasket can be cut from a single sheet Dr,by scarfing strips of the material. A convenient method for joining strips Isto :v ?|; make a Keystone Type joint. For this purpose, Westinghous*, : Sharon, Pennsylvania, offers their gasket cutter Style No. 32Q B614G01, (about $15) , The joints -and also the gasket ^ihodld^totementad to the flange, using one of the above o^nients. fixcass^cement should not be allowed to reachjthe'mterior of thotranaformer. HI 14 *V t* After installation and^joltmg, the outside'Kjg of the gasket . should be ooated thoroughly with-opjPxy cement to increase . weather resistance. . fL*,,. .Li ' V , ,** ' .d O This epoxy cement Ud^pasW towH'Ch^htiUring catalyst is added immediatelybafQif4^.'1l4rpl6ll4ra:f^, T n > .: d Epoxy PatchKitJr\ % Hysoi Corporation^UMM^e^Vorjc'^^ <1*' V b Scotchcast** Raitl&M *K Minnesota MiningwMRpbmBany ^ St Paul, Minnesota. ,, - > A c Adhesive A-l tad . Armstrong Product*Company j jgjsjijjfc < , m d. Argonne Road, Wr*ewr1qjliarw % 'J Adhesive Lfi860-V>^yflthetlc>^9rganic' Company, i*# Cleveland,^lo,sedwr^hctiVkt6rJilthvl0hetriarnine (Carbide and Oar^M>>W^-^f^Fiy) , V> Straight Nitrile fC^bor was oriBinally used, InvarleWyJtfwg#tktMgfitanKi 4n a groove. This was 10 prawnt <hi material ,, ** * Since groovatri v "'trite robtort ^ vwwnmi$teSj b^trlodie flu Cu.aSiagularKhartuW K~Wf~ m , Visual Inspection: Askarel is a clear, faint-yellow liquid. After long-term use this :.<color may gradually intensify to light brown. The fluid should .remain clear and free from turbidity or cloudiness. Any color change -- such as to a green, red or blue cast - indicates extraction of impurities (color materials) from the solid insulation If a distinct foreign color pick-up is noted, check the complete range of electrical characteristics and notify the transformer maker. Blackening of the askarel may indicate an arcing condition. Other color changes alone are not danger signals since the dielectric breakdown voltage is not likely to be impaired. Dielectric Breakdown Vertege If the dielectric breakdown voltage has decreased significantly from the last inspection, or if it has gradually decreased below 26 KV range (at 25C) - RUN A CHECK FOR MOISTURE. Use - ASTMD1533 (Karl Fischer Method). , The dielectric breakdown voltage of askarel is the major indicator to the operating efficiency of your liquid insulation. Besides the visual inspection tests, dielectric breakdown voltage is the only test necessary to run on a routine basis. Well-sealed askarel transformers have service records of 25 to 30 years on the original askarel. XVII. inspection Checklist 1. If askarel is clear --.even though darkened to light brown, has no sediment or turbidity, has dielectric breakdown voltage over 26 KV - give it the inspection "OK". If askarel is clear, but has foreign color of blue, green, red ... it is "extracting color" from internal materials. This is not, of itself, an operating hazard when the dielectric breakdown voltage stays over 26 KV and moisture remains low. However, this rare occurrence calls for checking into the condition of the interior construction and consulting the transformer maker. However, when sampling the fluid care should be taken to avoid getting color into the askarel from paint that may be inside or outside of the sample valve. 3. If the moisture content is found to be above 70 ppm at operating temperature, then sampling should be done at more frequent intervals to establish a possible trend, particularly on outdoor installations. 4. If askarel is clear, but dielectric breakdown voltage drops to 22 or iower KV, and moisture rises over 80 ppm when sampled at operating temperature ... the askarel is ready for simple "refining". If the moisture is near the saturation level (about 125 ppm at room temperature) a thorough inspection should be made for water droplets in the transformer tank, and even for "globules" of water floating on the askarel surface. If found, the transformer manufacturer should be consulted for reconditioning both the transformer and the fluid. . If askarel is dark brown to black, if black particles of carbon are seen, and dielectric strength is low . .vthe askarel has been broken down by arcing. It cannot be refined and should be removed and incinerated under proper conditions. (See ANSI Committee C107 report on Use and Disposal of Askarel sod Atkarei-Soaked Materials. 115 East 44th Street, New York, New York 10017). TOWOLDMON0036826 WATER PCB-00021295 f jMl. Contamtnation intwmform*^' 4^ ^'? JM^MoiiturBr^>Brticu>ata mattar `and arced decomposition productsare W* known to fee serious contaminating influenoK^w transformer askaral. ii |':c i.-A-A '..'.''"'/iji -. j-,i. ... u&tf-W ' t^ j Ths power factor test normally used for the detection of contamination In mineral oil (Med transformers is df little use for -this purpose in askarel filled transformers, due to the extreme effect of extraneous soluble polar materials. This increase in power factor as illustrated in - ,, tfTable VI has no adverse effect on dielectric breakdown voltage. '; Table VI 1 J ' Effect of Common Insulation Materials on Power 1* v` Factor and Dielectric Strength - S # . {Heat Aged 96 Hours in Askarel at 100C.) _P__o_w_e_rAFskaacrteolr,After EDxipeolescutrreic iM 'Percent at 60 . eye., 100*0 Strength 25"C. ^Material Immersed 1.0 35 KV i - None (control) .v Black varnished cloth -t.11' Copper *. Pressboard Manila paper ': Phenol formaldehyde resins Shellac .. , ^ ! -^V-lron-.':.'' V "".' 85.0 1.5 2.0 1.5 . 1.6 ` 6.0 5.0 70.0 42 40 37 39 41 36 39 39 Synthetic rubber ' Similirly/:^trace contaminants from commonly used construction '% HtnaterWiden lower the volume*resistivity of askarel, without affecting Y: ' its dielectric breakdown voltage. This is shown ipTable VII. .. 1, ' ........................ ' .................''..... *............... 1 ' ' Table VII Effect of Common insulation Materials on Volume Resistivity of Aakarel ' Volume Resistivity , x 10 ohm-cm (at ' , IOO`C.,600 Volts Sample ' 1. New askarel before heat aging OC.2,0,0r0*g0 ap) * 2. New askarel after heat aging 96 hours at 100C 1,900 *f3. Alter heat aging with 1 sq. Inch specimens of : a. Phenolic resin tap changer material 1,200 . b. Paper 750 c. Grade A pressboard (tan) > 600 `d.Grade A pressboard (gray) - > 600 v . a. Grade A pressboard, laminated strip 400 f*Cotton wrapping - 300 r&: ,f*2:rW , v; - &:<r TOWOLDMON0036827 WATER_PCB-00021296 Manufacturers of askarei type transformers point out that it is quite well known that askarei transformers with initial power factor of the -askarei fluid in excess of 50% at room temperature and 60 Hz are giving satisfactory service life. However.there needs to be assurance that both dielectric breakdown voltage and moisture are at satisfactory levels and do not show adverse trends. XIX. ASTM Method For Investigating The Compatibility of Transformer Insulation end Construction Materials in Askarels This method12 uses the change of electrical and/or chemical characteristics of transformer askarei resulting from its controlled exposure to insulation and construction materials, in order to evaluate their immediate major "contamination'' effect on the askarei fluid. Delayed or long time contamination effects may not be detected. The methcrd also utilizes various physical tests on the insulation and construction materials after controlled exposure to the askarei to determine the compatibility of these materials with transformer askarei. Properly proportioned specimens of the insulation or structural materials are immersed in refined askarei for 168 hours at 100 + 1C in a forced draft oven. Changes in electrical and chemical properties of the transformer askarei are compared against a control sample of the askarei treated in the same manner, in absence of the test specimens. Dissipation factor (ASTM D 924) change is one of the criteria used. The askarei fluid is refined by absorptive treatment to a dissipation factor level of 0.05 max. at ?00C and 60 Hz and 0.01 max. at 25C and 60 Hz. Corresponding values of the askarei fluid after heating 168 hours at 100"C in absence of a test specimen are 0.075 and 0.02 respectively. The maximum dissipation factor levels suggested for the askarei after heating in presence of the test specimen are 0.20 at 100C and 60 Hz and 0.04 at 25C and 60 Hz. XX. Refining Askarei for Reuse A. Filtering Through Dry Blotter Paper to Remove Moisture and Extraneous Particles: Most operators prefer portable refining apparatus, such as a plate press fitted with a dolly, available from Sparkler, Mundelein, Illinois or General Electric Company, Pittsfield, Massachusetts, or the earthen cartridge filter type available from Industrial Filter Corporation, Lebanon, Indiana. Filter paper liners for the plate press are available from Carl Schleicher and Schuell Company, Keane, New Hampshire and manufacturers of filter presses listed above. The filter paper must be dried immediately before use. For best results, spread the paper for maximum surface exposure in a hot air circulating oven and heat it for 4 to 6 hours at 110C. Circulate the askarei hot (but not over 40C) through the filter fitted with the dry paper liners. After filtration the dielectric breakdown voltage of the askarei should be 35 KV minimum. 1. Precautions: Filtering should not be done when the relative humidity exceeds 75%. 2. Any flexible hoses and gaskets on the refining equipment should be lined with or made of materials that will not be softened by contact with askarei fluid. (Materials lined with Silicone, Viton or Teflon* or flexible metal materials are suitable.) ^In process of publication by ASTM. as of this writing. Trademark of E. I. DuPont DeNemours & Company, Inc. TOWOLDMON0036828 WATER_PCB-00021297 TOWOLDMON0036829 WATER_PCB-00021298 <;& j^r. it"" k?4' (W'm*' Iwf m Table IX . % ^ Apprdrimiate Relationship Showing the Insignificant 'Effect of Rower Factor and Volume-Resistivity on Dielectric Breakdown Voltage of Transformer Aakaral Power -Factor 160 eye.) T5gg~ ' 25"C Volume Resistivity x 109 ohm-cm (at 100*0,500 Volts OC. 0.1" aaD) Breakdown Voltage 28*0,1). V* gap 2% 65% 16% 20-25% 40-50% ` : D.05% t;;so.i% . -MK s`9, Vfl.O% ^ ' '. - 1500 500 too flO-70 25 35 KV . 35 ; V1 -35 * -J____; XXI. Cleaning Aroad Transformers .V if a unit has arced,|bat she askarel is no longer fit forSfiM>thorough .cleaning of the^itmf^i/neoessary before refilling whhvfww askarel Insulation erKlietUmwlft^eservioe*. Follow this prooedor^i * . - 1 'ii )ls " v 1 A. ; Drain out ali>dari('/oertion-contaminated askarel. Arrange to have v J . the scrap fluid Incinerated under proper conditions. (See ANSI CommineeCfOTyepOftJ. N -~y" B. Carefully brushcerbondeposits from internal parts end insulation, v- using a toftJyjrtlg .brush making sura that insulation is not damaged. #>V` " * ; VJiVi* - ' ' ' ' . v^ "" C. Flush thoroughly musing new askarel - -/tor an oil, not a cleaning ' . solvent. .* . .. > D. flush a second time with fresh askarel; dram; then fill to the proper level with new askarel. E. Energize transformer to warm the fluid for 24 to 46 hours; then circulate the arikarel through a fitter, returning it to the unit filtered and ready for use. ' *Thit assumes that the cause of arcing has been established r>d corrections made. 'When severe arcing occurs, major repairs are usually necessary and the unit rebuilt. This procedure can be applied for flushing out the repaired units. -XXII. Sampling Askarel ; Take a sample as close to the top of the liquid surface as possible. Many large askarel transformers have a built-in sampling tube near the surface for convenient sampling. Then, to make sure that your sample truly represents your askarel insulation, take another sample from the bottom. If additional 4ampling tube connections are contrived on the valves for easier sampling, make the tubes of clean glass, stainless steel, aluminum or tin for rigid types; and silicone, or Viton or Teflon tubing for flexible types. i> . . .. . Use NEW containers for the askarel sample. A newpnd{thoroughly pre-dried,small-mouth 'quart glass bottle fitted with ;akftitfc* screw cap with aluminum or. tin gap ^ner, if recommended-for qyfck,on-site testing, (if complete,*na!y*ty'4 tin** a8*piry is nquirec ) .W*. Miff" Aw *. -, ^/.aBbaS* ifle sure fhat the Jiew^bdttle does not stand open *1 'tttpisbim. RimCljhftiftMe bottle nd cap Wning %* TOWOLDMON0036830 WATER PCB-00021299 TOWOLDMON0036831 WATER PCB-00021300 BvwJprjjrJn3ji*v. ' ' V-aO. IBfcttSjV *' ' t^s% " V ItvWvVSyjj ,V Askarelfc'},' Sited Switches land Terminal Chambers V:;C - . : *shi >*? . I. Introduction '% High voltage leads are trtually connected to askarel or mineral oil-tilled network transformers end powerccenters through terminal chambers land switches. In somejqpses terminal chambers are not used, and the high voltage leads aregconnected directly to the switch terminals. They may be filled with either askarel or mineral oil. Switches are usually rotary or drum type fitted with a revolving block and porcelain unit as ' the principal element arranged for three-phase service. Askarel transformers 4jyjth attached switches have been in use for about 30 years. When theyWere first introduced, the availability of insulating and gasketing materials was rather limited and even the best materials at the time had no service history. As a result, inadequate gasketing materials such as cork, nitrile rubber, and nitrile rubber-and-cork particles were used. White satisfactory for a limited period of time, these materials cannot be depended upon for the expected long life of the equipment. , . The terminal ^chamber is usually above or below the switch compartment and separated by a steel wall through which the bushings are inserted. When bushings are'properly selected and correctly installed, there is no leakage from one compartment to the other. With poor bushing seals, and the terminal chamber above the switch, potting compounds or cable oil can seep into the askarel. When the terminal chamber is below the switch, askarel can drain into the terminal chamber, II. Sources of Contamination There are three possible sources of contamination for askarel in switches and terminal chambers; they rank in this order of frequency: (1) water entering through poor gaskets; (2) decomposition products from arcing when switch is used to break magnetizing current; (3) entrance of pothead or cable compounds through leaky bushing seals. Unlike an askarel transformer where the amount of contaminant is likely to be very small Iprobabiy only trace amounts) in relation to the volume of askarel fluid -- in switches or terminal chambers with faulty seals, the amount of contamination can be relatively large. Experience has shown that, based on the number of installed askarel-switch units, the percentage of failures is extremely small. When investigated, it has been found that most failures originate in the switch chamber. Water is the chief source of contamination. However, heavy contamination of askarel with petrolatum and asphalt material, due to leakage, have caused a few failures. Petrolatum is used frequently for filling terminal chambers. When either cable oil or petrolatum seeps into askarel, no great harm results. The fire resistance will be somewhat decreased and power factor of the askarel will increase with an accompanying drop in resistivity. While highly undesirable, it is doubtful that failure of the unit results. Where asphaltic compounds are used in place of petrolatum, the danger is increased ..somewhat because asphaltic contamination may cause excessively high dielectric losses in the askarel. ; ' "^When $he `'Jerrofnel chamber is 'below ehe twitch chamber, the potting be contaminated by ^askarel If the bushing seals are < because the askarel willinweese the power fl^nductivity f.the spotting compound or .cable oil end mdie.lectricloss.Jtf'this mixture Is drawn Into thleeWe v: -V 1 565139 TOWOLDMON0036832 WATER PCB-00021301 ding Wherever^m f'SMtdWhere ..... .-jAfiwskf.;...t>v> "**? .i/3 r iqulpmenf'tho utenlhpuld speclfy/jtbaseu Umanuto kaaptdufcontaminants and minimiae i ilhtenance. ^|&ikaret Utad Under Mild Arcing Conditit U,r-- P^CGG Guide fpr Trsnslormer Asksrel crihigi btion '.to the - Slowing: \T- " > * i**- ffdsikarel is uied.ifo some extern, in ap;>a'etuiiWh*r^t is Subjected. , itt light intermment arcing. auch at ig^aelt ewwlnad ptfrutife gulatort. whet? opetatlng ^witches erecortiftiiaUyltfOducintl :, Jght ,,*fgs, ' in ..'traniformer de-energizing MMPtdAK < UMfej-- iprmal conditions, .deterioration of the asksfsl iris eepf ali^vt^S Uowevar, Improperly adjusted or defective swltqhbs in this type,i($*I apparatus can produce excessive and . prolonged arcing arid .*,$ .''accelerated deterioration of the askarel. ft js recommended th(t -S 'When etkarel it used under these conditions, chBCkt of the liquid,' i'^ 'eipecially for 'moisture'and,;dielectric Oreekdown uoltage medeci more frequently than when it is used only es A cooling and S', Insulating fluid- Deterioration of this type is indicated bySe ;f Bffelackenlng_ ' W.f'*th#er liquid. It c-a--n u...s..u. ally be reoondltiOned at lously dosoribed. -tSpecial attention. should . be .given yth , /# sdiintanancaiofAitatilfcMiod Swittww^^^-r.f'' . 1J- Switches uted'ffdr igroundi^b after peweragutoa |ias been*' 5 > -de-energizedwlliti^t^ndergMgii(ig. <S. Switches interrupting megri^itlng cunyhStSflbi subject arcing; the .amount inf decomposition will depend on povysr,I. interrupted, -time andJjattdency ofi-ciperation.'iH.t i general rdlfe the liquid should be chedtaildSterS'idf'IOiKWrattMq,:i 1. On newly installed switches, oheok tbe-askeoel Jt3,6 end 12, . '* month mtervelsi if found satisfactory.ipfysAr'.onca annually thereafter. WJthibfoparjfttentionlo .thejjMketirtgof oo( and bushings. 4i)<fwrJem ;w)ll-%ri>t>ibl/i<dMj(lhate vthetli frequent in&^r^fedtj ' 2. Check askerel '- T Dielerlcni^^itol*^rt72):-'1tShc^ ' be 28rKVfnin]n)u|S;lf#aIectriqfet4eWown>raltege1 low.orififmb*swofwitefl>y'l<rt Fischermet' ' A$TM D-lB33. 'i:hjer to yemos^ <Sdoisture..jpielei strength fhoptfltheh&e3fl KVflilnWsun),' .' ill V.vy X Presence f ncerbebl.'ifrom r-aigiifgt^luid should fre:3f?' relgtiwly'frka of M&n. If bsd)y>(iadI and-e*e*,rty bbiieaqkjprrt|Sl iyShlnutee iaw.fp`tvspretant,diitttifbi| i<* - |f HdUld'llfibdidt #lp. f&iimibtriwaP WSr 1H 05651*0 TOWOLDMON0036833 WATER PCB-00021302 ... wi". My 6. bv swelling and cracking of the exposed edge* In cases bf severe deterioration, liquid seepage Is usually present,. Check for leakage at packing fiend of twitching shaft. If leaking, repack with a Silastic ring type gasket.' tVI. Askarel Under Excessive Temperature or Fault Conditions ;^ yThe IEEE Guide also points out that, -` ' "Chlorobenzenes used in transformer askarel* begin to boil at temperatures of about 205*C, under atmospheric conditions. If the material is heated to such high temperature in a sealed system, i pressure develops. Pressure will also develop tn the system if the askarel is arced sufficiently to generate copious hydrogen chloride . ,aS. , j ?,diw 'yjfT w-: ' . 'Oh, ' -\- - "Therefore, it Is -recommended that -wherever posflbfo,1 sealed eskareMilled equipment be provided with pressure relief devices. , These devices must!* large enough to provide immediate reliefat _r a definite pressure,<)ind to.prevent further build uppfrpressure If . decomposition .ibontiqutt, -it must be remembered that iha presence of devices of this aort does not necessarily preclude the rupturing of containing vassals, since pressure build up can be extremely rapid under violent arcing conditions." *# jf Obbb'-'*1 TOWOLDMON0036834 WATER_PCB-00021303 insformer Askarel Available From Monsanto Transformer users not wishing to make their owh fluid analyses can obtain the service from Monsanto: Simply contact Monsanto and specify what analyses are wanted. You wilU>a sentthe proper-sized, clean sample container, fitted with a proper label. When you receive this, carefully take your sample {following the procedure for sampling in this guide). Send the container to Monsanto's laboratory. Charges listed include iampteontainer, shipping, handling arjjl laboratory costs. .... Typos of Analytes Available Analysis I) ROUTINE MAINTENANCE CHECK , .W * ' : >; , Total Charge: *S&*0 (/" ' To determine the general condition of the fluid and find whether further analysis is necessary, (one-quart sample required) Properties Tested Dielectric Breakdown Voltage Color and Condition Moisture You will be notified of the results of this test. If further testing is indicated, and you want a complete analysis, you will be sent a five-pint sample container. This sample will be used for the following series of tests: Analysis 2) - ^ 7 COMPLETE ANALYSIS Total Charge: $5fcW (1) To determine the extent of fluid contamination, (2) earth refinement to determine what degree of restoration of electrical and Insulating properties Is possible, (3) check test to tee how the fluid responded to earth treatment. a) Complete Analysis: to determine the extent of contamination Properties Tested Free Chlorides Color and Condition Acidity Specific Gravity Dielectric Breakdown Voltage Refractive Index - Power Factor, Dielectric Constant, and Resistivity Water b) Earth Refinement Response: Consists of treatment for 2.5 hours at 50-60C. with 0.1 to 0.2 percent by weight of properly conditioned Attapulgus clay and then filtration through dry filter paper. . c) Analysis After Laboratory Earth Refinement: Properties Tested Acidity Refractive Index Dielectric Breakdown Voltage Water Power Factor, Dielectric Constant, and Resistivity Free Chlorides You will be notified of the results of this test series on your sample. Then after refining your entire transformer fluid till you can check on the results by requesting the following analysis: / 7* Analysis 3) ANALYSIS AFTER EARTH REFINEMENT Total Charge: $3fr0 ^ (This charge will not apply when analyses 1 and 2 have already been made.) To determine whether the entire lot of the askarel fill responded to the same extent as the laboratory sample, (five-pint sample required) Properties Tested Free Chlorides Color and Condition Acidity Refractive Index Dielectric Breakdown Voltage Water Power Factor, Dielectric Constant, and Resistivity To arrange for the tests described above write to the following address: Paul G. Benignus Monsanto Company 800 North Lindbergh Blvd. St. Louis, Missouri 63166 Samples to be tested should be clearly marked for identification and sent directly to: Monsanto Chemical Company .. W.G. Krummrich Laboratory a. Sauget, Illinois62201 . . Attention: R. Kuster , .... - ~ . ^ . w1 , TOWOLDMON0036835 WATER_PCB-00021304 I Stability and Composition of Arc Formed Gas: Askarel insulation is one ohe most inert, chemically-atabla heat tant, non-corrosive liquids known, it will not break down, oxidize or sludge when exposed to air and high temperatures, C, or even somewhat higher. Arcing, however, will break down the oompound to liberate some hydrogen chloride and Stittfemounti of oarbon. " "P #, '' " APPROXIMATE COMPOSITION " - ARC-FORMED GAS FROM TRANSFORMER ASKAREL BLENDS ASTM TYPES D AND G * (INERTEEN 70-30 AND PYRANOLA13B3B-3, RESPECTIVELY) Gas carbon monoxide carbon dioxide oxygen . inert gases hydrogen chloride (note the absence of phosgene) Amount 0.3% 0.3% 0.6% 1.5% 97.3% Sw^tfe-formed gas from ASTM Type D and Type F transformer askarels is non-flammable and non-oombustible. WK'V - . JJ'drall practical purposes, the amount of gas liberated from askarel under a given set of arcing conditions is about 100 cubic ^Centimeters per kilowatt-second. ^APPENDIX B SOLUBILITY OF GAS IN TRANSFORMER ASKARELS ASTM TYPES D AND G Carbon dioxide Air Nitrogen Hydrogen chloride1 Mn absence of scavenger Percent of Gas By Volume Corrected to: 25*C 760 mm 0*C. 760 mm 25C 71% 5.7 6.0 37.8 100C 47% 4.9 4.8 50.9 25"C _ 5.8 5.5 - 100C _ 5.0 4.4 - EFFECT OF TEMPERATURE ON DIELECTRIC BREAKDOWN VOLTAGE OF ASKAREL Dielectric Breakdown . Voltage ASTM D877 TOWOLDMON0036836 WATER PCB-00021305 THE DENSITY OF INERTEEN 70-30 AND TRANSFORMER PYRANOLA19B303 Approx. Density gm/oc. -''mv- Tamp.'C 0 20 40 . 80 80 Inerteen 70-30 1.574 1.552 1.529 1.507 I486 * , : JX * t ;; Pyranol A13B3B-3 1.677 1865 1.532 1.510 1.488 RfcEPENPIX F The thermal conductivity values of transformer Pyranol A13B3B-3 at 27*C and 58*C are 26.2 and 258 x 10*# calories centimeters**, degrees centigrade-1, second-1, respectively. Or, approximately 0.06 BTU per <hr.) <sq. ft.) (*F.) per loot. ' This same approximation applies to inerteen 70-30. HTf APPENDIX0 ' ' ' " : ' ' Heat Capacity . Over the temperature range of 25* to 125*C the specific heat of transformer askarel is close to 0.30 calories per gram per 'degree. . ' '. . . APPENDIX H ^Coefficient of Expansion The average coefficient of expansion of transformer askarel over the temperature range20 to 100*CU0.0007oc/cc/aC.One gallon would increase to 1.056 gallons on heating from 20 to100*C. ' ; APPENDIX I "tit1*" 'Jl Ayifgfteslstanoe - . ' v..;. , ... - hsAskarel* of various compositional types are used. Under ercing oondifions the gases produced, while consisting of ?4dpradominantly non*comtMJStible hydrogen chloride can yield varying amounts of combustiMeoasestitpendlngnipoiithe 'aAlraltype. , * - y* * . 'YttJrer * 'r : InliS^itioh tystems Incorporating these askarels and cetlulosio or other organlc-vfteterialsmay, when arced.prddocagaseous |v$fflntxttff*t which are moderately flammable. As a precaution, such gases should be removed from the askarel byPubbiingdry ~ ``n through the askarel and flushing the gas space with dry tiitrogen before any work is performed on thM 056514* TOWOLDMON0036837 WATER PCB-00021306 APPENDIX j Seats, Properties and Procurement Dow Corning Corporation, Midland, Michigan with Districts at Atlanta, Boston, Chicago, Cleveland, Dallas, Los Angeles, New York City, Washington, D.C, and Toronto has available Bulletin 09*019, August 1962 entitled "Silastic Design Data". This lists the gasket fabricators throughout the country from whom the "Silastic 50" gasketing can be purchased in sheet, extrusions or molded shapes. Generally, Silastic 50 sheet goods are stocked by local die cutters, hence, could be generally purchased locally. Usually small quantities of gaskets are die cut. If larger quantities are needed, tools are made of the same type used to cut other elastomers. Where the gasket is extruded for fitting into a machined groove or between gasket stops, Dow Corning advises use of a scarved joint. This joint is then cemented using Dow Coming's Silastic 140 (clear) or their RTV 731 (white) materials, which air cure. .** Dow Corning points out that the local "rubber" fabricators purchase the Silastic 50 in billet form. This is worked on a roll mill in preparation for sheeting or extrusion. Then to obtain the desired physical properties the fabricator must oven cure the Silastic 50 for 24 hours at 480F. SPECIFICATIONS* ASTM D676 ASTM D412 ASTM D412 ASTM D395 Color Specific Gravity at 77F Hardness, Shore A. Scale Tensile Strength, psi, min Elongation, percent, min Compression Set after 22 hrs at 30OF, percent, max White 1.20 + 0.02 45 to 60 800 250 30 *All physical properties measured on 0.075 inch thick samples molded 5 minutes at 240F, and oven cured 24 hours at i% 480*F. APPENDIX K Caution Label The following or equivalent caution statements should be fixed on ell containers of transformer askarels and the transformers themselves: This product contains Polychlorinated Biphenyls (PCBs). Care should be taken to prevent entry into the environment through spills, leakage, use, vaporization, or disposal of liquid or containers. Avoid prolonged breathing of vapors or mists. Avoid contact with eyes or prolonged contact with skin. If skin contact occurs, remove by washing with soap and water. Following eye contact, flush with water. In case of spillage onto clothing, the clothing should be removed as soon as practical, skin washed, and clothing laundered. Monsanto MONSANTO INDUSTRIAL CHEMICALS COMPANY specialty products group won.LINDBERGH BLVD. ST. LOUIS, MISSOURI 63166 A'.kMr|>4!^5>fl!'on herein regarding obtaining optimum results from askarel fluids in your transformer has been accumulated by Monsanto for over 40 fritilmi.iirom the experienwce uoif makers and users of askarel transformers and it is believed will be helpful. --Onem^of ** construed applying to other than askarel insulation. Data and maintenance suggestionsiierein do not apply to the other " ._\?e ,r*nsformer. All operating end maintenance suggestions recommended by the manufacturer pi the transformer should also be L directions apply only to the askarel insulation. Monsanto disclaims any liability for damage to property or injury to T^'^dormeroperation. .- TOWOLDMON0036838 WATER PCB-00021307 TOWOLDMON0036839 WATER PCB-00021308