May 30, 1991
Dow U.S.A.
The Dow Chemical Company PO Box 150
Plaquemine, Louisiana 70765 0150
Dean Walters
Cell Service
Building 5601
On May 30, 1991, AT-500 and conveyor In the Cell Service Block, Building 5601, was checked for face velocity. The Alnor Model 8925 Thermo Anemometer was used to take the face velocity measurements. AT-500 was checked at afnV 24 " sash opening.
The criteria for hood classification, smoke tube observation, and flow measuring devices used in rating hood ventilation performance is attached.
Also included are recommendation(s), observation(s), testing data sheet(s) and a maintenance checklist which should be followed to maintain effective hood ventilation and appropriate classification.
Please respond in writing to Industrial Hygiene within one month as to action taken'or planned in regard to these recommendations.
Please feel free to contact me with any questions.
Thank you
Darlene S. Creel Industrial Hygiene Department Building 3502-W Ext. 6181
DO A 072876 CONFTDFNTT Al
Page 2
Observations;
The laboratory hood designation, the average face velocity (FV) and minimum measurements (FVm) reported in feet per minute (FPM), and its rated classification is as follows:
(FPM) (FPM)
DesignationSash Hood Opening FV______ EYm___ Classification
AT-500
24 " 163 125
The smoke turbulence was good on AT-500.
OONVEYOR
The smoke turbulence was GOOD.
Recommendations;
1. AT-500 and conveyor should be put on C-9 checklist for annual check and routine maintenance done on them.
2. Practice good housekeeping inside the AT-500.
no A 0??S77
CONFTOFNTTAl
Page 3
CRITERIA FOR HOOD CLASSIFICATION. SMOKE TUBE OBSERVATION. AND FLOW MEASURING DEVICES
CLASSIFICATIONS;
CLASS "A" (HIGH TOXICITY USE) CARCINOGENIC, TOXIC HIGHLY FLAMMABLE
CLASS "B" (MODERATE TOXICITY USE) TOXIC OR FLAMMABLE
125-150 FT/M IN AVERAGE FACE VELOCITY 100 FT/MIN MINIMUM READING
100 FT/MIN AVERAGE FACE VELOCITY 80 FT/MIN MINIMUM READING
INADEQUATE DOES NOT MEET MINIMUM REQUIREMENTS
SMQKEJUBLQBSERVATIQfciSi
****GOOD (AIR CAPTURE BY HOOD IS STRONG AND WELL DEFINED WITH MINIMAL INTERNAL TURBULENCE, AND NO OBSERVABLE SMOKE SWIRUNG BACK TO HOOD FACE WHEN PERSON STANDS AT HOOD FACE.)
"`MODERATE (AIR CAPTURE BY HOOD IS POSITIVE BUT WITH SOME INTERNAL TURBULENCE OBSERVED APPROACHING THE HOOD FACE. NO SMOKE ESCAPING THE HOOD.)
"POOR (AIR CAPTURE BY HOOD IS WEAK AND/OR NOT WELL DEFINED. TURBULENCE INSIDE THE HOOD AND SMOKE OBSERVED ESCAPING HOOD FACE.)
FLOW MEASURING DEVICES:
WHEN THE STATIC PRESSURE DEVIATES (-/+) 10% FROM THE LISTED STATIC PRESSURE, ITEM #20 SHOULD BE FOLLOWED ON THE MAINTENANCE CHECKLIST ATTACHED TO THIS REPORT. THE STATIC PRESSURE READING WAS ESTABUSHED AT TIME OF PERFORMANCE CHECK AND INDICATED BY A RED LINE ON THE DEVICE. DOCUMENTATION OF AIR FLOW MONITOR DEVICE PERFORMANCE IS TO BE DONE ONCE PER WEEK. INSPECTION/ZEROING/CAUBRATION OF AIR FLOW DEVICE IS TO BE DONE ONCE PER YEAR. THIS DOCUMENTATION IS TO BE PART OF THE INDUSTRIAL HYGIENE RECORDS FOR YOUR PLANT. PLEASE FORWARD DOCUMENTATION TO THE PLANT INDUSTRIAL HYGIENE CONTACT FOR YQUR PLANT.