Document pBdvpk6506LZwM7Gvzobe8gkw
420
CHAPTER 28
1960 Guide
tures by room thermometers, and the determination of the temperature drop of water Sowing through a heating unit or zone by means of surface contact thermometers or ther mometers installed in the piping. When adjustment is made by means of water temperature drop, the capacity of the units after adjustment must equal the heat delivery actually required. Control is then accomplished by making the tem perature drop through all units equal.
(Provision shooid bo modo for expansion m each dosed drewf) fig. 20.... Vertical Zoning of Hot Water Heating System
in a 12-Story Building
The procedure for making a permanent adjustment of heat distribution in a larger system should be as follows:
1. Select a time or day when conditions of heat gain are minimum; Le, nighttime or an overcast day. Outdoor tempera tures should be such as to require at least 50 percent of the sys tem capacity to maintain the design indoor temperature.
2. Place the system in operation and make certain that all valves, adjusting fittings, and dampers are in the open position. Automatic control which might reduce the flow or capacity of any unit should be rendered inoperative. Doors and openings between rooms should be closed.
3. Prepare a form for recording data on temperatures in spaces or at the supply sod return of heating elements or of zones.
4. After the system has reached equilibrium a complete rec ord should be made of temperatures throughout the system.
5. An initial adjustment of flow regulating devices in the sys tem should, be made on the basis of the record of the original readings. A new set of temperature readings should be recorded after sufficient time has been allowed to establish a new equilib rium throughout the building.
6. Continue adjustments of flow control devices until a satis factory condition is obtained.
7. When a satisfactory adjustment has been accomplished, it is advisable to mark the position of each of the adjusting fit tings or valves. This facilitates return to proper control settings if the flow controls are disturbed by accidental or emergency changes at any time.
CARE AND MAINTENANCE OF SYSTEMS A hot water heating system should last during the life of the building if it is designed, installed, and maintninftH properly. Maintenance instructions for individual dements
of the system such as burners, motors, pumps, and accessories may be obtained from the manufacturers who supply this equipment. Two factors contribute in a most important way to the satisfactory operation and life of the hot water heat ing system: (1) the proper cleaning of the system when in stalled; and (2) a minimum change of water in the system, except as required by periodic maintenance of the boiler or draining of the expansion tank.
INITIAL CLEANING OF SYSTEM
Rules that should be followed for the initial cleaning of the system are:
1. All equipment and piping should be thoroughly cleaned of iron cuttings and other refuse during assembly and installation.
2. .When installation is complete, the system should be filled with a solution of 1 lb of tnsodium phosphate per 50 gal of water and should be operated for 24 nr at maximum tempera ture with all pumps operating. The system should then be drained and thoroughly flushed with water before refilling.
In order to minimize the addition of water to the heating system, the operation of air-vent valves, relief valves, and the tightness of the system generally should be subject to continuous inspection. Drips from automatic air-vent valves should discharge in places where leakage is readily detected. Continual operation of the pressure relief valve should be a signal for the inspection, repair, or replacement of the relief valve, or a check on the operation of the expansion tank or the automatic water feeder, if one is provided.
REFERENCES
1J. H. Keenan and F. G. Keyes: Thermodynamic Properties of Steam (John Wiley & Sons, New York, 1936, 1st ed.).
*F. E. Giesecke and J. S. Hopper: Friction heads in standard six-inch pipe (ASHVE Transactions, Vol. 47, 1941, p. 71).
*F. E. Giesecke and J. S. Hopper: Comparative study of friction heads in screwed and welded elbows (ASHVE Trans actions, Vol. 48, 1942, p. 201).
* F. E. Giesecke: Friction heads due to water flow in copper, brass, and other smooth pipes (ASHVE Transactions, VoL 49.
1943, p. 175).
*F. E. Giesecke: Determination of pipe sizes for hot water heating systems (ASHVE Transactions, Vol. 21, 1915, p. 473).
* F. E. Giesecke: Friction of water in iroD pipes and elbows (ASHVE Transactions, Vol. 23,1917, p. 499).
*F. E. Giesecke: Effect of temperature upon the friction of water in pipes (ASHVE Transactions, Vol. 31, 1925, p. 9).
*F. E. Giesecke: Friction of water in elbows (ASHVE Transactions, Vol. 32, 1926, p. 303).
*F. E. Giesecke and W. H. Badgett: Friction heads in oneinch standard cast-iron tees (ASHVE Transactions, Vol. 37. 1931, p. 395).
" F. E. Giesecke and W. H. Badgett: Loss of head in copper pipe and fittings (ASHVE Transactions, VoL 38, 1932, p. 529).
UF. E. Giesecke and W. H. Badgett: Supplementary friction heads in one-inch cast-iron tees (ASHVE Transactions, Vol. 38, 1932, p. 111).
u F. E. Giesecke: Two methods of figuring the friction loss in pipe lines (ASHVE Transactions, Vol. 59, 1953, p. 49).
"L. N. Montgomery and W. S. Hams: Sources of vent gas in a hot water heating system (ASHAE Transactions, Vol. 61, 1955, p. 483).
14 Low-pressure heating boilers (ASMS Boiler and Pressure Vessel Code, with 1954 and 1955 addenda. Section IV).
" R. C. Chewning and R. W. Peterson: Consider pump heads
when siting hot water expansion
(Healing, Piping and
Air Conditioning, July 1955, p. 106).
M H. A. Lockhart and G. F. Carlson: Compression tank selec tion for hot water heating systems (ASHVE Transactions, Vol. 59, 1953, p. 55).
aOscar Faber and J. R. Kell: Heating and Air Conditioning of Buildings (Architectural Press, London).
CHAPTER 29
HIGH-TEMPERATURE WATER SYSTEMS
features; Baric System; Design Considerations: Boilers, Boiler Piping and Controls, Direct-Contact Heaters and Auxiliary Heat Exchangers, Boiler Feed Pumps, Circulating Pumps; Distribution Piping Design: District Distribution, Pipe, Valves and Fittings, Thermometers and Pressure Gages; Space Heating Equipment; Temperature Control; Water Treat ment; Storage
HIGH-TEMPERATURE water systems discussed in operating temperature will govern central boiler-plant de this chapter are thos8 operating with supply water at sign and construction. Some determining considerations are: temperatures exceeding 250 F. Operating temperatures range 1. Type of load: heating, process, or both.
from 250 to 450 F, with pressures from 55 to 450 psig. Hightemperature water systems used in the United States are
2. Distance from heating plant to space or process requiring heat.
predominantly closed-type systems.
3. Terrain of land on which buildings are located.
This chapter is intended to give a broad general idea of . 4. Zoning requirements based on occupancy and load dis
principles and practices that apply to high-temperature tribution.
systems and distinguish these systems from the systems op
6. Quantity of steam used for power equipment, if required.
erating below 250 F.
Variations in elevation may make it desirable to locate the
FEATURES OF SYSTEMS
boiler house on the highest ground in order to obtain maxi
The following are among the outstanding features of high temperature as compared to low temperature systems:
1. It is common practice to use greater temperature drops.
' 2. Supply and return piping may be given the same pitch or grade, or may be run level. Grading is desirable but a definite minimum pitch is not required.
3. Piping may slope up or down or run at a variety of ele vations to suit the terrain and the architectural and structural requirements without provision for drainage at each low point except for emptying sections of piping for shutdown. This fea ture may reduce the excavations required.
4. The pressure in any part of the system must always be above the pressure corresponding to the temperature at satura tion in the system in oraer to prevent flashing of the water into steam.
5. Processes requiring different temperatures of water may be served at their required temperatures by use of heat ex changers, by regulating the flow to certain processes, by plac ing some processes in aeries with others, etc.
6. Heat may be stored in the. mains and boiler by build-up of temperature in the return main during periods of light losa.
mum static pressure head on the system. Boiler auxiliaries such as boiler feed pumps, pressure tanks, economizers, and system circulating pumps are usually located in the boiler house, as indicated in Fig. 2.
DESIGN CONSIDERATIONS
Factors to be considered in selecting the type of boiler are (1) the maximum operating pressure of the system, (2) the water temperature requirements during a 24-hr operat ing period, (3) the sue of the load, and (4) temperature drop aeross the boiler. Process loads may require water at a given minimum supply temperature continuously, while space heat ing and other loads may permit a lower water temperature at night or an off period during each 24-hour operating pe riod.
Theoretically, water temperatures up to about 350 F may be provided using boilers and piping suitable for 125 psig,
THE BASIC SYSTEM
High-temperature water systems are basically similar to the conventional forced hot water heating systems since they require boilers or direct contact heaters for heating the wa ter, expansion or pressurizing tanks, circulating pumps, dis tribution piping, and heat transfer or emission equipment, as shown in Fig. 1. The principal differences from the low tem
but practically, maximum water temperatures will be limited by the system design and elevation characteristics to values between 300 F to 325 F. Most systems are being designed with the system circulating pump in the supply line and with a steam drum for pressurization^ expansion, and tem-
perature system are the higher pressure used, the conse
quently heavier equipment, and the manner in which pres
sure is maintained on the water. When cushioned by steam
in the boiler, the system in effect is a hot water system using
a boiler producing steam to heat the water. The supply piping draws water from the boiler below its water level so
that water flow may occur even though steam is kept above the surface of the water.
Water is circulated in a closed circuit from the central sta
tion to areas where heat is required and back to the boiler.
The size of installation, the extent of the load, and the
421