Document pBdomk7nz2Eg5xo6N3pKjE6k
Heating Ventilating Air Conditioning Guide 1939
difference in temperature between the inside and outside. To determine the total heat
loss, multiply U for each material by the square feet of surface and the temperature difference.
2 Find the .value of U for a 6-in. concrete wall with plaster on metal lath attached to 2-in. furring strips with flanged J^-in. blanket insulation.
0.23 (Table 3, WaU 12L).
3 A wall is built with two layers of ^-in. insulating material spaced 1 in, apart; the air space is lined on one side with bright aluminum foil; mean temperature is 40 F; still air on both sides of wall; h for insulating material is 0.34. Calculate the value of U.
fi = 1.65;/o = 1.65; a = 0.46
R
= _L_ 4- JLL 1.65 0.34
4. _i_ , 0.46 ^
0.34
4. _JL
1.65,
= 6.327
U=
= 0.158
.4 What is the inside surface temperature of a 6-in. solid concrete'wall? Inside airv70 F; outside air, --20 F with 15 mph wind.
The temperature drop from point to point through a wall is directly proportional to the heat resistance.
fi = 1.65; k for concrete. = 12.0;/o = 6.0
Over-all resistance R = -jig- +
^ =1.27 .
...
1
Temperature drop, inside air to surface = 1.65
Temperature drop, air to air
1.27
90
Temperature drop, inside air to surface --
-
= 43
!.*/ X l.oo
70 -- 43 = 27 F, inside surface temperature of wall.
5 How many inches of insulating material having a conductivity of 0.30 would be required, for the wall of Question 4, to.raise the inside surface tem perature to 60 F?
Temperature drop, air to inside surface = 10 F; temperature drop, inside surface to out side air -- 80 F. Therefore, the heat resistance from inside wall surface to outside air
must be right times that from inside air to inside wall surface, or 8 X . 4 = 4.85. The 1.65
resistance for added material is, therefore,
485 - (nf.o + i) =4-19
4.19 X 0.30 -- ,1.25 in. of insulation.
6 An unheated attic space in a residence has an equivalent pitched roof area of 1560 sq ft and a ceiling area of 1200 sq ft. If 15 per cent of the roof area is composed of vertical 'wall spaces having a value of U = 0.52, determine the
-total heat loss per hour through the ceiling and roof for a temperature dif ference of 85 F, if U = 0.46 for the roof and U = 0.38 for the ceiling.
An approximate value of 7 for the roof is equivalent to the summation of coefficients for each individual section times its percentage of total area.
Ur = (0.52 X 0.15) + (0.46 X 0.85) = 0.47.
Ratio of roof area to ceiling = 1560 -s- 1200 = 1.3.
Substituting in Formula 6: -
0.47 X 0.38
0.47 + 0.38 = 0.235 1.3
H = A U (ft - to) = 1200 X 0.235 X 85 = 23,900 Btu per hour.
118
Chapter 6
AIR LEAKAGE
Mature of Air Infiltration, Infiltration Through Walls, Window TLeieaakkaagaee, Dvowor Lea_k__aHgee,atSelection of Wind Velocity, Crack
IR leakage losses are those resulting from the displacement of heated
A air in a building by unheated outside air, the interchange taking Dlace through various apertures in the building, such as cracks around doors and windows, fireplaces and chimneys. This leakage of air must be considered in heating and cooling calculations. (See Chapters 7 and 8.)
NATURE OF AIR INFILTRATION
The natural movement of air through building construction is due to two causes. One is the pressure exerted by the wind; the other is the difference in density of outside and inside air because, of differences in temperature.
The wind causes a pressure to be exerted on one or two sides of a building. As a result, air comes into the building on the windward side through cracks or porous construction, and a similar quantity of air leaves on the leeward side through like openings. In general the resis tance to air movement is similar on the windward to that on the leeward side. This causes a building up of pressure within the building and a lesser air leakage than that experienced in single wall tests as determined in the laboratory. It is assumed that actual building leakages owing to this building up of pressure will be 80 per cent of laboratory test values. While there are cases where this is not true, tests in actual buildings substantiate the factor for the general case. Mechanical ventilating systems are frequently designed to produce positive or negative pressures in an enclosure which are greater or lower than prevalent wind pressures. In such designs, if the rate at which air is specified to be introduced to or removed from the enclosure by positive means exceeds the infiltration rate, it is common practice to use the greater value in determining-the heating capacity to warm the outside air.
The air exchange owing to temperature difference, inside to outside, is not appreciable in low buildings. In tall, single story buildings with openings near the ground level and near the ceiling, this loss must be considered. ' Also in multi-story buildings it is a large item unless the sealing between various floors and rooms is quite perfect. This tempera ture effect is a chimney action, causing air to enter through openings at lower levels and to leave at higher levels.
119