Document pB2LKo2J8zQB12ddkBw7L6B27
308
CHAPTER 12
1952 Guide
- The factor 1076 is defined in list of symbols at Equation 14. (Sensible cooling of the water vapor is included in the factor 1076.)
The only means of preventing moisture transfer is to. use a vapor proof wall, or to apply a special lining, which is vapor proof. All openings in moisture proof construction must be equipped with special gaskets to pre vent entrance of moisture.
JWhen moisture transfer contributes an appreciable part of the latentheat load, it is recommended that estimates should be made intentionally liberal in order to avoid later difficulties with insufficient dehumidifying capacity. Storage spaces, for example, would require sufficient dehumid ifying capacity to handle the moisture brought in with goods to be stored, in addition to moisture leaking in subsequently.
MISCELLANEOUS HEAT LOADS
This designation is intended to cover the various small heat gains from exposed piping, ducts, work done by circulating fan, and unforeseen con tingencies. Where sufficient data are available, these various heat gains may be estimated individually. In the majority of cases, however, common practice is to lump- these factors together and combine them with a safety factor according to the experience and judgment of the estimator. On this basis, a small safety factor is added to the calculated cooling load to com pensate for miscellaneous effects. No'rules can be given for this procedure, as experience in air conditioning is indispensable for application of suitable safety factors.
REQUIRED AIR QUANTITY THROUGH CONDITIONING EQUIPMENT
The procedure for determining the required air quantity is based upon the thermodynamic principles, of Chapter 3 and the use of the A.S.H.V.E. psychrometric chart. Readers are advised to review these principles, paying particular attention to the illustrative examples of cooling load calculations; and to refer to the section on Apparatus Dew-Point in Chap ter 29.
Calculation of the;cooling load for a conditioned space is equivalent to making, for the space, a heat balance in which all heat, moisture, and infil tration are treated as directly entering the space. As explained in the section,- Load from Outside Air, Ventilation, and infiltration, the outside air load normally does not become a part of the space load, because heat and moisture are removed in the air conditioner before this air gets into the conditioned space. The desired conditions are maintained by considering a certain quantity of air to be withdrawn from the space, passed through the conditioning equipment, and returned to the space with such a tem perature and humidity ratio that its net effect will be to counterbalance or remove the given entering amounts of heat and water vapor. This quantity of indoor air, which is considered to be circulated in this manner, is called the required air quantity and its determination is normally part of every cooling load estimate. The procedure is as follows:
1. Determine the total sensible and latent heat loads in Btu per hour for the space.
2. Compute the quantity called the enthalpy-humidity difference ratio (also
referred
to
as
heat-moisture
ratio)
of the
room load,
h - h. W i - BY
Use the equation:
Cooling Load
309
hi -- ft. (Space sensible load + space latent load)
W i -- W, =
Space latent load/1076
!. ''
where
h, = enthalpy of moist air supplied to the space, Btu per pound of dry air.
hi = enthalpy of moist air at room design conditions^ Btu per pound of dry '
` air.
.....
' .humidity ratio of moist air supplied to the space, pounds of vapor per pound
of dry air.)
Wi = humidity ratio of moist air at room design conditions, pounds of vapor
per pound of dry air.
Note that the ratio (space latent load/1076) is the equivalent of the required rate of water vapor removal in pounds per hour. If the rate of water removed is known, it may be used directly in Equation 18.
- 3. Draw a line through the reference point on the A.S.H.V.E. psychrometric chart and the value of (A, -- h,)/(Wi -- .1V,) determined above. Draw a second line through the state point of the room air' (design wet-bulb and dry-bulb temperatures) parallel to this line. This is the condition line for the process.
4. Read the t,emperature where the condition line from step 3 intersects the satura tion line. This is called the apparatus dew-point.
5. Compute the required air quantity from the relation
(Space sensible load) Space \ /Apparatus V]
Coil V
(19)
Kdry-bulb/ \dew-point/J * efficiency /
The magnituderof Qn is substantially the quantity, cfm, of cooled and dehumidified air for which the distribution system must be designed.
The numerical factor 1.08 is derived from the product' 1 cfm X 60 min X 0.244 X
(1----0-'00923X 1-08, assuming an average supply air dew-point of 55 F. Since
standard air density (0.075) includes the weight of the water vapor, it is desirable to reduce it to the basis of dry air by the last factor where 0.00923 = humidity ratio of air at 55 F dew-point, and 0.62 =* ratio of density of water vapor to dry air at same temperature and pressure. Refer to Chapter 35 for coil selection.
Note that the product [(space dry-bulb) -- (apparatus dew-point)] X (coil effi ciency) is equal to the dry-bulb range through which the conditioned air is cooled. Hence, inVare instances when the condition line of the process may not intersect the saturation line, any other convenient reference temperature on the condition line may be used instead, provided that the coil efficiency is specified accordingly on the
proper basis.
MINIMUM ENTERING AIR TEMPERATURE
Due consideration must be given to the temperature of the air entering
the conditioned space in order to prevent objectionable drafts. With ceil-
ing type diffusers or wall grilles with a high aspect ratio (see Chapter 30),
many engineers consider 20 deg as the maximum difference for good design
under average conditions. This difference can only be exceeded with ex
tremely high ceiling outlets or wall grilles. Thus, if 80 F dry-bulb is to be
maintained in a space with average ceiling height, the minimum delivered
air temperature would be limited to about 60 F diy-bulb temperature. If
the'latent heat load is relatively high, it is often necessary to circulate more
air with a higher delivered dry-bulb temperature in order to produce a
thermodynamic balance. If the dry-bulb temperature of the air supplied
to the space is known, the required air quantity can be calcuated from
the formula,
g.:
Qn,
1.08 (ti - O
(20)