Document p7EK3nMQz7K215Q2452V602D
FIRE EXTINGUISHMENT AND CONTROL
When recharging, it is important to use only the dry chemical agent and cartridge
that is recommended by the extinguisher manufacturers
Sodium bicarbonate-base dry chemical, the most common agent, is available in or dinary form and foam compatible form The foam compatible type can be used simul taneously with foam without causing the foam blanket to break down
Potassium bicarbonate-base dry chemical, "purple K," is similar in extinguishing properties to sodium bicarbonate base dry chemical, but it has twice the effective fire fighting capacity on a pound-to-pound basis This agent has good moisture repellency and is compatible with the simultaneous use of water or foam Operator technique is not critical because it does not allow fuel to reflash as easily or as rapidly as sodium bicarbonate The absence of momentary flare-up also permits the user to approach fires more closely Also, the potassium
compound extinguishes the leading edges of contained flammable liquid fires more easily than the sodium compound
Ammonium phosphate-base dry chemical (multipurpose) has operating characteristics on Class B and C fires similar to sodium and potassium base dry chemical extin guishers. When discharged into a Class A fire, chemical reaction will destroy the flames and a coating, formed when the ex tinguishing agent softens and adheres to the burning surface thereby retarding fur ther combustion To obtain complete ex tinguishment on Class A materials, all burn ing areas must be thoroughly exposed to the extinguishing agent Because any small burning ember may be a source of reigmbon, the importance of proper application on Class A fires is more critical than with water extinguishers In the presence of moisture, multipurpose dry chemicals may cause corrosion when discharged on metals.
(Text continues on page 34-28)
Operation Carbon dioxide gas is the propellant for the dry chemical To operate, remove nozzle from holster and press puncturing lever (On some models pull locking ring pm and push charging lever down ) This will release the gas and pressurize the large chamber containing the dry chemical The discharge is controlled by the nozzle on the end of the hose When the fire is out and the extinguisher is no longer needed, invert the container, hold nozzle in the air, and squeeze lever to release all residual pressure
Maintenance. Weigh carbon dioxide cartridge every 6 months, replace if it has lost % oz of the weight stamped on the shell Annually check dry chemical for caking and proper level, cap gaskets for deterioration, hose, nozzle, and siphon tube for obstructaons, and container for physical damage or corrosion
Caution Dry chemical will cake if moisture enters con tainer Never wash out extinguisher or parts with water or other liquid Special models are available for tempera tures below --40 F and above 120 F
fig 34-20. Dry chemlcol fire extinguisher, cortndge operoted.
34-25