Document p2RdzVpqmM4DM9MGOwEwDGQaE

540 CHAPTER 20 1958 Guide this excess pressure would not be so great as the case might be in a one-stage reduction. In making a two-stage reduction, allowance for expansion of steam on the low pressure side of each reducing valve should be made by increasing the pipe area to approximately double the area of a pipe of the size of the reducing valve. This also allows steam flow to be at a more nearly uniform velocity. Separating the valves by a distance up to 20 ft is recommended to reduce excessive hunting action of the first valve. When the reduced pressure is approximately 15 psig or lower, the weight and lever type diaphragm valve is frequently used for moderate steam flows. Above 15 psig, up to 50 psig, spring loaded, direct operated di aphragm valves may be used providing they can pass the required steam flow without an excessive deviation in reduced pressure. Pilot-controlled reducing valves may be used without limitation for all reduced pressure settings for all heating, process, laundry, hot water, etc. services. Pressure equalizing lines must be connected to properly serve the type of valve se lected. For direct-operated diaphragm valves, they should be connected into the bottom of the reduced pressure steam main to allow maximum condensate to exist in the equalizing lines or the connection can be made into the top of the main if a water accumulator is used to reduce the varia tion of the head of water on the diaphragm. Equalizing lines for pilotcontrolled reducing valves employing metal diaphragms should be con nected into the expanded outlet piping approximately 2 to 4 ft from the reducing valve and pitched away from the reducing valve to prevent the accumulation of condensate. Pressure impulse lines for external-pilotcontrolled reducing valves employing compressed air pr fresh water should be installed in accordance with the manufacturer's recommendations. Care should be exercised in selecting the size of a reducing valve. The safest method is to consult the manufacturer. It is essential that sizes of piping to and from the reducing valve be such that they will pass the desired amount of steam with the maximum velocity desired. A common error is to make the size of the reducing valve the same size as that of the service, or outlet pipe size. Generally, this will make the reducing valve oversized, and bring about wire-drawing of valve and seat, due to small lift of the valve seat. On installations where the steam requirements are relatively large and variable in mild weather or reduced demand periods, wire-drawing may occur. To overcome this condition, two reducing valves are installed in parallel, with the sizes selected on a 70 and 30 percent proportion of maximum flow. For example, if 50,000 lb of steam per hour are required, the size of one valve is on the basis of 0.7 X 50,000 lb, or 35,000 lb, and the other on the basis of 0.3 X 50,000 lb, or 15,000 lb. During the mild or reduced demand periods, steam will flow through the smaller valve only. During the remainder of the season, the larger valve is set to control at whatever low pressure is desired, and the smaller one at a somewhat lower pressure. Thus, when steam flow is not at' its maximum, the smaller valve is closed, but it opens automatically when the maximum steam demand occurs, because this maximum demand creates a slight pressure drop in the service line. The installation of reducing valves in pipe lines requires detailed planningThey should be installed to give ease of access for inspection and repair, and wherever possible, with diaphragm downward, except in cases of pilot operated valves. There should be a by-pass around each reducing valve of area equal to Steam Heating Systems 541 one-half the area of reducing valve. The globe valve in a by-pass line should be of a good type of construction, and must shut off absolutely tight. A steam pressure gage, graduated up to the initial pressure, Should be installed on the low. pressure side. Safety valves located on the low pressure side should be set at least 5 psi higher than the reduced pressure where the reduced pressure is under 35 psig and at least 10 psi higher than the reduced pressure if the reduced pressure is above 35 psig or is the first stage reduction of a double reduction. They should be of sufficient capacity and set to relieve the entire output of the reducing valve if the pressure on the equipment should exceed the low pressure setting by 10 percent or more. Strainers should be installed on the inlet of the primary pressure reducing valve and are also desirable before the second stage reduction if there is considerable piping between the two stages. If a two-stage reduction is made, it is well to install a pressure gage immediately before the reducing A-WAKE THIS PIPE SAME SIZE AS BOILER OUTLET aurrLT B-EQUALIZER-OFFSET TO CLEAR FLUE OUTLET AND PERMIT STRAIGHT VERTICAL DROP SHORT NIPPLE AND 90* ELBOW FOR SYSTEMS WITH PUMP RETURNS BOILER RETURN SHUT-OFF GATE VALVE DRAIN FOR COMMON RETURN HEADER BOILER DRAIN CONDENSATE RETURN COMMON RETURN HEADEi "^EQUALIZER OR DRIP _ ^ ^PLUGGED TEE g. 23. Piping Including Hartford Return Connection for Boilers in Battery valve of the second stage reduction for use in setting and checking the operation of the first valve. In all cases it is advisable to install a drip trap between the two reducing valves. Steam BOILER CONNECTIONS ton"aST*rn' sectional heating boilers usually have several outlets in the vp] ` wo. [ more outlets should be used whenever possible to reduce the Drev * f * steam *n the vertical uptakes from the boiler, and thus to of water the steam main. Piping connections to the steam header are shown in Fig. 23. Return sides^whT k^ers are generally provided with return tappings on both tappine m11 boilers are generally equipped with only one return Proper pi W, e.re two tappings are provided, both should be used to effect , rrculation through the boiler. Recommended piping connections