CHAPTER 11
1959 Guide
Table 1 .... Infiltration Through Walls* Expressed in cubic teal per (square fool) (boor)
5 10 15 20 .25 30
Brick Wallb 8H in. Plain Plastered*
2 4 s 12 19 23 0.02 0.04 0.07 0.11 0.16 0.24
Plain 13 in. Plastered*
Plastered*1
1 4 7 12 16 21 0.01 0.01 0.03 0.04 0.07 0.10 0.03 0.10 0.21 0.36 0.53 0.72
Frame Wall, lath and plas- 0.03007 0.13 0.18 0.23 0.26 .ter*
4 The valua liwa in this table are SO percent las then test values to allow tot building up of pressure in rooms, and are based on tot data reported in the paper* listed in chapter footnotes.
b Constructed of porous brick sad lime mortar--workmanship poor. * Two eoste prepared gypsum plaster on brick. 4 Furring, lath, and two coats prepared gypsum plaster on brick. * Wall construction: bevel siding painted or eedar shingles, sheathing, build ing paper, wood lath, and three coats gypsum plaster.
office building, with imperfect sealing of plaster at the base boards of the rooms. With perfect sealing the range is from 0.5 to 2.7 percent; or a practically negligible quantity, which indicates the importance of good workmanship for proper sealing at the baseboard. It will be noted from Table I that the infiltration through properly plastered walls can be neglected.
The value of building paper, when applied between sheathing and shingles, is indicated by curve 3D-7D, Fig. 1, which represents the effect on outside construction only, without lath and plaster. The effectiveness of plaster prop erly applied is no justification for the use of low grade building paper, or of the poor construction of the wall con taining it. Not only is it difficult to secure and maintain the full effectiveness of the plaster, but also it is highly de sirable to have two points of high resistance to air flow with an air space between them. The infiltration indicated in fig. 1 is that determined in the laboratory, and should be multiplied by the factor 0.80 to give proper working values.
Window and Door Leakage
There are two methods of estimating air leakage through window and door cracks, nameiy, (1) the crack method, and (2) the air change method. The crack method is generally regarded as being more accurate than the air change method, provided the variables, such as crack width and clearance, can be properly evaluated.
Crack Method
The crack method is based on known air leakage factors for various types of windows, and widths of crack and clearance. The wind velocity and length of crack are also considered when the crack method is employed. The amount of infiltration for various types of windows is given in Table 2.* The fit of double-hung wood windows is determined by crack and clearance. Crack thickness is equivalent to onehalf the difference between the inside window frame dimen sion and the outside sash width. The difference between the. width of the window frame guide and the sash thickness is
considered as the clearance. The length of the perimeter opening or crack for a double-hung window is equal to three times the width, plus two times lue ueigul, or iu other words, it is the outer sash perimeter length, plus the meeting rail length. All of the window crack in any given room is not necessarily used in estimating the infiltration heat loss by the crack method. The length of crack to be selected in any given case depends on the number of exposed sides, as explained in Chapter 12.
Values of leakage shown in Table 2 for the average double-hung wood window were determined by using, on nine windows tested in the laboratory, the average measured crack and clearance of a large number of windows found in a field survey. In addition, the table gives figures for a poorly fitted window. All of the figures for double-hung wood windows are for the unlocked condition. Just how a window is closed, or fits when it is closed, has considerable influence on the leakage. The leakage will be high if the sash are short, if the meeting rail members are warped, or if the frame and sash are not fitted squarely to each other. It is possible to have a window with approximately, the average crack and clearance that will have a leakage at least double that of the figures shown. Values for the aver age double-bung wood window in Table 2 are considered to be easily obtainable figures, provided the workmanship on the window is good. Should it be known that the windows under consideration are poorly fitted, the larger leakage values should be used. Locking a window generally decreases its leakage, but in some cases may push the meeting rail members apart and increase the leakage. On windows with large clearances, locking will usually reduce the leakage.
Wood casement windows may be assumed to have the same unit leakage as for the average double-hung wood window when property fitted. Locking, a normal operation in the closing of this type of window, maintains the crack at a low- value.
For a metal pivoted sash,, the length of crack is the total perimeter of the movable or ventilating sections. Frame leakage on steel windows may be neglected when they are property grouted with cement mortar into brick work or concrete. When they are not properly sealed, the linear feet of sash section in contact with steel work at mullions should be figured at 25 percent of the values given in Table 2 for industrial pivoted windows.
When storm sash are applied to well fitted windows, some
30-7D: 3-D-I6 tndt dnaglci on I x 4 inch boards on 5 atch center* with paper, 7-0-16 inch rftinytei, dtipiap and paper.
fig. \ .... Infiltration Through Various Types of Shingle Construction
Infiltration and Ventilation
Table 2 .... Infiltration Through Windows Expressed in cubic feet per foot of crock per hour*
141
10 15 20 25 30
Double-Hung Wood Sash Windows (Unlocked)
Around frame in masonry wall--not calkedb...................... Around frame in masonry wall--calkedb.................................. Around frame in wood frame construction*............................. Total for average window, non-weatherstripped, Ms-in.
crack and Ms-in. clearance.* Includes wood frame leakage*1...................................................................... .......................... Ditto, weatherstrippedd.................................................................. Total for poorly fitted window, non-weatherstripped, Ma
3 1 2
7 4
8 2 6
21 13
14 20 27 '35 3 4 56 11 17 23 30
39 59 80 104 24 36 49 63
in. crack and Ms-in. clearance.* Includes wood frame
leakage11..................................................\...................................... 27
69 111 154 199 249
Ditto, weatherstripped*.................................................................. 6 19 34 51 71 92
Double-Hung Metal Windows(
Non-weatherstripped, locked........................................................ Non-weatherstripped, unlocked................................................... Weatherstripped, unlocked-- ...................................................
20 20
6
45 47 19
70 96 125 154 74 104 137 170 32 46 60 76
Kolled Section Steel Sash Windows1
Industrial pivoted, K(-*n- crack*................................................ Architectural projected, Ma-in- crackb...................................... Architectural projected, Ms-in. crackh...................................... Residential casement, Hs-in. crack*...........................................
Heavy casement section, projected, Hs-in. crack*............... Heavy casement section, projected, Ha in- crack*...............
52 15 20 6 14 3 8
108 36 52 18 32 10 24
176 244 304 372 62 86 112 139 88 116 152 182 33 47 60 74 52 76 100 12S 18 26 36 48 38 54 72 92
Hollow Metal. Vertically Pivoted Window'
30 88 145 186 221 242
* The nliM given in this table. with the exception of those far'dwblr-hnni sad hollow metal windows are 20 percent less than tat valua to allow (or building up' proeure in rooms, and are bated on test data, reported in the papers bated tn chapter footnote*.
The valua given for frame leakage ai* per foot of aaab poimeter, as determined lor double-hung wood window*. 8ome of the frame leakage in masonry walla origiuta in the brick wall iteeif, and onnot be prevented by calking. For the additional reason that talking fa not done perfectly and deteriomtea with time, it ia con sidered advisable to ehnoaa the maeonry (tame leakage value* far calked frames a* the average determiima by the calked and non-alked tcate.
* The fit of the average double-hung wood window waa determined aa Ht-in. crack and Ht-in. clearance by measurements on approximately (00 window* hating season conditions.
* The valua given are the totals for the window opening per foot of aafi'perimeter, and include frame leakage and so-called etarwter* Uakoft. The frame tcaka^ valua included are far wood frame eonstrueUon, but apply aa well to masonry construction annulling a SO percent efficiency ci frame *afvg
* A Ha-in. sack and darang represent a poorly fitted window, much poorer than average. 1 Window* tested in place ia building, ao that no reduction from tat valua is Mcesaary, aa mentioned in footnote a.
* Industrial pivoted window generally used in industrial building*. Ventilators horixontally pivoted at center or slightly above, lower part swinging out.
.Architecturally projected made,of urn sections as industrial pivoted, except that outside framing
a heavier, and it has refinemente in weathering and
hardware. Used id aeau-mouumental buildings such as schools. Ventilators awing in or out and are balanced on side arms. Ha-in. mack ia
hi fa the bat preo-
uacs manufacture and installation, H->n. crack eonsideed to represent avenge practice.
`Of **me design and section shapes as so-called kesay stetson eossasraT, but of lighter weight. Ht-in. crack is obtainable fa the bat practice of manufacture and in stallation, Ha-in. crack considered to represent average practice.
Hade of heavy sections. Ventilators awing fa or out and stay set at any degree of opening. Ht-in. crack ia obtainable fa the beat practice of manufacture and in stallation, Hi-in. oack considered to represent average practice. Known as Interntediate Window* by steel window manufacturers.
* With reasonable ore fa installation, leakage at contacts where windows are attached to steel framework and at mullions, is negligible. With H<*in. eraek, representm^poor installation, leakage at Contact with steel framework ia about one third, and at mullions, about one-sixth of that given for industrial pivoted window* fa
reduction in infiltration is secured; the application of the sash provides an air space which reduces the heat trans mission and helps prevent the frosting of the windows* By applying storm sash to poorly fitted windows, a reduction in leakage of 50 percent may be obtained, the effect, so far as air leakage is concerned, being roughly equivalent to that obtained by the installation of weatherstrips.
Door Leakage
Doors vary greatly in fit because of their large size and tendency to warp. For a well fitted door, the leakage values for a poorly fitted double-hung wood window may be used. If poorly fitted, twice this figure should be used. If weatherstripped, the values may be reduced one-half. A single door that is frequently opened, as might be the case in a store, should have a value applied three times that for a well fitted door. This extra allowance is for opening and
closing losses, and is kept from being greater by the fact that doors are not used as much in the coldest and windiest weather.
The infiltration rate through swinging and revolving doors is generally a matter of judgment by the engineer making cooling load determinations. In the absence of adequate re search data, the values given in Table 3 may be used to represent current engineering practice. Some tests of infiltra tion through swinging and revolving doors have been re ported.1 The data in Table 3 are indicative of what might be expected in this connection, but it should be noted that Table 3 is based on a no-wind condition, and therefore is not directly applicable to heating design.
A wide range of infiltration rates would be expected for swinging doors because of variations in the indoor-outdoor
pressure difference caused by wind, temperature differences,
and the degree to which a heating or an air-conditioning