CHAPTER 45
1965 Guide Arid Data Book
Internal equalizer. When the' refrigerant -pressure ' drop'
through a singlecircuit evaporator is equivalent to a 2 F deg-
drop in evaporator temperature,' or less,1 a thermostatic ex
pansion valve having an internal equaliser may be used.'
Internal equalisation amply mptn" that valve outlet pressure
'is transmitted through-an internal'passage to the imHnwHw
of the diaphragm; See Fig. 4. '
The friction-loss in many evaporators'is greater'than the
2 F deg equivalent:Where the pressure drop type refrigerant
distributor is used/the pressure drop across the distributor'
may be as high as 25 to 35 psi, and'the pressure at the outlet
of the expansion* vahrewill'be considerably higher than the'
pressure at the evaporator outlet. As a result, an-internally
equalized valve will control at an abnormally high superheat,
once Pt is a false pressure arid does not reflect the true pres*'
sure in the evaporator. Under these conditions, the evaporator
will not perform efficiently because it is starved for refrigerant.'
Furthermore, -the false pressure is not constant, but varies;
with evaporator load and consequently cannot be1 compen
sated for by adjusting the superheat setting of the valve. '
' External equalizer. In order to avoid the ill effects on sys-'
tern -performance that evaporator or refrigerant distributor-
pressure drop, or both, will produce with an internal equalizer-
valve, a valve having an external equalizer is used/Instead of-
the internal communicating passage shown" in: Fig. 4, an
external connection to the underside of the diaphragm is pro-'
vided. The external equalizer line is connected eithertothe
suction line, as shown in Fig. 9, or into the evaporator at a
point downstream from the major pressure drop,;-thereby.
freeing the operating pressures at the diaphragm-from`any
effect of pressure'drop or of fluctuations in pressure drop,
between the expansion valve outlet and the evaporator outlet/
- Pilot-operated thermostatic expansion voices are; used on
large systems where the capacity required per valve is beyond
the range of the direct-operated type valves.' The < pilot-
operated valve consists of &`piston type pilotroperated regu
lator, which is used as the main 'grpamann valve, and a low-'
capacity thermostatic-expansion valve, which serves as' an*
external'pilot valve.-Tire gnm.ll pilot thermostatic expansion
valve supplies pressure to, or bleeds'pressure from,'the'pistoti
chamber (depending on the regulator design) in response to a-
change in the operating superheat. Pilot operation permits the':
use of a characterized port in the main expansion valve for the'
purpose of providing good modulation over a wide range of
loading. Therefore, the pilot-operated valve performs well
on refrigerating systems having-some form-of compressor
capacity reduction,' such as cylinder tinloading, fig. 10 illus
trates such a control valve applied to a large capacity, direct
MpmwiQi) chiller.
"
- The-auxiliary -pilot controls need only be:sized to handle
the pilot circuit flow; this permits' the use of gmaller controls:
than if full system capacity were to be handled. For example,,
in fig. 10 a small solenoid valve in the pilot circuit, ingte)l*t-
ahead, of. the; thermostatic expansion valve, .converts the
pilot-operated valve into a stop valve.-when the solenoid-
valve is.closed...
;
Application . .
- Hunting of the thermostatic expansion valve is character-'
ized by alternate overfeeding and'starving of the refrigerant:
feed to the evaporator,, thereby producing sustained cyclic:
changes in the pressure and temperature of the refrigerant-'
gas leaving the evaporator.-Extreme hunting reduces the re-,
frigeration system capacity because the mean evaporator;
pressure and temperature are lowered and compressor ca
pacity is thereby'reduced.Tf the overfeeding of-the expansion-
valve results in' intermittent flooding of liquid into the sue-'5
tibn line, the compressor may be damaged eventually, v -
. Although hunting is commonly attributed to the action.ofi
the thermostatic expansion valve, .the valve alone is seldom
responsible..One reason for' the'existence of hunting is'that
all evaporators have an inherent-time lag. When the bulb sig
nals :for- a change in refrigerant flow; the .refrigerant: must!
traverse the entire evaporator before a new gign*l reaches the':
bulb. ThisTag or time lapse may;result in continuous over--
shooting of the valve operation both in the opening-'and*
closing directions. In addition, the thermostatic element has
a time lag due to its mass, which may be in phase with the-
evaporator lag and'amplify the original over-shooting.
' It is often possible to alter the response rate of the thermo^-'
static element by using thermal ballast or.by changing the.
mass'or-heat; capacity of the bulb, thereby introducing, a:
damping action which will effectively. minimize or even
eliminate the original hunt. A change in valve gradient may
accomplish the same result..
--
Extremely high refrigerant .velocity in the evaporator can*'
also cause hunting of the valve. Liquid refrigerant movement'
under these conditions is in the form of waves, or slugs, which-
completely fill a portion-of the evaporator tube' and are
ejected into the suction line. These 'unevaporated slugs chill-'
the bulb and temporarily reduce the feed of the valve, result
ing in intermittent starving of the evaporator.
On multiple circuit evaporators, a lightly loaded or overfed
circuit will also flood out into the suction line, chill the bulb,
and throttle the valve. Again, the effect is intermittent; when
the valve feed is reduced the flooding ceases and the valve
reopens.
Hunting can be minimized or avoided by:
1. Selection of the proper valve.size. Oversized valves gener ally tend to aggravate hunting.
Fig. 10.... PiJot-Operoted Thermostatic Expansion Valve Controlling Liquid Refrigerant Row'to a Direct : " Expansion Chiller ; -
Refrigerant Control Devices
721.
2 the valve adjustment. Lower superheat settings
ufpially (but potalways), tend to increase hunting. 3 {selection ofthe con-ect thermostatic element charge. Cross-
chanced elements have inherent antihunt characteristics. 4. Designing: the evaporator for a short'refrigerant path;
mntont with Bd bcat transfer5 Correct <"mg and arrangement of suction piping.
' <}^Correct location and application of the bulb.
7: Selection of the'best location for the external equalizer line
connection.
"
Bulb location. Clamping the bulb on a horizontal suction
i;nA mVetk the requirements of - most installations! Good
thermal'contact between'the bulb'ahd the'suction line must
be provided. Ideally, the.bulb-should be located reasonably
to the evaporator outlet,' upstream of suction line traps,
and ' nr the evaporator side of any liquid-to-euction heat
exchanger., Certain'installations require increased sensitivity of the
frinv; as a protective measure against floodback.' The bulb,
if it is located in a well in the suction line, has a rapid response
feature because of its intimate .contact with, the refrigerant
stream. The bulb sensitivity can be further increased by. the
use of a smaller bulb.than is normally.supplied-' However, the
use of the smaller,' bulb is limited to gas-onarged valves.
Although the details of refrigerant piping are not the subject
of this chapter, good piping practice has a direct bearing on
expansion valve performance.
fig. 11 illustrates the proper piping arrangement when the
suction line run is located above the evaporator. An oil trap,
as short as'possible, is located downstream from the bulb.'
The vertical riser- or.'risers must be sized to produce a re
frigerant velocity which will assure continuous return of oil to
the compressor. The terminal end of the riser or risers enters
the horizontal run at the top of the suction line; this avoids
interference'from the overfeeding-of any other liquid expanr
eiou .valve, and drain-back during the off-cycle.
.'
A; heavy concentration.of.oil circulated with oilrmiscible"
refrigerants has the effect of elevating their' boiling tempera-'
tures. The response of the thermostatic charge, of the expand,
sion valve, on the other hand, is related to'the'saturation
pressure and temperature of pure refrigerant. In an operating
system, the false pressure-temperature signal* of oil-rich re
frigerants will invariably cause floodback or operating super
heats which are considerably lower tban indicated, and quite
often will cause erratic valve operations. Either the oil pump-
ing rate must be reduced or an effective.oil separator used,-to keep the oil concentration at an acceptable level
' Tlie external equalizer line is ordinarily connected at the evaporator outlet^ as shown in fig. 9. It may also be connected at the evaporator inlet or at any other point in the evaporator downstream of the major pressure drop. On evaporators with long refrigerant circuits having inherent lag, hunting may thus be minimized by changing the point of connection of the external equalizer fine. Where suction line controls such as evaporator pressure regulators are required, one of the alter nate locations of the equalizer may assist in stabilizing the modulation of both valves and prevent one valve from oppos^ ing or bucking the other. However, a compensating superheat adjustment" may be required for the different locations of the' external equalizer line connection. -
The ambient temperature at the valve does not assure' a corresponding temperature of the diaphragm chamber, be cause a certain amount of heat is conducted to -the cooler valve body. It is not unusual for the diaphragm chamber temperature to fall below that of the bulb. When this occurs with a gas-charged valve, the entire thermostatic charge can condense in the diaphragm chamber, and the refrigerant feed can then be controlled from that point. Extreme starving of the evaporator, to the point of complete cessation of feed, is char acteristic of this condition. For this reason, refrigerant dis tributors of the pressure drop type are normally used with gas charged-valves. The pressure drop through the distributor' elevates' the valve body temperature above that of the evapor rator and assists in maintaining control at tire valve bulb.Refrigerant distributors are described in Chapter 34. liquid and liquid cross-charged thermostatic expansion valves will operate regardless of the temperature of the space in'which they are located because of the cross-ambient characteristics of tire charge.
Direct expansion chillers are among the few applications in which gas-charged valves are successfully used without, re^ frigerant distributors. This is possible because of operation at considerably lower superheats and'narrower'ranges of oper ating temperatures than .the other types of direct expansion evaporators. At .these low superheats, usually 4 to 6 F deg/ condensing of the charge in the diaphragm housing can be avoided if proper valve application and installation prac tices are followed.
Flooded System
The application of thermostatic expansion valves to flooded evaporators is rather uncommon. Superheat is neces sary for proper valve control, and only a few degrees of suc tion vapor superheat in a flooded evaporator will incur a sub stantial loss in capacity. If the bulb is installed downstream from a liquid-to-euction heat exchanger, a thermostatic expansion valve can be made to operate on a higher superheat available at this point. Valve control is apt to be rather poor because of the variable rate of heat exchange as flow rates change.
However, valves with modified thermostatic elements are available, in' which electrical heat is supplied to the bulb. The bulb is inserted into the system in direct contact with refrigerant liquid -in the evaporator. Contact of cold re frigerant liquid with the bulb overrides the artificial heat source and throttles the expansion valve. As the liquid falls away from the bulb, the valve feed again increases! Although similar in construction to a thermostatic expansion valve, this, is essentially a liquid level control, modulating type valve.'