Document oM67G5q86pEnmmwp3mEkjRd1R
PYRcCL^oR
FOR TRANSFORMERS
MONSANTO, 10-10 VIOTONU ST., LONDON SW1 MONSANTO, 1 PUOi MADOO, ONUSSEU S
0531962
9
L
TOWOLDMONOQ36390
CONTENTS
INTRODUCTION
Advantages of Pyroolor Transformers Applications of Pyroolor Transformers
PROPERTIES
Composition Physical Properties:
Vlsoosity Solubility of Water Vapour Pressure Air Absorption Chemical Properties: Fire Reslstanoe Thermal Stability and Effeot of Arcing Resistance to Oxidation Stability to Hydrolysis Dielectrlo Properties: Dleleotrlo Strength Permittivity Power Faotor DC Resistivity
DESIGN OF PYROOLOR TRANSFORMERS
Compatibility of Materials Reduotlon in Volume Sealed Transformers Unsealed Transformers Tap Changer Terminals Tank and Lifting Lugs
FILLING PYROOLOR TRANSFORMERS
MAINTENANCE
Sealed Transformers Unsealed Transformers
TOXICITY AND HANDUNO PRECAUTIONS
APPENDIX
3 3 4
o
5 g g g g g g g 6 7 7 7 7 8 3 g
n
17 17 17 is 18 18 16
is
19
19 19
21
22
0531963
TOWOLDMONOQ36391
INTRODUCTION
Pyroclor Is the transformer askorel mode by Monsanto. (Askarels are non-flammable insulating liquids which, if decomposed by an electric arc, evolve only non-explosive gaseous mixtures). Monsanto has been producing askarels in the U.S. since 1932, and in the U.K. since 1951 under the name Pyroclor. This booklet describes the characteristics of askarels, particularly how they differ from mineral oil, and gives Information on the design and operation of askarel transformers. This Information is based on facts gathered by Monsanto from the knowledge and experience of transformer manufacturers and users over three decades.
Advantages Of Pyroolor Transformers For siting Indoors, Pyroclor transformers have considerable advan
tages over other types of transformer. 1 Pyroclor transformers provide the cheapest way of obtaining a fire
proof installation. The use of fire fighting equipment, fire walls, and pebble drains is unnecessary. 2 Pyroclor transformers are particularly suitable in many applica tions where fire risk is great and space is limited, such as near furnaces, and, as In the United States and on the Continent, in coal mines. 3 Pyroclor transformers can be used in dusty and dirty atmospheres without extra protection or frequent outages for maintenance. 4 Pyroclor transformers can be used in installations where over voltages due to lightening or switching surges are prevalent. 5 Pyroclor transformers are quiet in operation. 6 Since Pyroclor transformers can be Installed at the load centre, ex pensive low voltage cable runs are reduced and voltage regulation is improved. 7 The stability of Pyroclor means that it can last at least as long as 30 years even if overloads cause the rated temperature to be exceeded.
3
TOWOLDMONOQ36392
8 Pyroclor transformer installations permit the fire Insurance pre miums to be reduced In some oountries.
9 Pyroclor transformers can operate at voltages as high as 120 kV.
Application of Pyroolor Transformers Pyroclor transformers have been used In a very wide range of appli
cations and recent examples include Installations in steel works, glass factories, public bulldlngB, stores, and offices. The tendency now for buildings to be taller favours the positioning of sub-stations on the top storeys of buildings, and in a recent example Pyroclor transformers were Installed on the 42nd floor of a building in Montreal.
The mining industry employs askarel transformers in America and In France, and elsewhere they have been installed at the load centre in mine winding gear, which is situated over the mine shaft itself.
Askarel transformers are also widely used on electrified railways. On some U.S. railways, where askarel transformers have been used satisfactorily since 1983, the transformers are located below the floor on the Multiple-unit cars. Underground railways in a number of cities have also Installed askarel transformers In their distribution system.
Other reoommended applications include eleotrio furnaces, infra red ovens, oil refineries and ships.
Monsanto itself has some 10 Pyroclor transformers Installed at its various plants. These have so far given satisfactory service for vari ous periods up to 6 years.
Properly designed and installed askarel transformers will give trouble-free service for a minimum of 30 years. 31noe their introduc tion in 1932, the manufacturers report finding the overall failure rate to be less than 0.5 per oent for all units under test and servloe condi tions. The Edison Eleotrloal Institute's report on their memberutili ties publishes the failure rate for askarel transformers as 0.13 per hundred banks per year. Even the rare reports of failure are invari ably found to be due to improper sealing, which allows moisture to enter.
Askarel transformers working at 120 kV have been made, but most work in the region of 11 kV. Units are in servloe with ratings up to 30 MVA, although since they are normally employed only Indoors, the majority are found in the range between 50 KVA and 1.5 MVA.
4 0531965
TOWOLDMONOQ36393
PROPERTIES
Pyroolor was developed for normal operation under claae A condi tions. An alternative askarel, Pyroclor ETR, has been developed for operation under olass B conditions.
The most important properties of Pyroclor and Pyroclor ETR are shown in the table.
OompMltiM Pyroclor is composed of 40% trichlorobenzene and 60% hexaohloro-
diphenyl by weight, with 0.126% of gas scavenger. Pyroclor ETR Is entirely tetrachlorodiphenyl with the same concentration of gas scavenger.
Typloa) properties of Pyroolor and Pyroolor ETR
(These values do not constitute a specification)
Property
Pyroolor
Pyroclor ETR
Description
Viscosity at 80*0 (oS) Pour Point (*C) Relative Density at 15.5/15.6*0 Coefficient ofexpanslon/deg C Specific Heat atT6*C {31% deg 0) Thermal Conductivity at 75*0 (W/mdegC) Evaporation loss (per cent)
Fire Point Refraotlve index dq Inorganic chlorides (ppm) Add number (mg KOH/g) Water content (ppm) Dieleotrlo Strength at 20*0 by B.S. 148:1969 (kV) DC Resistivity at 100*0 and 500V/mm after 1 minute electrification (Q cm) Loss tangent at 100*0 and 50 o/s Permittivity at 100*0 and 50 o/s
LlQuldwhlob. at room temperature, may oontain crystals 2.9 --32 or lower 1.564 0.0007 1.3
Clear, pale straw coloured, viscous liquid
5.8 --7 1.461 0.00070 1.16
0.107 2.5 (6 hat 100*0) None 1.6148 0.1 max. 0.01 max. 30 max
0.1008 0.07 (2 hat 128*0 None 1.6205 0.1 max. 0.01 max. 30 max.
40 min.
40 min.
1.Ox HP'min. 0.08 max. 3.9
I.0xl0"mtn. 0.03 max. 4.6
0531966
?
TOWOLDMONOQ36394
Physical properties Viscosity The ratio of trichlorobenzene to hexachlorodiphenyl in
Pyroolor has been selected to match the viscosity-temperature characteristic of mineral oil. Figure 1 illustrates the similarity.
Solubility of Water Figure 2 shows that water is slightly more soluble in clean Pyroolor than in mineral oil, but there is very little change in the solubility between new and used Pyroolor, as can be seen from the graph.
Vapour Pressure The variation of the vapour pressure of Pyroclor and Pyroclor ETR with temperature is shown in Figure 3.
Air Absorption The amount of gas dissolved in a liquid may be ex pressed as a Bunsen coefficient, that is, the volume of gas at NTP dissolved in unit volume of a liquid at a partial pressure of 760 torr. The Bunsen coefficients for the solution of air in Pyroclor and Pyro clor ETR are shown in Figure 4.
Gbemioal properties The chemical inertness of Pyroclor is outstanding and in particular
it has excellent fire resistance, thermal stability and resistance to oxidation and hydrolysis.
Fire Resistance Although Pyroclor will be shown to have a flash point when examined by the usual laboratory tests, this flash burns with a `cold' flame and no fire is carried baok to the liquid phase, therefore there is no corresponding fire point. The autogenous ignition tem perature of Pyroclor has been measured by dropping small quanti ties of the liquid on to the floor of a ceramic lined muffle furnace. The liquid did not take Are until the surface was a dull red heat, approxi mately 700C. Once the liquid, however, leaves suoh a hot surface it ceases to burn and it is therefore impossible to convey Are by moving streams of liquid. The laboratory of the National Board of Under writers (U.S.A.) have carried out stringenttests onthe fire resistance of this type of liquid and have concluded that it is essentially non flammable.
Thermal Stability and Effect of Arcing Pyroclor undergoes no thermal decomposition whatsoever at temperatures below 176C. If Pyroclor is raised above this temperature by, for example, local over-beating or transient arcing, small quantities of hydrogen chloride are pro duced. The gas scavenger, absorbs this hydrogen ohloride and pre vents attaok on the iron oore or the cellulosio insulation.
If a major internal fault ocours in a Pyroclor transformer which results in a sustained arc below the Pyroclor surface, then the high temperature of the arc will decompose the Pyroolor. The main de-
0531967
TOWOLDMONOQ36395
composition products are carbon and hydrogen chloride. Hydrogen chloride is non-flammable and will not form explosive mixtures with air, but is an unpleasant and irritating gaa to breathe. However, it is easily detected in the atmosphere and exposure to low concentra tions would produce no lasting ill-effects. Since it is very readily soluble in water, it Is likely to be removed rapidly from the atmo sphere under most normal circumstances. Hydrogen chloride does not quench the arc that produces it, and consequently the circuit breakers should be capable of interrupting the probable fault cur rent. For the same reason, Pyroclor is unsuitable for switchgear. The amount of gas that is produced by an arc in Pyroclor will vary according to the circumstances, but a figure quoted is 136 cm* per kWs.
Laboratory tests and practical experience have shown that phosgene and chlorine are not formed as decomposition products ofaskarel.
Resistance to Oxidation Pyroclor has exceptionally good resistance to attack by oxygen. When subjected to a bomb test at 140C in oxygen at a pressure of 250 pslg. (17 kg/cm*) there was no evidence of oxidation as judged by development of acidity or the formation of sludge. Hot mineral oil in the presence of oxygen undergoes a series of complex chemical reactions, producing by stages, peroxides, acids, water and other condensationproducts which eventually form a sludge.
Stability to Hydrolysis Pyroclor is resistant to attack by water, although water will dissolve in Pyroclor and the presence of this mixture will naturally affeot the electrical properties. In an experi ment, Pyroclor was refluxed with water and oxygen was passed through the mixture and at the end of the experiment no free chlorides were generated, even after extending the time over a con siderable period. A further experiment was conducted whereby the liquid was sealed in a glass capsule with water and heated for many hours at 150C, and once again no chloride formation could be deteoted.
Dlelsotrio prtpsrtlM Although a transformer liquid is principally a coolant, it must also act as an insulation in and between the windings of the transformer, and the dlelectrlo properties are therefore of great importance.
Dielectric Strength The dleleotric strength ofPyroclor is equal to the best quality mineral oil and has the dleleotric qualities required for the voltage stresses encountered in transformers over the entire temperature range of operation. Figure 5 shows the variation of the dielectric strength of Pyroclor (measured according to B.S.148:1959) with temperature.
053196b
TOWOLDMONOQ36396
At low temperatures the eras scavenger has a tendency to crystallise and exhaustive tests have shown that even with samples of Pyroclor contalniner large Quantities of suspended crystals, the dielectric strength of the liquid is not affected and there is no alignment of the crystals between the electrodes. Permittivity The permittivity of Pyroclor is much closer to the per mittivity of cellulose and this leads to a greater uniformity of stress in Impregnated press board. The variation in the permittivity of Pyroclor at 50 c/s is shown in Figure 6. Lose Tangent The variation of the loss tangent at 50 c/s of new Pyro clor with temperature is shown in Figure 7. Satisfactory Pyroclor in a transformer may be expected to have considerably higher loss tangent than new material, in the range 0.2 to 0.8 at 100C. D.C. Resistivity The variation of the d.c. resistivity of new Pyroclor with temperature Is shown in Figure 8. These readings were made one minute after the application of a stress of 500 V/mm. Satis factory Pyroclor sampled from a transformer may have a d.c. resistivity as low as 2.5 x 10,#o cm. at 100C. D.O, Resistivity of Pyroclor is thus seen to be much lower than that of mineral oil by comparison. This Inevitably leads to lower Insula tion resistance on finished transformers filled with Pyroclor than on their counterparts filled with oil. This is, however, quite normal and Is an accepted characteristic of Pyroolor transformers.
0& 31969
TOWOLDMON0036397
K IN E M A TIC VISCOSITY (<S )
EEHfElumE (C>
Fl|r 1 Tin vtoanHjr-MMlMntir* okanotiHitiM *f Pyroolcr, Pynoter IT* art mlaaral alL
0531970
9
TOWOLDMONOQ36398
WATER IN SOLUTION ( p p m )
Figure l The eolnhllltr ef water la Fyrooler tad aaw niaeral ell. 10
0S31971
TOWOLDMONOQ36399
TOWOLDMON0036400
0-10-
BUNSEN COEFFICIENT
Flgnro 4 Tho air absorption of Pyroelor and Pyrooior ETR. 12
0531973
TOWOLDMON0036401
TOWOLDMONOQ36402
Flgoro Th varlatlta if tho (Mrmlttlvlty of Fyroofor wltk tomporatiiro.. 14
0531975
TOWOLDMONOQ36403
Figaro 7 Tha vaHatioa of tha laas tangaat of now Pyraolar with tamparatara. 0531976
15
TOWOLDMONOQ36404
ISO1
Figrn ( Tkt nrlitloa f tha 4.0. mtethrtty of mw Pyroelor wltk tinparattr*. 16
0531977
TOWOLDMONOQ36405
DESIGN OF PYROCLOR TRANSFORMERS
Compatibility of matorlalo Since Pyroclor is a mixture of chlorinated hydrocarbons, it is a
plasticizer for a variety of resins and plastics normally used in the
construction of mineral oil transformers. If any of these materials
are polar, they ionise to a greater extent in Pyroclor than in mineral
oil because of the greater permittivity of Pyroclor and so increase
the dlelectrio losses more. For these reasons special attention must
be given to the selection of materials which will be suitable for use
with Pyroclor.
. '
-^ /
r ,
Pyroclor is a more searching liquid than mineral oil, so we do not recom
mend that the oil filling of existing transformers be replaced by Pyroclor
as this would be very likely to cause extensive leaking and, in many
cases, a breakdown due to the attack on insulating materials.
__ --<
A very large number of materials has been examined for their suit ability for use with Pyroclor, and lists of tested materials are avail able. Further information can be obtained from Monsanto.
Raiaotlaa la vtlams For successful transformer design using Pyroclor it is desirable to
keep the liquid volume to a minimum because it is more costly than
oil. Even without radical re-design, useful economies can be made by
rounding the oomers of the
or by using tanks with cruciform
shape. Considerable economy oan be made by filling dead space with
wood or even glass marbles. The wood, however, must be of low resin
content a-M must be thoroughly dried. In addition, cooling tubes
having oval or star-shaped cross-sections can be used to cut the
volume.
Sealed traasferiaere Transformers using Pyroclor are normally hermetically sealed,
since as Pyroclor transformers do not require any maintenance, possible ingress of moisture is eliminated. Welded tank designs have become popular with Pyroolor transformers. Another special fea ture with hermetically sealed Pyroclor transformers is the so-called `top hat* type of construction with an air or nitrogen filled space
0531978
17
TOWOLDMONOQ36406
< ' {7 {> / '' ; -( :a-
which is used to allow for expansion of the fluid. The sealing Is fre quently so arranged that the gas is under a slight negative pressure when cold. With hermetically sealed units it Is customary to make provision for a rupturable relief diaphragm which can be vented to the outside atmosphere.
Unsealed transformers Pyroclor transformers fitted with breathers are also made. The
breather should be fitted with a silica gel moisture trap to prevent Ingress of moisture with expansion and contraction following heat cycles of the transformer. The conservator Is recommended with breather designs, since at maximum operating temperatures the tri chlorobenzene present has a relatively high vapour pressure and the conservator will prevent losses by evaporation. An alternative Is to fit the breather on to the end of a section of vertical tube which will act as an air condenserfor the Pyroclor vapour. If a Bucholz relay Is fitted. It should be suitable for use with Pyroclor.
Tap ohaagar Since Pyroclor Is unsuitable for switchgear, on-load tap changing
below the liquid surface Is not adopted. It Is usual to Incorporate some form of Interlook to prevent this.
Terminals Because water floats on the surtaoe of Pyroclor. the terminal con
nections should preferably be brought through the side walls of the tank, below the surface. If connections have to pass through the liquid surfaoe, they should be enoased in suitable sleeving to prevent the possibility of a flashover arising from surface moisture.
Taak aad lifting lap Since Pyroolor le nearly twice as dense as mineral oil, these items
must be sufficiently robust.
FILLING PYROCLOR TRANSFORMERS
Pyroclor as reoelved, either In drums or In bulk, le ready for filling the transformer directly. Care should be taken to carry out the fill ing as quickly as possible Indoors, and days when the hur.dity le high should be avoided. If the drums have been exposed to low tern18
0531979
Ctf*' r, >r-
peratures, the gras scavenger may have crystallised, but this will re* dissolve when the temperature of the tranaformerrleee, to It la only neoessary to agitate the drama to ensure that the oryetala are washedinto the tank. Alternatively, the oryetalamay be re-dlseolved by pre-heating the drums to approximately 60*0.
Vacuum impregnation of tranaformer windings can be oarrled out with Pyroclor, but unless precautions are taken the volatile trlchlorobenzene Is likely to esoape. This can be avoided by using a trap In the vacuum line or alternatively the vlsooslty of the Pyroclor can be brought baok to normal after the impregnation prooese by adding fresh triohlorobenzene.
A table for converting volumes to weights Is given In the Appendix.
MAINTENANCE
tealed transformers A properly designed sealed Pyroclor tranaformer requires no
maintenance.
Hassalad transformers Pyroclor and oil are two different chemical substanoes and the con
dition of Pyroclor should be Judged only on the basis of dleleotrlo strength, appearanoe and water content. High loss tangent and low d.o. resistivity In used Pyroclor la to be expected; these values are not an indication ofchemical or electxioal breakdown.
New Pyroclor has a minimnm dielectrio strength of 40 kV at 25C, and amaximum moisture content of90ppm. Ifthe dleleotrlo strength decreases significantly this Indicates moisture plok-up, arcing or both. When the dielectric strength hasfallen below40 kV, an analysis for water is necessary. If water is found In exoess of 100 ppm, its source should be located and corrections made.
When the moisture oontent approaches 125 ppm (saturation level) the dielectric strength of Pyroclor drops below the value required for efficient Insulating. The moisture content should not be allowed to rise over 70 ppm; It should be held as near as possible to 30 ppm. Maintaining % low moisture level will ensure high dleleotrlo strength and top operating efficiency.
0531980
2
TOWOLDMONOQ36408
The oolour of need Pyrodor is a useful guide to ite condition. In a properly designed transformer the Pyroclor retains its original pale straw oolourthroughout its life. A blue, green, orred oast shows that extraction from the other internal materials is occurring, but this is not necessarily a hazard unless the dielectric strength also fails, or this phenomenon Is accompanied by leakage. If the Pyrodor Is dark brown or black, and if black particles of oarbon are seen and the dielectric strength Is low, then arcing has been occurring and Immediate action must be taken. The development of turbidity lndloatee contamination from water, Insulation particles, metallic dust, or dirt. Care must be taken, however, to distinguish this from the preoipltatlon of the scavenger that occurs at low temperatures. High dielectric strength Indicates that any turbidity present Is not water, and that the insulating efilolenoy of the Pyroolor Is still exoellent.
Mineral oil is soluble In Pyrodor and any contamination of the Pyrodor by oil will reduoe its fire resistance. A ma-rtmnm hydro carbon oontent of 2% by volume oan be tolerated, however, but it is reoommended that Pyroolor transformers should never be topped up with mineral oil.
Dissolved water oan be removed from Pyroolor with a filter press. Before use, the filter paper should be dried In an oven at 110*C for 3 to 4 hoars. The Pyrodor Is preferably circulated hot, 66 to 60*0, through the filter. If water Is present as a separate phase, It should be first removed by separation.
When oonneotlng a filtration plant to a transformer, the dirty Pyro dor should be drawn off from near the top of the tank, pumped through the plant, and then returned to the transformer through the bottom drain valve.
7 Ifarcing has oocurred, as shown by the presenoe of carbon, It Is often
possible to restore the eleotrloal properties of the Pyrodor by treat
ment with activated alumina. Peter Spenoe Alumina A 300 is reoom
mended for this purpose. It should be aotivated by
to 100*C
for two hours and then added to the Pyrodor In the proportion of
0.06% by weight. (A volume to weight conversion table Is given In the
appendix.) The mixture is stirred for 2.6 hours at 60 to 60*0 and then
filtered through either a filter press, an edge filter, or a filter with a
built-up bed. Only the latter Is likely to remove oolloldal carbon.
After treatment the unreaoted gasscavenger oontentofthe Pyrodor should be tested by the method of ASTM D1701 - 69T. If necessary, additional gas scavenger should be added to restore the original oontent.
4 ^
TOWOLDMONOQ36409
TOXICITY AND HANDLING PRECAUTIONS
Askarela made by Monsanto have been oaed for over 30 years without causing any toxic effects, but they must be handled with care.
These precautions should be observed:
1 Avoid skin contact. Protect the hands, preferably by oil-resistant gloves or, for short oontact, by using a barrier cream.
2 If skin oontact should occur, wash off with soap and water.
3 If hot askarel must be handled in a dosed or confined area, provide exhaust ventilation or wear an approved respirator.
4 If askarel gets in the eyes, flush with large amounts of water. In the event that Irritation persists, refer the patient to a physician.
^jnfroq>uqu' ent exposure}o askarel vapours will not oause ^ any Hl-efTeclsTbutprolonged exposure to a high vapour """ concentration should be avoided.
Neglect of these precautions may oause acne and may ^, lead to liver damage.
0531982
21
2
TOWOLDMONOQ36410
APPENDIX
Packaging Pyroclor is. at present, packaged in steel drums containing 6001b. (272 kg) by weight, or 38.3 UKgal (174 litres) at 15.56C by volume. Pyroclor ETR is similarly packaged, but these drums contain a volume of 41.0 UKgal (186 litres) at 15.5C.
Volume to weight conversion tablet Pyrodw These tables are based on the density of Pyroclor at 15.5"C:
15.67 lb/UKgal 1.563 kg/litre Weight in pounds
UKgal
0
20 40 60
80
0 313
100 1567 1880
200 3134 3447
300 4701 5014
400 6268 6581
500 7535 8148
600 9402 9715
700
10969
11282
800
12536
12849
900
14103
14416
Weight in kilogrammes
Litres
0
100
627 2193 3761 5328 6895 8462 10029 11596 13163 14730
200
940 2507 4074 5641 7208 8775 10342 11909 13476 15043
1254 2821 4388 5955 7522 9089 10656 12223 13790 15357
300 400
0 156 313 469 625 1000 1563 1719 1876 2032 2188 2000 3126 3282 3439 3595 3751 3000 4689 4845 5002 5158 5314 4000 6252 6408 6565 6721 6877
Litres
500
600
700
800 900
0 782 938 1094 1250 1407 1000 2345 2501 2657 2813 2970 2000 3908 4064 4220 4376 4533 3000 5471 5627 5783 5939 6096 4000 7034 7190 7346 7502 7659
22
0531983
TOWOLDMONOQ36411
Pjroolor ETR These tables are based on the density of Pyroclor ETR at 15.5'C:
14.63 lb/UKgal 1.460 kg/litre Weight In pounds
UKff&l
0
20 40 60 80
0_
293
100
1463
1756
200
9226
3219
300
4389
4682
400
5862
6145
500
7315
7608
600
8778
9071
700
10241
10534
800
11704
11997
900
13167
13460
Weight In kilogrammes
585 2048 3511 4974 6437 7900 9363 10826 12289 13762
878 2341 3804 5267 6730 8193 9656 11119 12582 14045
1170 2633 4096 5559 7022 8485 OSAQWifl 11411 12874 14337
Litres
0
100 200 300 400
0 1000 2000 3000 4000
Litres
_
1460 2920 4380 5840
500
146 1606 3066 4526 5986
600
292 1752 3212 4672 6132
700
438 1896 3358 4818 6278
800
584 2044 3604 4964 6424
900
0 1000 2000 3000 4000
730 2190 3650 5110 6570
878 2336 3796 5256 6716
1022 2482 3942 5402 6882
1168 2628 4088 5548 7008
1314 2774 4234 5694 7154
083148a
TOWOLDMONOQ36412
TmJmImI Stnrlo*
The teohnioal service staff of Monsanto Is always ready to provide additional informa tion on the ose of the materials Indicated In this report, and to assist manufacturers in the solution of particular problems ensuing from their application.
Front cover illustration A 600 KVA, 3 phase, 50 oyole, ground mounting transformer with a voltage ratio of 11,000/416 volts. This Pyroolor filled transformer was ordered for installation in the Royal Palaoe at Baghdad.
Every effort has been made to ensure that the information in this publication is reliable, but as the conditions under which it may be applied are beyond our control, we cannot accept responsibility for any results of its use.
Form* No. 114 (B) M-B (11/68)4
Published by Monsanto Chemicals Limited
Printed in
by J. D. Oarrod Ltd.. London. 8..16
0531985
TOWOLDMONOQ36413