pyrocLor
MR RESISTANT II
.
TRANSFORMER COOLANT BY |f|0nS3nt0
The information contained in this publication is, to our best knowledge, accurate; but all recommendations or suggestions are made without guarantee, since the con ditions of use are beyond our control. Monsanto Company, its subsidiaries, associates and affiliates disclaim any liability for loss or damage incurred in connection with the use of the following material. Moreover, nothing contained herein is to be construed as a recommendation to use any product in conflict with any patent.
The information, recommendations and suggestions made herein are offered in the light of prevailing legislation and on the basis of present scientific information (1972) avail able to Monsanto.
Monsanto Chemicals Limited 10-18 Victoria Street London SWIH ONQ Telephone: 01-222 5678 Telex: 916093
Monsanto Europe S.A. Place Madou, I B-1030, Brussels, Belgium Telephone: (02) 19.11.01 Telex: 22110/21986
TOWOLDMONOQ22279
1. INI ROIM CIION HISTORY OF PYROC'LOR
2. CSES OF PYROri.OR-FII.I.KI) TRANSFORMERS
Automotive Industry................................................... Aviation Industry......................................................... Chemical Industry....................................................... Electricity Generating Boards................................... Engineering Industry................................................... Exhibitions................................................................... Gas Boards................................................................... General Post Office..................................................... Glass Industry............................................................... Multi-storey Buildings................................................. National Coal Board................................................... Oil Industry................................................................... Rubber Industry........................................................... Steel Industry............................................................... Television.......................................................................
7 10 12 14 18 20 22 26 28 30 33 34 36 38 40
3. ADVANTAGES OF PYROC l,OR-FIIJ.F.I> TRANSFORMERS
Fire Resistance............................................................. No Fire Precautions..................................................... No Siting Limitations................................................. Freedom from Contamination.................................... Over-Voltages............................................................... Low Noise Levels......................................................... Low Power Loss........................................................... High Impulse Level..................................................... No Maintenance........................................................... Ideal for Package Substations................................... Lower Insurance Premiums....................................... Summary of Main Benefits .......................................
43 43 43 43 43 43 44 45 45 45 45 45
4. C OST SAYING WITH PYROC I.OR-FN EKI) TRANSFORMERS
Installation Cost Comparison................................... Maintenance Cost Comparison.................................. Examples of Cost Savings:
Example 1................................................................. Example II............................................................... Example HI.............................................................
47 47
48 52 56
TOWOLDMONOQ22280
5. TYPICAL PHYSICAL PKOPKKTIKS OFPYROCLOR
Viscosity............................................................................. Density............................................................................... Solubility of Water............................................................ Vapour Pressure................................................................ Water Absorption............................................................ Gas Absorption................................................................ Stability (Corrosion) Test............................................
62 62 62
62 62 63 63
CHEMICAL PROPERTIES
Fire Resistance.................................................................. Thermal Stability.............................................................. Resistance to Oxidation.................................................. Stability to Hydrolysis......................................................
64 64 64 64
DIELECTRIC PROPERTIES
Dielectric Strength............................................................ Permittivity........................................................................ Loss Tangent...................................................................... D.C. Resistivity.....................................................
6. PYROCLOR-F1LLED TRANSFORMERS IN OPERATION
Effect of Temperature...................................................... Fire Resistance.................................................................. Transient Arcing and Pressure Build-up........................ The Effect of Time............................................................ External Contamination.................................................. Weight of Pyroclor-Filled Transformers...................... Transformer Faults:
Leaks............................................................................. Major Faults................................................................ Regulations and Codes for Practice for Indoor Transformer Installations............................................
65 65 65
66 66 67 67 68 68
68 68
69
7. FLUID C HEC KS
L Sealed Transformers............................................... 2. Unsealed Transformers.......................................
Sampling Procedure.....................................................
70 70
71
65
1. Appearance............................................................. 2. Dielectric Strength.................................................. 3. Moisture Content................................................... 4. Loss Tangent............................................................ Reclamation.................................................................
8. DESIGN OF PYROCLOR-FILLED TRANSFORMERS
Compatibility of Construction Materials.................. Coolant Volume............................................................ Hermetically Sealed Units............................................ Tap Changers............................................................... Terminal Entry..............................................................
71 7| 71 72 72
74 75 75 75 75
9. STORAGE, HANDLING AND DISPOSAL OF PYROCLOR
Drums ......................................................
76
Bulk...................................................................................... ?6
Handling Precautions.................................................. 77
Disposal ofempty drums and waste Pyroclor .......... 77
10. GLOSSARY OF TERMS
79
0102B17 3
TOWOLDMONOQ22281
1
Introduction History of Pyroclor
Over forty years ago electrical engineers expressed the need for a synthetic electrical insulating fluid to replace mineral oil for transformer installations where fire was a particular hazard. The new fluid had to be as good as mineral oil in every respect, in terms of electrical insulation properties and performance under working conditions. But it had to be fire-resistant.
This new synthetic transfoimer fluid was termed an "askarel" and like all chemical innovations underwent an initial period of acceptance. But gradually the askarel proved itself and its use is now widespread. In Europe askarel transformers form a large percentage of the distribution transformers installed today. In France, one-third of the distribution transformers brought into service each year are of the askarel type.
The first askarel fluid was produced by Monsanto in 1932 and was the ideal solution to many engineering problems. It meant that transformers could be placed indoors exactly where the electrical engineer wanted in his distribution system, at the load centre. Askarel-
4
filled transformers could be sited in confined spaces and no maintenance would be required.
Askarel is a generic term for a group of fire-resistant products used as electrical insulating media.
Monsanto manufactures transformer askarel at their Newport, Monmouthshire, plant and the fluid is known as Pyroclor.
The purpose of this book is to enable both transformer manufacturers and transformer users to better under stand the many benefits of Pyroclor in modem industry and to answer many of the questions which are still asked about transformer askarel.
An international specification for transformer askarels has been drafted and is being reviewed by the competent authorities of the various countries involved. It is intended that this international specification will form the basis of a British Standard. Manufacturers are assured that Pyroclor will meet or exceed this British Standard specification.
0102818
TOWOLDMONOQ22282
Pyroclor contains Polychlorinated Biphenyls (PCB's) which some studies have shown may be persistent, an environmental contaminant and, possibly, injurious to certain forms of bird, aquatic and animal life.
However, the need for the safety and reliability pro vided by askaret-filled transformers, coupled with the fact that they are designed to be leakproof has enabled the continued use of PCB's in this application.
Two organisations in the electrical industry:--American National Standards Institute (Committee C-I07) and C.I.G.R.E. (Study Committee No. 15 working group 02) are working to produce documents setting out guidelines/codes of good practice for the use of PCB askarels in electrical equipment.
A typical 1250 k Va 33(X)j433 Volts sealed Pyrochr-filled transformer.
0102819
5
TOWOLDMONOQ22283
2
Uses of Pyroclor-filled Transformers
Pyroclor-filled transformers have been used in a very wide range of applications including installations in steel works, glass factories, airports, public buildings, offices and shops. In high rise buildings, Pyroclor-filled transformers have been installed several stories up or even on the roof, thereby saving valuable architectural space in overcrowded conurbations. In railways, ships,
6
coal mines, oil refineries and chemical plants Pyroclorfilled transformers have provided fire safe installations, protecting both personnel and property.
Here, together with photographs, are a number of cases where Pyroclor-filled transformers are used by well known companies in many different industries.
TOWOLDMONOQ22284
Automotive Industry
Fifty-three Pyroclor-filled Transformers on Motor Company Rooftops
Pyroclor-filled transformers solved a factory planning problem for the Ford Motor Co. Ltd. new tractor produc tion plant at Basildon, Essex.
Although the plant covers 800,000 square feet the planners ruled that, in order to permit maximum flexibility in pro duction layout, there should be no permanent obstructions in the floor area. This meant that the many transformers required to supply the manufacturing and assembly oper ations could not be placed inside the building at floor level. Owing to the immense size of the building, transformers sited externally would have meant long runs of expensive low-voltage cables to connect with the many load centres required. The obvious place was the roof.
But conventional transformers in this location would have meant an unacceptable fire risk--not so much from the
possibility of a transformer itself starting a fire, but from the likelihood of it becoming involved in an extraneous blaze and its fluid carrying the fire to other parts of the building. Modern single-storey open-plan factories in fact constitute a major fire hazard since there are no solid walls to prevent the lateral spread of flames and smoke.
Nevertheless, the roof had undeniable attractions and Ford decided to carry on with the scheme using U Pyroclorfilled fire-resistant transformers.
In addition, 18 Pyroclor-filled transformers are sited at the Ford Motor Co. Ltd., Dagenham, works and 14 at the new car assembly plant at Halewood. All transformers are on the roof, so too are the 10 units at the Caterpillar Tractor Co. plant at Glasgow.
7
102 ft
^ O -*
TOWOLDMONOQ22285
Roof installation--Two Pyroclor-filled fire-resistant trans formers are installed on the flat roof of the Ford Motor Co. Ltd., Basildon Works, with a light enclosure around them, fn the event of a fire in the factory below there is no risk of the transformer cooling fluid spreading the blaze.
0102820
TOWOLDMONOQ22286
Pyroclor-filled transformers are supplying all power requirements at VauxhaU Motors' new 700 acre vehicle proving ground near Lidlington, Bedfordshire.
TOWOLDMONOQ22287
Aviation Industry
Britain's First Jumbo Jet Hangar Powered by Transformers
Two 1.5 MVA transformers filled with Pyroclor are sup plying all power requirements to Britain's first Boeing 747 hangar at Heathrow Airport, London.
Among unique features powered from the transformers are six sliding glass doors each 75 square feet and weighing 45 tons and an air conditioning system that blasts down an invisible curtain of hot air to bring the hangar temperature up to a comfortable 20' C (65 F) within 15 minutes of the doors closing, even in the coldest weather.
Besides natural light from a glass roof, a blended installation of 283 mercury and sodium lamps will provide pleasant working light for technicians maintaining the giant jets.
For servicing, aircraft will be towed into the hangar nose first and manoeuvred into a specially contoured steel mezzanine floor 16 feet above ground. This will allow access to wings, engines and forward fuselage. (In conventional hangars, movable steps and gantries arc used.)
Another innovation powered via the transformers is the system for maintaining undercarriages. Normally, an aircraft has to be lifted up with jacks before the wheels can be moved, but in the new Hangar 01 the aircraft will remain on its normal level while the floor beneath the wheels is lowered to make inspection pits.
The periphery of the hangar, housing all ancillary buildings within 4-storey structures, will also receive all power require ments from the two transformers.
TOWOLDMONOQ22288
And whilst performing these many tasks, the Pyrodorfilled transformers will not require maintenance for at least 25 years. They were chosen because of safety, space and cost factors. Several hundreds of pounds a year will be saved because fire precautions are unnecessary and the transformers are load-centred, bringing further economies in installation layout.
The units are sited in a small transformer house in a corner of the Hangar and breakers of 800 amps feed into a bus bar circling the hangar's mezzanine floor with tap off points every two feet.
Right.--A 1000 k VA Pyroclor-fitled transformer is installedat the Westland Aircraft Ltdfactory in Yeovil, Somerset. To save space the transformer is located in the roof over a busy machine shop.
Below.--The new Jumbo Jet Hangar at Heathrow Airport, London. {Photo: courtesy Holland & Hannen & Cubitts (Southern) Ltd., and B.O.A.C.)
0102823
TOWOLDMONOQ22289
Chemical Industry
Low-Voltage Power Supply at Chemical Processing Plants
Some chemical processes involve the use of highly inflam mable base materials. Large amounts of electric power may also be required, and the provision of suitable low voltage supplies under flameproofconditions can present problems.
At the Coleraine works of Monsanto Textiles Ltd., where Acrilan fibre is made, the necessary power is obtained from 8 x 1000 kVA (11 kV/415 V) and 6 x 500 kVA (I I kV/415 V) transformers. Four of the main distribution sub-stations are located in the main factory building. This location was made possible by the choice of Pyroclor-filled transformers which have reduced both installation and running costs.
At Baglan Bay, where Forth Chemicals Ltd. manufacture styrene monomer, the whole factory compound has been declared a flameproof area; consequently the 4 x 500 kVA transformers which supply the works are Pyroclor-filled even though they are sited out of doors. Similarly three 800 kVA and one 1500 kVA (II kV/3.3 kV) and two 100 kVA (II kV/415 V) transformers for the Monsanto poly ethylene plant at Fawley have been located adjacent to the buildings involving ethylene processing.
In neither of these cases would it have been economical to use dry transformers, since these would have required protection from wind-blown dust and driving rain. 12
010282*
TOWOLDMONOQ22290
PyrocIor-fiHed transformers have reduced installation and maintenance costs at Monsanto Textiles Ltd., plant, Coleraine, N. Ireland.
TOWOLDMONOQ22291
Electricity Generating Boards
Almost Twenty-Five Years Service in Electricity Generating Stations
The oldest transformers in Britain using Pyroclor are at Trafford, Manchester, power station of the Central Electri city Generating Board. Installed in a basement there as long ago as 1941, thev are still in service. The units are of 500 and 800 kVA. More recently, Pyroclor-filled transformers have gone into the San Esteban and Mallorca power stations in Spain, and in India, transformers of this type form part of the huge Damador Valley development in West Bengal, at the Bokara and Durgapur steam power stations. 14
0102626
Installed in 1941 and still in service--
Pyroclor-fiUed transformers at Trafford Generating Station, Manchester
0102817
TOWOLDMONOQ22293
Pyroclor in "Excellent" Condition after 30 Years Service !
For 30 years two 1000 kVA transformers have been working in the sub-basement of the Birmingham Civic Centre, built before the war as the Town Hall. One of the transformers was taken out of service, because of re-development and re distribution of load and it became possible to do a thorough examination of the Pyroclor fluid.
Samples of Pyroclor were taken from the top and bottom of the transformer and tested at Monsanto Technical Service Laboratories for electrical, physical and chemical properties. Results prove that Pyroclor is still in excellent condition and there is no evidence of decomposition after three decades of service.
Dielectric tests in accordance with BS 148:1959 (4 mm gap) showed that there was no breakdown of the fluid up to 90 kV. Modem transformers, unlike the one tested, are often hermetically sealed to prevent contamination by water. But tests on this unsealed transformer showed that the water content was only 52 ppm, substantially below the maximum level when drying out of Pyroclor is recomm ended.
Low acidity, low inorganic chloride content and the absence of carbon particles indicated the lack of decom position over the years. Age had contributed to a slight increase in the boiling range of the Pyroclor, although not enough to affect the insulating properties.
Throughout their service life, these transformers (built to a specification dating back to 1936), have required no maintenance other than routine visual inspection. Nor have they required any topping up.
"Since the transformers were installed, records have either been lost or destroyed, but it is safe to assume that the Pyroclor was selected because of its fire resistant properties," said Mr. C. Claridge of the Birmingham Area M.E.B. who supervised the removal and examination of the pre-war transformer.
16
The top removed to show the dean condition of the interior.
And now, the 1000 kVA transformer will simply require topping up before it goes back into service at a suitable indoor location. Two more transformers of similar age are installed at Marshall and Snelgrove, the busy Birmingham store. This is a remarkable example of the reliability of Pyroclor. What other insulating material would withstand 30 years of fluctuating load and still be in first-class dielectric condition? Or consider how many times a conventional transformer would have to be cleaned out and refilled over that period.
0102828
TOWOLDMONOQ22294
The 1000 k VA. 30-year~ohi Pyrodor-jiUed transformer at the Birmingham Civic Centre.
TOWOLDMONOQ22295
Engineering Industry
Analysing the Advantages of Pyroclorffiled Transformers in Package Sub stations
When the choice has to be made between various types of transformers for a distribution system, the best analysis is to compare relative advantages.
This was the procedure adopted by Giddings & Lewis-Fraser Ltd, one of the world's leading manufacturers of numerically controlled machine tools. The total existing transformer capacity for the works was approximately 2,500 kVA installed in units of 500 kVA, and all transformers were of the oil-filled type having voltage ratios of 11,000/415.
Giddings & Lewis-Fraser Limited proposed installing an
IS
additional 750 kVA inside the factory to cater for the numerically controlled machine tools they manufacture, which are equipped with motors rated from 20-40 HP direct-on-line. It was decided that a package substation would show considerable cost and space savings compared with a conventional brick-built substation having a separate transformer connected by cable to the medium voltage switchgear. Only two types of transformer were considered: either Pyroclor-filled or Class "C" dry type. This was because of possible fire risk associated with oil filled transformers inside the factory and because of recommen dations by the insurance company concerning fire risk.
And here are the various factors which were considered by Giddings & Lewis-Fraser Limited and which influenced their ultimate decision.
0102830
TOWOLDMONOQ22296
Pyroclor Filled Transformer 750 kVA
Advantages 1. Fire-resistant insulant, consequently low fire risk. 2. No special buildings required for installation. 3. Compact and therefore suited to integrated transformer
switchgear layout. 4. Can be placed at load centre resulting in large savings in
cable costs which outweigh the additional cost of a Pyroclor-filled transformer. 5. Transformer hermetically sealed thereby preventing harmful ingress of dirt from a dust-laden atmosphere. 6. No fluid maintenance required. 7. Lower fire insurance rates.
Disadvantages 1. Possible long term efficiency of hermetic sealing unless a
welded construction is used.
750 kVA Transformer Class "C" Insulated
Advantages 1. Air-cooled, consequently low fire risk. 2. No special buildings required for installation. 3. Compact and therefore suited to integrated transformer/
switchgear layout. 4. Can be placed at load centre but savings in cable costs
would not outweigh additional cost of the air-cooled transformers. 5. Lower fire insurance rates.
Disadvantages 1. High cost: approximately 80% more than an equivalent
rated oil filled unit. 2. High risk of winding failure due to deposits of coolant
vapour and cast-iron dust associated with machine shop atmosphere. 3. Maintenance cleaning problems associated with removing above deposits. Pyroclor was the final choice and the finished package substation is a neat, compact arrangement. The medium voltage switch panels are fitted with 8 fuse switches TP & N, rated from 150 Amp. to 300 Amp. Future extensions can easily be accommodated on the switchboard together with cabling.
TOWOLDMONOQ22297
Exhibitions and World Fairs
EXPO 67
No less than 96 of the 100 electrical transformers used at Expo 67--Montreal's World Fair--were Pyroclor-filled. This architectural extravaganza with its 62 national pav ilions created a high demand for electrical power to supply exterior illuminations, monorail systems and escalators, the Expo Express train service and for the massive displays designed around such themes as Man and his World and Mart the Creator. Consumption of electricity during the exhibition period was rated as equivalent to a city with a population of 50,000 and the estimated cost including installations was 10,000,000.
Five single circuits at 25,000 volts nominal came from a substation on the south shore of the St. Lawrence river. Three of these circuits were transformed down from 25,000 to a 12,500 volt distribution network and the other two circuits were transformed down from 25,000 to a 600volts network for the various buildings and amusements.
Three double circuits at 12,500 volts from the north shore of the St. Lawrence river served directly electrical installations on Mackay Pier and the five rectifier stations of the mass transit system (Expo Express). These five stations were equipped with Pyroclor-fillcd transformers and rectifiers.
20
0102832
TT'rV'r'r
system
"" '0"
'reformers used for "* Exp ExpreSS rapid ,rami`
0102033
21
TOWOLDMONOQ22299
0102833.01
22
Gas Boards
The New Generation of Gas Works
The latest methods of town gas production are presenting plant designers with a number of new and interesting prob lems, derived from the inflammable nature of raw materials and from the large amounts of electric power required for the reforming process. A modern reforming plant may need up to 10 MW to drive motors for fans, feed pumps, hydro gen compressors, cooling tower pumps and other machinery. A further problem is space limitation. Most ofthe new plants must be erected on sites already occupied by coal-fed stations, and the latter cannot be removed until the new equipment is in full production. Both must operate together at first. Finally, there is the question of reliability. The new install ations usually comprise a number of separate gas-making units built into a common process. An electric power failure would halt the whole complex, and it might take several hours to bring a 120 million cu. ft./day output back on stream.
TOWOLDMQN0022300
The North Thames Gas Board's new plant at Slough, built by Woodall Duckham Ltd. on the site formerly occupied by a coal carbonising plant, will have an output of SO million cubic feet of gas a day. Space was a critical factor, and the only way to fit three transformers into an area set aside for two was to specify 3 x ISOOkVA Pyroclor-filled units to avoid the need for fire walls between and around them. They will work in parallel with automatic protection equipment; and should any of the three units fail the load will be automatically transferred to the other two. AH arc hermetically sealed and although their initial cost will be higher than equivalent oil-filled units, it is anticipated that maintenance costs will be lower.
On the same West London site, there is a 15-million cubicfeet-per-day peak load reforming plant which is fed with 1000 BTU methane gas. This plant is supplied with electri city from two 500kVA transformers which again are Pyroclor-filled, chiefly because a gas main runs across the only site available for the unit.
Pyroclor has the advantage of being chemically inert; it does not deteriorate in any way with time, consequently no maintenance is required and the initial charge of fluid should last for at least thirty years without replenishment or attention.
This was a factor in the choice of Pyroclor-filled trans formers for the Slough Works and also for the new 120million cubic-feet-per-day Town Gas Plant, Romford Works of the North Thames Gas Board. This is the largest capacity gas producing unit yet ordered by the British Gas Industry. Here there will be one group of 3 x lOOOkVA and one group of 3 x 1500kVA Pyroclor-filled transformers on a site which may also have to be occupied by tanks containing light distillate spirit. The reformers in this plant are fully instrumentated and will be operated by a very small staff. It is therefore important that maintenance requirements should be kept to a minimum.
Other Gas Boards who have specified Pyroclor-filled transformers for reasons of space limitation and reduced maintenance are The North Western Gas Board at Preston where four ISOOkVA units are in service whilst plant reconstruction is underway.
At the North Thames Gas Board. Southall. Europe's largest gas plant, two 600kVA Pyroclor-filled transformers have been operating since 1958. Pyroclor-filled transformers were chosen because of possible fire hazard and drainage pit considerations if conventional oil-filled units had been used. Furthermore, problems of space and cost precluded the use of air-cooled transformers.
Pyroclor-filled transformers at the North Thames Gas Board, Southall, have operated successfully since 1958.
23
One of the four 750 k VA hermetically sealed Pvroclor-filled transformers installed in a flame-proof area at the North Thames Gas Board Convey Island Methane Terminal, in dose proximity to the liquid methane tanks. These trans formers are manufactured to B.S. 171 andoperateat 3300/415 volts. The low tension cable hox is pressurised with nitrogen and there is a flame-proof cable box on the high tension side. The transformers are fitted with temperature gauges and bursting discs.
Pyroc/or-ft/fed transformers located at North Thames Gas Board, Slough.
24 0102834
TOWOLDMONOQ22302
Pyrodor-fiUed trans
formers associated
with the power supply
to the large-scale prod
uction plant of the
North Thames Gas
Board, Romford. They
are installed in dose
proximity to highly
inflammable
spirit
tanks.
0102835
TOWOLDMONOQ22303
General Post Office
Compact, Dust Free, Pyrocfor-filfed Units Below Ground for Railway Power
Recent modernisation on the British Post Office's private underground railways, which link eight postal depots in the busiest parts of London, included the installation of Pyroclor-filled fire-resistant transformers.
In the event of the transformers becoming heated due to a fire in the vicinity there is no risk of burning fluid spreading the conflagration through the underground tunnel systems. For static rectification of alternating current, the combin ation of Pyroclor-filled transformers and mercury-arc rectifiers has proved extremely reliable and economic.
At Mount Pleasant the sub-station is below the platform on which the mail-bags are handled. Pyroclor-filled trans formers were chosen because no enclosures or CO2 equip ment were required. They were preferred to air-cooled units because they are more compact, an important consideration below ground. In Lisbon. Portugal, the Metro has installed seven Pyroclor-filled transformers for a sunken rectifier sub station and The Pennsylvania Railroad Co. has now used Pyroclor-filled units for 25 years. Every one of the company's 215 electric locomotives is now equipped with this type of transformer.
010^636
TOWOLDMONOQ22304
A Pyroclor-Jilled transformer of the type used by the British Post Office at its Mount Pleasant, London, sorting office.
0102837
At the Post Office private underground railway, power for traction, signalling and lighting comes from transformers filled with Pvroclor fire-resistant cooling fluid.
TOWOLDMON0022305
Glass Industry
It
Where large numbers of transformers are required for diff erent duties as, for example, in a modern glass works with electric furnaces and electrically driven machinery, L.T. cable costs can become astronomical unless the transform ers can be sited close to the equipment they are to serve. This often means that only Pyroclor-filled fire-resistant transformers can be considered for most duties, and at Chance-Pilkington Optical Works, St. Asaph. N. Wales, a total of 19 such units have been installed. Four 750 kVA transformers are the main source of power, with 15 special transformers and reactors, to supply the various furnaces. The latter include 1 x 200 kVA, 5 x 150 kVA, I x 100 kVA, 6 x 50 kVA and 2 x 37.5 kVA units. All are located at load centres inside the factory itself and the use of Pyroclor has saved fire protection costs, reduced maintenance and by far the greatest saving has come from the reduced lengths of L.T. distribution cable required.
0102938
TOWOLDMONOQ22306
Large numbers of Pyroclor-ftlled transformers performing various duties at the Chanee-Pi/kington Optical Works, St. Asaph, N. Wales.
Multi-Storey Buildings
Freedom from Fire Risk in High-Rise Structures
Pyroclor-filled transformers are ideal for supply services in tall buildings. Freedom from fire risk is important in overcrowded areas and these transformers can be sited anywhere, in the basement or at the bottom of a lift shaft, for example, without special fire protection. Costly runs of L.V. cable are avoided by using Pyroclorfilled transformers in the sub-stations on several levels of a tall office block. The clean lines and modern appearance of present-day architecture are not marred by obtrusive out buildings or cages. Pyroclor transformers can be installed indoors, out of the way, and assist improved architectural planning. The Canadian Imperial Bank of Commerce, Montreal, installed Pyroclor-filled transformers on the 42nd floor, further proof that these units can be safely installed any where--even at the top of the Commonwealth's tallest skyscraper! 30 010Z840
TOWOLDMONOQ22308
An interior view of the sub-station at the Canadian Imperial Bank of Commerce.
Pyroclor-fiUed transformers have been installed on the 42nd floor of the Canadian Imperial Bank of Commerce, Dominion Square, Montreal, Canada.
0102t>i
TOWOLDMONOQ22309
TOWOLDMONOQ22310
National Coal Board
Several modern colliery winding installations in Britain have been equipped with Pyroclor-filled fire-resistant trans formers.
In the event of the transformers becoming heated due to a fire in the vicinity there is no risk of burning oil pouring down the mine shaft to spread the conflagration.
The North Western Division of the National Coal Board, for example, has installed 14 Pyroclor-filled transformers for rectifier duties at collieries in the Lancashire area. These are installed in the winding towers immediately above the pit shafts and, according to an NCB official, "the fire hazard associated with the difficulty of containing such a large volume of oil from reaching the shaft, made it essential to use a non-flammable fluid if the transformers were to be mounted in this position and avoid long and costly copper connections". Very similar installations have been com pleted at two collieries in the Durham Division of the National Coal Board.
33
0102643
Oil Industry
In Oil Pipeline Systems
With completion of a new 500-mile pipeline by Con structors John Brown Ltd., over the Atlas mountains, from the Sahara Desert to the Mediterranean coast, a further 10 million tons of crude oil a year will flow from the Algerian oilfields of Soci6t6 Nationale de TransportetdeCommercialisation des Hydrocarbures (S.O.N.A.T.R.A.C.H.).
At the Arzew terminal on the Mediterranean, where light crude oil is stored ready for loading into sea-going tankers, a 500 kVA Pyroclor-filled transformer has been placed beside the main switchroom. Two more, one of 150 kVA and one of 200 kVA, have been installed at a nearby tanker deballasting station and in the maintenance workshop.
The advantage gained by installing Pyroclor-filled trans formers was the freedom from fire risk when pumping a light crude oil at ambient temperatures which may vary between--2C and 4-50C. By minimising this risk it was possible to obtain better insurance rates and to conform with the practice in Algeria, where all existing oil plants have transformers with fire-resistant filling.
All units supplied for the S.O.N.A.T.R.A.C.H. project are hermetically sealed and will require little maintenance--a factor of some importance where unskilled staff are being trained to take over. And because the transformers were sited close to the plant long cable runs have been avoided. 34
0102644
TOWOLDMONOQ22312
In the Sahara Desert, Pyroclor-fiHed transformers for the 500-mile S.O.N.A.T.R.A.C.H. oil pipeline installation.
0102845
35
TOWOLDMONOQ22313
Rubber Industry
In Motor Tyre Factories
As in many other modern factories it is important to locate distribution transformers close to the plant they serve and to eliminate the expense of low-tension cable runs. But if the factory has a fire hazard, as in a large motor tyre plant, such economies are impossible to achieve unless Pyroclorfilled transformers are specified.
At the Goodyear Tyre & Rubber Company's works in Glasgow, electric power and lighting demands are met by one 1250 kVA and four smaller transformers, all sited inside the factory buildings. Three have been installed in major control rooms and the other two on platforms high above the production shops. The aim in choosing these sites was to place transformers as close as possible to the various load centres without encroaching on valuableproduction space at floor level. This was made possible by using Pyroclor-filled transformers.
The main transformer installation at the Belfast factory of Michelin (Belfast) Ltd., is oil filled. Even so, the six 40 kVA transformer/transductors, six 50 kVA transformers and four 100 kVA transformers on the shop floor, where the fire hazard is greater, are filled with Pyroclor.
Pyroclor-filled transformers are also used at the Firestone Tyre factory. South Africa. In countries where higher ambient temperatures are experienced, the high thermal stability of Pyroclor is an added advantage which has con tributed to its general use in such areas. 36
0102046
TOWOLDMONOQ22314
Saving space on the factory floor with Pyroc/or-filled transformers mounted in the roofgirders at Goodyear Tvre A Rubber Co. Ltd.
TOWOLDMONOQ22315
Steel Industry
Basement Locations in Steelworks Eliminate Fire Hazard
At the world's most advanced steelworks, the Spencer Works of Richard Thomas & Baldwins in South Wales, Pyroclor-filled transformers are installed in the basement of one of the rolling mills to eliminate fire hazard. The basement houses part of the main power distribution and control systems and even minor damage there could result in complete plant stoppage.
Two Pyroclor-filled transformers supply rectifiers providing direct current for the main drive motors of the two 60-inch temper mills which give the final finish to the cold-rolled wide strip. These 11 kV transformers are rated at 2625/4280 kVA.
This installation is only one of several completed in recent years in British steelworks. The Steel Company of Wales, at its Port Talbot Works, uses three Pyroclor-filled trans formers for the 56-inch high-speed temper mill, and the Appleby-Frodingham Steel Company, at Scunthorpe, has 11 units, supplying mercury-arc rectifiers.
In all these three installations, in basement locations, air cooled transformers with the British Class H insulation (180" C.) were considered but Pyroclor was preferred on cost grounds and because of the dusty environments. The modern steelworks depends on an unfailing supply of electricity. Even if a minor fire damaged the power distri bution system this could have far-reaching repercussions.
38 0102848
TOWOLDMONOQ22316
Left: Pyroclor-filled transjormers en route to Steel Company of Wales. Below: Pyroclor-filletl transformer units at Richard Thomas and Baldwins Ltd.
TOWOLDMONOQ22317
Television
Pyroclor-filled Transformers in high ambient Temperatures
Pyroclor-filled transformers are now in service at the new national television station for Malaysia. They are rated at 3.750 kVA, 11 /3.3 k>rA, and connect with a series of smaller Pyroclor-filled transformers--2 x 1,000 kVA. I x 750 kVA and I x 500 kVA at 415 volts. Package sub-stations arc used for these smaller units, built in the form of control panel consoles. Despite their size, these 3,750 kVA Pyroclor-filled units form a neat indoor installation with control gear alongside, as illustrated. The Pyrcclor fluid is unaffected by high ambient temperatures associated with tropical areas and the transformers are sealed, as recommended when using Pyroclor. so that maintenance is eliminated completely. Hence, there is always trouble-free transformer activity, an important consideration for ensuring continuity of tele vision programmes. 40 0102650
TOWOLDMONOQ22318
TOWOLDMONOQ22319
3
Advantages of Pyroclor-filled Transformers
Pyroclor-filled transformers are intended primarily for medium voltage distribution systems from 50 kVA to 2.000 kVA. The electrical engineer has a choice when designing such systems between three types of trans former unit:
Oil-cooled
Air-cooled (Class C) Pyroclor
Following are some of the reasons why Pyroclorfilled transformers are often considered in preference to the conventional oil-filled or ``Class C" dry-type transformer.
Figure 2 flame lest for Pyroclor-- the oil-soaked material on the right hums rapidly while the material soaked in Pyroclor on the left will not ignite under a hunsen burner.
42
0102052
TOWOLDMONOQ22320
Fire resistance
Pyrodor is very (ire-resistant. It cannot be ignited by internal transformer arcing or by surrounding flames and therefore provides maximum transformer safety.
Over-voltages
Pyroclor-filled transformers can be used in installations where over-voltages due to lightning or switching surges are prevalent.
No Fire Precautions
Pyroclor-filled transformers eliminate the need for fire walls, pebble drains and fire lighting equipment.
No siting limitations
Pyroclor-lilled transformer are particularly suitable in many applications where fire risk is great and space is limited. They can be located indoors, close to working areas or at the load centre. Increasing population, higher density of building and proliferation of industrial plants, high rise offices and apartments have put a high cost on space. The electrical engineer faces problems of reduced architectural space. Tight cost control has set a premium value on construction economies and reduced operational costs. These limitations present a number of difficult problems in system design for the electrical engineer. "Load centring" has emerged as a means of solving them. In load centring, Pyroclor-filled transformers, long-established and thoroughly service-proved can provide new solutions-- reducing expensive low voltage cable runs and improving voltage regulation.
Low noise levels
A comparison of various noise levels is tabled for Oil-filled. Air-cooled and Pyroclor-filled transformers. Pyroclor-filled transformers are the quietest in operation across the complete kVA range and for guidance 50-60 decibels repre sent the noise of suppressed conversation in a business office whereas 60-70 decibels is equivalent to a radio at high volume. The decibel range of noise measurement is an exponential progression. Hence a "7" decibel noise increase represents a noise seven times as loud.
Comparison of Noise Level
Size kVA
500 750 1,000 1.500
Oil-Filled Decibels
54 56 57 59
Air-Cooled Pyroclor-filled
Decibels
Decibels
58 53 60 54 62 55 64 57
Freedom from contamination
This is particularly important when transformers are being installed while building construction is in progress. Sealed Pyroclor-filled transformers are unaffected by dirty or dusty atmospheres.
0102833
43
Low Power Loss
Loss levels are another important consideration. In the graph below, the losses of Oil-filled and Pyroclor-filled transformers are identical whereas the loss level of Air cooled transformers is consistently higher.
Iron core and copper core losses for the three alternative types of transformer are given in detail in this table:
Comparison of Power Losses
Size kVA
300 500 750 1,000 1.250 1,500 2.000
44
Iron Core Loss (Watts)
Dry-Type (Class 'C")
Oil-Filled or Pyroclor-filled
1,200 1,480 1,900 2,400 2.950 3.480 4,375
673 1.030 1,420 1,770 2.150 2,400 3,000
Copper Core Loss (Watts)
Dry-Type (Class "C ")
Oil-Filled or Pyroclor-filled
6,250 8,050 10.400 12,800 15,500 18.500 26,000
4,600 6,860 9.500 11,820 14,000 16.000 20,000
0102854
TOWOLDMONOQ22322
High impulse level
Pyroclor-filled transformers (built to BS.I7I) have high impulse strength and offer a greater margin of safety against surging and overload than Class `C' transformers.
No maintenance
Because Pyroclor is blended to provide maximum thermal and chemical stability, a properly sealed Pyroclor-filled transformer requires no maintenance. No fluid checks, fluid filtration or fluid change should be needed for the entire life of the Pyroclor-filled transformer, see page 70.
Maximum reliability
Pyroclor-filled transformers are as sturdy and reliable as oilcooled units. A statement of their reliability by a large network user is given as follows: "Properly designed and installed askarel-filled transformers will give trouble-free service for over 30 years. Since their introduction in 1932, the overall failure rate has been less than 0.5% for all units under test and service conditions."
Ideal for Package Substations
The fire-resistance and elimination of fluid maintenance benefits make Pyroclor-filled transformers particularly suit
able for package substations where connections between transformer and switchgear may be solid busbar, thus eliminating the need for M.V. cable. Overall cable costs, site labour charges for interconnecting and time for installation are also greatly reduced. Busbar interconnections also lower the chances of a fault. Floor-space is saved, and the package Load Centre can be neat and uniform.
Lower Insurance Premiums
Although there is no standard reduction of premiums by insurance companies for Pyroclor-filled transformer users, many companies have been able to negotiate lower insur ance premiums.
Summary of Main Benefits of Pyroclor-filled Transformers
No pebble drains & fire eq. No maintenance No siting limitations Low noise levels Low loss levels High impulse levels No fire risk
OIL air PTR0CL0R
V
V V' V
0102855
TOWOLDMONOQ22323
4
Cost saving with Pyroclor-fiiled Transformers
Typical installed costs of Pyroclor-fiiled, mineral oilfilled and Class `C' transformers, based on equivalent rated transformers have been calculated. While the initial cost of a mineral oil-filled transformer is lowest, once provision has been made for maintenance, re filling and the fire precautions almost certainly necessary with a flammable liquid, the installed cost can well be even higher than that of a Class *C' dry-type. The Pyroclor-fiiled transformer, whose initial cost is be tween that of the other two, can prove to be the least expensive. 46
0102856
TOWOLDMONOQ22324
In a well constructed transformer, the initial Pyroclor charge can be expected to last the life of the transformer. Thus a Pyroclor-filled transformer is maintenance free under normal operating conditions. Maintenance must be carried out on both oil and dry-type transformers. The following table gives details of typical maintenance require* ments and costs.
Source of Cost*
OIL
Transformer 1000 kVA
Fire-protection equipment
58 32
Civil Work TOTAL
10 100
AIR
PYROCLOR
CLASS 'C'
FILLED
110 82
--
8 14 118 86
1 Type
Work Required
Frequency
OIL-FILLED Cyclic Loading
Oil Filtration Oil Change Sample Check
Every 7 years Every 14 years Every year
Continuous Load
Oil Filtration Oil Change Sample Check
Every 4 years Every 8 years Every year
OPEN DRY-TYPE (Class "C")
Regular cleaning of air gaps and air ways
Depending upon environment, but at least once annually
PYROCLOR-FILLED NONE
-
0102a*?
47
TOWOLDMONOQ22325
Examples of Cost Savings with Pyroclor-filled Transformers
The most impressive savings that Pyroclor-filled trans formers can make are in the total solution of the power distribution design problem. The following are two typical problems with their alternate solutions com-
EXAMPLE 1 (Theoretical)
Small factory, 200' x 400', requiring installed capacity of 1,000 kVA, supplied at II kV, and distributed at 415 V. 48
0102858
TOWOLDMONOQ22326
Two 500 kVA transformers in outside sob-station, feeding two indoor distribution and starter boards inside.
Cable Costs
MV Cable: 0.6 sq. in. Copper (P.i.L.C W.P.V.C.) (singles) 0.8 sq. in Aluminium (singles) (P.V.C.) (Assume 4-core M.V. cable required)
2,227/1,000 yds 888/1,000 yds
Solution A Requires:
200 ft. MV cable between each transformer and distribution board. 2 x 200 x 4 (cores) 1,600 -- X 2,227/1,000 (Copper)
1,600 -- X 888/1,000 (Alum.)
- 1,600 ft. = 1,190
= 474
Note: All pricings quoted are based on costs prevailing 3rd quarter 1967.
0102859
49
TOWOLDMONOQ22327
Site two 500 kVA transformers inside building with distribution boards.
Cable Costs
E.H.V. Cable: 0.06 sq. in. Copper (P.l.L.C.S.W.A.) 0.10 sq. in. Copper (P.l.L.C.S.W.A.) 0.15 sq. in. Aluminium (Sat. polythene S.W.A. & P.V.C.) (Prices are for 3-core cable)
50
1,342/1,000 yds. 1,837/1,000 yds.
1,838/1,000 yds.
Solution B requires two 200 ft. E.H.V. cable runs to connect source of supply to the indoor transformers.
200 x 2 = 400 ft. E.H.V. 400 x (Costs cited) = 179 (0.06 Copper) T~ 245 (0.10 Copper)
245 (0.15 Alum.)
O102S60
TOWOLDMONOQ22328
Operating Costs
Assume the two transformers are 75% loaded, 50% of the time, operating 4,400 hrs/annum, with power costs at Ap./unit.
(Solution A) Power Loss in MV Cable
6,100 wans (Copper) 7.750 watts (Alum.)
The minimum improvement in conductor loss by using the E.H.V. cable to a load centre is 6.03 kW or an annual minimum saving of 110
Cost Comparison Summary
(Solution B) Power Loss in E.H.V. Cable
66 watts (0.06 Copper) 40 watts (0.10 Copper) 44 watts (0.15 Alum.)
Cable Cost: Minimum Saving 229 Operating Cost: Minimum Saving 110 per annum
A short check will show that the savings could be as great as 1,100 annually, approximately 65 % of the initial cost of the Pyroclor-filled transformers.
0102U61
TOWOLDMONOQ22329
EXAMPLE II
(Actual case history detailed cost analysis of instal lation and operation*).
Factory with fire risk. Transformer size 1,000 kVA; maxi mum demand, 700 kVA; load factor, 0.35.
Three alternative solutions of the problem of supplying this can be considered:
1
Substation to be installed outside factory with MV feed to load centre--a distance of 200 yds.
(Cost: 6,688)
2
Substation to be installed inside factory at the load centre containing a standard oil-filled transformer and MV switchgear. Fire protection equipment to be installed inside the substation. The II kV metering O.C.B. to be installed outside the factory a distance of 200 yards away.
(Cost: 2,891)
3
Same as 2 but utilising a Pyroclor-filled transformer; no fire protection needed.
(Cost: 2,623)
The costs that would be common to all solutions can be omitted. The electrical characteristics of Pyroclor and oil-filled transformers are similar, therefore the cost of transformer losses can be ignored.
Basic Pricing Data
Cable Losses:
Based upon C.E.G.B. bulk tariff
Day rate units (adjusted for 100/- per ton of coal) 0.6873 d/unit
Peak units (adjusted for 100/- per ton of coal) 1.0873 d/unit 90% of the losses occur at the Day Rate
10% of the losses occur at the Peak Rate
Therefore, cost per unit (plus 5% to cover losses in the system) is:
0 6783 X 0.90 4- 1.0873 x 0.10 x 1.05 d/unit = 0.7688 d/unit
Demand Costs:
(including 8 % to cover losses in the system) = 7.11 /kW
Loss Load Factor:
0.3F + 0.7F2= (where F = load factor (0.35)
0.191
* Grateful acknowledgement is mede to the Birmingham Electrical Engineering Dept.. Midland Electricity Board, for their assistance in calculating this case
52
010286
TOWOLDMONOQ22330
System Conditions:
Cables installed in conduits: 700 kVA = 970A (Rating of 3 x 4C .5 Al. cables installed in a 3-way conduit is 370 A--in accordance with ERA Report Reference F/T.183).
Voltage Conditions at Load Centre:
Assumed temperature of cables: 50C Resistance of 4C .5 Al. cables at 50C = 0.084 x 1.121 = 0.094 ohms/1000 yds Load on each cable 970 = 323A
T Volt Drop along 200 yd. length: 323 x 200 x 0.094 =
Tooo
6.1V (2.5%)
Capital Costs:
Additional cost over alternatives to house switchgear
and transformer
100
Oil-Filled Transformer
1,100
3 x 200 yds, 4C .5 Al. cable supplied, delivered and installed (including cost of conduits) and terminated 2,700
On cost 8%
3,900 310
Total: 4,210
Cost of Operating Losses:
I*R per cable 323* x 0.094 x 200 x 3kW
1666* = 5.9 kW per cable Annual unit losses in one cable: 5.9 x 8760 x
0.191 x 0.7688 =
240
Demand Losses per cable: 7.11 x 5.9 --
Total annual losses per cable:
Total losses per 3 cables:
Loss over 25 years at interest of 71 %: 220.5 x
11.147 -
'
31.5
42 73.5 220.5
2,478
0101063
53
TOWOLDMONOQ22331
System Conditions:
Load: Current: Size of Cable: Resistance of Cable at 20C:
700 kVA at 11 KV 37A
3-core 0.015 sq. in (Al) 0.282 ohms/1,000 yds
Capital Costs:
Building to house transformer
500
1000 kVA oil-filled transformer
1,100
Fire protection in substation
300
200 yds. 3C. .15 sq. in Al. cable supplied delivered,
installed (including cost of conduits) and terminated 750
On cost 8%
2,650 210
Total: 2*860 54
Cost of Operating Losses:
I2R per cable -- 372 x 0.282 x 200 x 3kW - 0.22kW 1000
Annual unit Losses: 0.22 x 8760 x 0.191 x .7688 1.2 240
Demand Losses: 0.22 x 7.11 --
1.6
Total Annual Losses:
2.8
Loss over 25 years at 71 % interest (2.8 x 11.147) = 31
0102864
TOWOLDMONOQ22332
Capital Cost:
Proportion of cost of Load Centre Housing for Transformer 1,000 kVA Pyroclor-filled Transformer 200 yds. 3C. .15 sq. in Al. cable supplied delivered installed (including cost of conduits) and terminated
200 1,450
750
On cost 8%
2,400 192
Total: 2,592
Cost of Operating Losses:
The cost of operating losses for this solution will be identi cal to that of Solution B. Annual Losses: 2.8. Loss over 25 years at 7i% interest:
31
Comparison of Costs
Capital Cost. Cost of Operating Losses. Total ()
Solution A (MV)
4,210 2.478 6.688
Solution B Oil Filled Transformer
2,860 31
2,891
Solution C Pyroclor Filled
Transformer
2,623
55
EXAMPLE III
Multi-Storey Buildings Supply to 32 Storey Blocks of Flats.
Details of Load
No. of consumers ..
ADMD per consumer
Total load of building
Load Factor
.
248 8 kW 1984 kW 0.32
Two alternative schemes of supplying this load are considered:
1. One 4 MVA capacity substation on ground floor.
2. One 2 MVA capacity substation on ground floor and one 2 MVA capacity substation on 16th floor.
Cost of Copper Losses:
Based upon latest C.E.G.B. bulk tariff.
Day rate units
(adjusted for 100/- per ton of coal)
0.6873d./unit
Night rate units
(adjusted for 100/- per ton of coal)
0.5573d./unit
Peak Units
(adjusted for 100/- per ton of coal)
1.0873d./unit
82 % of losses occur between 07.00 hrs and 23.00 hrs.
9% ,, ,, ,,
,, 23.00 hrs. and 07.00 hrs.
9% ,, ,, ,,
during peak periods.
Therefore cost per unit
(0.6873 xO.82 xO.5573 x0.09 +1.0873 x 0.09)d./unit
Plus 5% to cover losses in the system.
(0.6873 x 0.82 +0.5573 x 0.09 +1.0873 x 0.09) 1.05
=0.7463d./unit.
Demand Costs, including 8% to cover losses in the
System 7.ll/kW
56 0102666
TOWOLDMONOQ22334
Load Loss Factor:
Loss Load Factor = 0.3F -1- 0.7F2 where F = load factor (0.32) - 0.168
Capital Cost:
Contribution to Corporation for Substation Chamber 2 x 1000 kVA oil-filled Transformers at 1100 each MV Cables between substation and distribution board on 16th floor (53yds/cable)
On cost 8 %
1200 2200
300
3700 296
3996
0102867
57
TOWOLDMONOQ22335
Assumption:
Lift for hoisting equipment to 16th floor available. Contribution to Corporation 976 per substation. Transformer in ground floor substation oil-filled Transformer in 16th floor substation Pyroclor-filled HV switchgear installed in ground floorsubstation--isolation of Pyroclor-filled transformer by means of remote tripping.
Cost of Losses:
Assumed temperature of cable 50C Resistance of 4C .15 Al. cable at 50C - 0.316 ohms/1000 yds.
58
Current/Conductor/Cable = 345 A
Distance of feed 53 yds. = 0.0168 ohms. PR per cable = 345* x 0.0168 x 3 x 1^ kw
-- 6.00 kW per cable
Annual unit losses in one cable 6.00 x 8760 x 0.168 X 0.7463 240 27.5
Demand losses per cable 7.11 x 6.00 42.7
Total Annual losses per cable 70.2
Total Annual losses for 4 cables 280.8
0102868
TOWOLDMONOQ22336
Annual maintenance cost of 2-1000 kVA oil filled transformers = 2
Present value of above charges over 25 years at interest of
n%
(280.8 -f- 2) x 11.147
3140
Capital Costs :
Contribution to Corporation for Substations at 976 each 1 x 1000 kVA oil filled Transformer at 1100
I x lOOOkVA Pyroclor-filledTransformeratl450 53 yds. 3C .15 sq. ins. (AI.) cable supplied, delivered, installed and terminated
53 yds. 4C 0.3 sq. in. (AI.) cable as above (30% Interconnection between substations) Fencing off transformer, interlocking compound with 11 kV OCB and remote tripping
1953 1100 1450
124
150
200
On Cost 8 %
4976 398
5374
Cost of Losses:
Resistance of 3C 0.15 Al. cable 0.172 ohms/1000 yds.
Current/Conductor/Cable 50A at 11 kV
Distance of feed 53 yds. = 0.0092 ohms.
1*R per cable 50s x 0.0092 x 3 x 10~* kW 0.068 kW
Annual unit losses 0.068 x 8760 X 0.168 x 0.7463
240 0.3
Demand Losses 0.068 X 7.11 0.48
Total Losses 0.78
Annual maintenance cost of 1000 kVA oil filled transformer
1.
Annual maintenance cost of 1000 kVA Pyroclorfilled transformer
NIL
Present value of above charges over 25 years at interest of
n%
(0.78 + 1.0) x 11.147
20
Summary of Costs
Capital Cost P.V. of Running Costs Total Solution B is 24.5% cheaper than Solution A.
Solution A 4 MVA S.S. on Ground Floor
3996 3140
7136
Solution B 2x2 MVA
S.S. 5374
20 5394
0102669
59
5
Typical properties of Pyroclor
There are two grades of Pyroclor available:
PYROCLOR 5
the recommended fluid for all Pyroclor-filled transformers operating at normal ambient temperature conditions.
PYROCLOR 1
for cases where transformers are required to operate at unusually low temperatures.
Pyroclor I and Pyroclor 5 have similar properties but Pyroclor 5 has the additional advantages of lower density and higher relative permittivity.
The following table shows typical values for several properties of Pyroclor 5 and Pyroclor 1.
010270
TOWOLDMONOQ22338
Typical Properties of Pyroclor 1 and Pyroclor 5
Property
Appearance
Colour Density at 20C
Refractive Index at 20C Kinematic Viscosity at 20 C Fire Point Pour Point Neutralisation Number Inorganic Chlorides Scavenger Content (PPO) Water Content Electric Strength at 25C, 50 Hz Resistivity at 100C. 500V, after 1 minute Dissipation Factor (tan ft) at 100C, 50 Hz Relative Permittivity at 100C, 50 Hz
Test Method
ASTM D1702
ASTM D1702 ASTM D1810 and ISO/R 649 ASTM D1807 ASTM D445 ASTM D92 ASTM D97 Monsanto ASTM D1821 Monsanto ISO/R760 IEC 156 Monsanto Monsanto Monsanto
Unit
APHA g/cm*
Pyroclor 1
Pyroclor 5
Clear liquid free frorr suspended matter and sec ment
150 max.
150 max.
1.555 to 1.565
1.502 to 1.524
cSt C c mg KOH/g ppm Cl % ppm kV T D cm % -
1.6160 to 1.6180 24 max.
None to BP --33 max. 0.01 max. 0.1 max. ca. 0.2 30 max. 45 min. 1 min. 5 max. 3.8 to 4 0
oio;#TM
1.6173 to 1.6193 32 max.
None to BP --30 max. 0.01 max. 0.1 max. ca. 0.2 30 max. 45 min. 1 min. 5 max. 4.2 to 4.5
61
TOWOLDMONOQ22339
Viscosity
Table 1 shows that the viscosity temperature characteristics of Pyroclor 5 closely resemble mineral oil. Pyroclor 1 is suitable for very low temperature operation.
TABLE 1
Temperature (C)
-30 -20 -10
0 f 10
20 30 40 50 60 70 80 90 100
Kinematic viscosity (cSt)
Pyroclor 1
Pyroclor 5
Typical mineral oil
ca. 16 000 1 800 350 100 42 21 12.3 7.8 5.4
3.9 3.0 2.4 1.98 1.70
ca. 60 000 4 524 655 162 57 26 15 9.4 6.4
4.6 3.4 2.7 2.2 1.86
2 500 750 270 118 62 33 21 14 9.7 7.2 5.5 4.3 3.4 2.8
Density
Table 2 shows that Pyroclor has approximately twice the density of mineral oil (15.2 lb. U.K. gallon for Pyroclor 5).
TABLE 2
tC)
0 10 20 30 40 50 60 70 80 90 100
Density (kg/m3)
Pyroclor 1
Pyroclor 5
1.578 1.567
1.560 1.545 1.534 1.533 1.512 1.501 1 490 1.479
1.468
1.541 1.530 1.520 1.510 1.499 1.488 1.478 1468 1 457 1 446 1 436
62
Therefore the Pyroclor-filled transformer is heavier and this raises certain questions regarding the location of Pyroclor transformers, particularly in high-rise buildings. The subject is fully discussed in the section "Pyroclor-filled" transformers in operation" . . . page 66.
Solubility of Water
Water is slightly more soluble in clean Pyroclor than in mineral oil, but there is very little change in the solubility between new and used Pyroclor.
Vapour Pressure
The variation of the vapour pressure of Pyroclor with temperature is shown in Table 3.
Temperature (C)
40 60 80 100 120 140 160 180 200 220
TABLE 3
Vapour Pressure (torr)
Pyroclor 1
<1 2 5
12 27 55 105 188 322 527
Pyroclor 5
<1 1 4 9
20 41 79 141 242 397
In the above table the values at the lower temperatures have been obtained by extrapolation. This procedure was adopted to overcome inherent difficulties in the measurements of low vapour pressures of mixtures of liquids.
Water Absorption
Figure 4 shows the absorption of water from humid air by transformer askarel and mineral oil.
0102672
TOWOLDMONOQ22340
Gas Absorption
The solubility of carbon dioxide, air, nitrogen, and hydrogen chloride is shown in this table.
SOLUBILITY OF GAS IN PYROCLOR
Percent Gas by Volume
Corrected to:
25C--750mm
0C-- 760mm
Carbon dioxide Air Nitrogen
Hydrogen Chloride*
25C 71
5.7 6.0 37.8
100C 47
4.9
4.8 50.9
In the absence of gas scavenger
25C 100C
5.8 5.0 5.5 4.4 ----
Stability (Corrosion) Test
Description A sample of the Pyroclor is heated in darkness for 6 hours at a temperature of 210 C with a prepared piece of alumin
ium foil. At the end of this period, the appearance, colour, inorganic chlorides and neutralization number of the sample of Pyroclor are determined. The piece of aluminium foil is examined for changes in appearance and its weight loss is determined.
Results: The values in the following table must not be exceeded for the sample of Pyroclor to pass this test.
Property
Aluminium foil Weight loss (g) Change in appearance
Pyroclor sample Colour (APHA)
Inorganic chlorides (ppm) Neutralization number
(mg KOH/g)
Test method
Value
-- Visual
0.0 None
ASTM D1702 ASTM D1821
Monsanto
200 (max) 5.0 (max)
0.01 (max)
010^073
63
TOWOLDMONOQ22341
Chemical Properties
Fire Resistance
Although Pyroclor can be shown to have a flash point when examined by the usual laboratory tests, no fire is carried back to the liquid phase, therefore there is no corresponding fire point. The autogenous ignition temperature of Pyroclor can be measured by dropping small quantities of the liquid on the floor of a ceramic lined muffle furnace. The liquid does not take fire until the surface glows with a dull red heat, approximately 700C. However, once the liquid leaves the hot surface it ceases to burn and does not convey fire by means of a moving stream of liquid. The laboratory of the National Board of Underwriters (U.S.A.) have carried out stringent tests on the fire resistance of this type of liquid and have concluded that it is essentially non-flammable.
Thermal Stability
Pyroclor undergoes no thermal decomposition whatsoever at temperatures below 175C. If Pyroclor is heated above this temperature by local over-heating or transient arcing, small quantities of hydrogen chloride gas are produced. The gas scavenger additive in Pyroclor absorbs this hydrogen chloride and prevents attack on the iron core or the cellulosic insulation. If a major internal fault occurs in a Pyroclor-filled trans-
64
former which results in a sustained arc below the Pyroclor surface, the extremely high temperature of the arc will decompose the Pyroclor. Major faults are discussed in the section "Pyroclor-filled transformers in operation" .. . page 66.
Resistance to Oxidation
Pyroclor has exceptional resistance to attack by oxygen. When subjected to a bomb test at 140C in oxygen at a pressure of 250 psig. (17 kg/cm2) there is no evidence of oxidation as judged by development of acidity or the formation of sludge. Hot mineral oil in the presence of oxygen undergoes a series of complex chemical reactions, producing by stages, peroxides, acids, water and other condensation products which eventually form a sludge.
Stability to Hydrolysis
Whilst Pyroclor is resistant to attack by water, water will dissolve in Pyroclor and will deteriorate the electrical properties. Pyroclor has been tested by refluxing with water whilst oxygen was passed through the mixture. No free chlorides were generated during this test. In another test Pyroclor was sealed in a glass capsule with water and heated for six hours at I50X, and again no chloride forma tion was .detected.
0102874
TOWOLDMONOQ22342
Dielectric Properties
Although a transformer liquid is principally a coolant, it must also act as an insulation in and between the windings of the transformer. Good dielectric properties are therefore an important characteristic of the fluid.
Loss Tangent
Satisfactory Pyroclor in a transformer may be expected to have considerably higher loss tangent than new material, in the range 0.2 to 0.8 at 100C.
Dielectric Strength
The dielectric strength of Pyroclor is equal to or better than the best quality mineral oil and has the dielectric qualities required for the voltage stresses encountered in trans formers over the entire temperature range of operation.
Permittivity
The permittivity of Pyroclor is much closer to the permitti vity of cellulose and this leads to a greater uniformity of stress in impregnated press board.
D.C. Resistivity
Satisfactory Pyroclor sampled from a transformer may have a d.c. resistivity as low as 2.5 x 101#lcm at 100C.
D.C. resistivity of Pyroclor is thus seen to be much lower than that of mineral oil by comparison. This inevitably leads to lower insulation resistance on finished transformers filled with Pyroclor than on their counterparts filled with oil. This is, however, quite normal and is an accepted characteristic of Pyroclor-filled transformers.
TOWOLDMONOQ22343
6
Pyroclor-filled Transformers in operation
Effect of Temperature
The electrical engineer can place a Pyroclor-filled trans former anywhere in the distribution system, right at the centre of load if necessary because of these two important factors:
1. Pyroclor is fire-resistant. Where oil will ignite readily, Pyroclor will extinguish flame.
2. Pyroclor, unlike oil, is thermally stable. U suffers no change up to temperatures of 175C and is affected very little beyond that point.
Let us examine fire resistance more closely and take into account other operating conditions--electrical load (pres sure build-up), the effect of time and exterior contamination.
66
Fire resistance
The fire resistance of Pyroclor may be easily demonstrated. For example if Pyroclor is aerosoled in a container it may be sprayed out onto a conventional gas burner easily extingui shing the flame. A similar test with mineral oil will result in the immediate formation of a powerful jet of burning atomised liquid.
In the laboratory, tests may be conducted using oxyaoetylene welding flame and electrically heated metal strips. Pyroclor fluids will not ignite when sprayed on such high temperature sources. In contrast, mineral oil will readily ignite to produce immediate and sustained burning. See also Pyro clor--Flash Point and autogenous ignition ... page 64.
It is For these reasons that a Pyroclor-filled transformer installation does not require fire fighting equipment, fire walls or any other special fire precautions.
0101876
Should the fluid escape as a result of a severe local fire it would tend to dampen and blanket the flames.
Transient arcing and Pressure build-up
Transient arcing or corona discharge is not unusual in all types of transformers and is usually caused by load fluctua tion, switching surges or lightning. If Pyroclor is raised above 175C by local over-heating or transient arcing small quantities of hydrogen chloride gas may be formed. This gas will be immediately absorbed by the gas scavenger in Pyroclor. Thus any pressure build-up or possible attack on the iron core or celiulosic insulation of the transformer is avoided.
Experience based in over forty years ofcontinuous operation of Pyroclor-filled units shows that the gas scavenger does not normally need replenishment, the initial amount being capable of lasting the life of the transformer.
Sealed Pyroclor-filled transformers are constructed to with stand normal operating pressure fluctuations. Pressure relief valves or bursting discs can be incorporated as additional protection if required.
The effect of time
The breakdown strength of Pyroclor in a properly sealed transformer does not deteriorate with age despite possible variations in power factor and volume resistivity. It is frequently found that megger readings taken on Pyroclorfilled transformers are considerably lower than those taken on oil-filled transformers. This is quite normal and the transformer is quite safe for use. The lower reading is simply a reflection of the much lower DC resistivity of Pyroclor compared with mineral oil. The reliability of Pyroclor is not affected by such low megger readings.
TOWOLDMONOQ22345
External Contamination
Pyroclor-ftlled transformers can he operated successfully in adverse environments. Satisfactory operation has been achieved in countless applications which include exposure to the dust and dirt of building sites, the metallic dust of load centred industrial factory installations or even the atmosphere surrounding a blast furnace. The layers of dust which may accumulate on a transformer during the years should have no effect on its operating efficiency.
One source of external contamination which really will affect a Pyroclor-filled transformer in service is water. Water ingress should always be avoided. For example if the Pyroclor reaches a moisture level of 70 ppm the dielectric properties may be seriously degraded. This is one of the main reasons why sealed Pyroclor-filled transformers are recommended. Unsealed units require the installation of protective devices such as silica gel to prevent water being drawn in by the natural breathing of the unit. Experience shows that inadequate maintenance of the breather gel can often render such protection useless.
The Weight of Pyroclor-filled Transformers
Pyroclor is approximately twice as heavy as mineral oil (See table). Generally the weight of a Pyroclor-filled transformer does not pose any particular problem when installed in high rise structures. Local floor strengthening may be necessary but present day architects generally allow for varying load stresses on intermediate floors, the tolerance being well above the weight of a Pyroclor-filled transformer. Often the transformer and control gear can be located near main
Size (kVA)
TABLE
Oil-Filled 1 Dry-Type 1 Class C
(weights in pounds)
Pyroclorfilled
500 750 1,000 1,500
5200 6.600 8,100 14,000
5,000 5,000 7,300 9,800
7,000 8,500 11,000 17,000
68
support areas where additional high floor loading may be tolerated. Pyroclor-filled tranformers have been installed in elevated locations in many tall buildings and rarely has local floor strengthening been required. See page 30.
Transformer Faults. .Leakage
A properly sealed Pyroclor-filled transformer should norm ally never leak, but if leakage does occur, Pyroclor should not be fed into a normal drainage system. Monsanto will advise on disposal.
Major Faults
As with most liquid filled transformer units major faults are extremely rare with Pyroclor-filled transformers. However, should sustained arcing result from a major fault condition in a Pyroclor-filled transformer, hydrogen chloride gas would be formed but since hydrogen chloride is a non combustible/non-explosive gas there will be no danger of a resultant fire. The quantity of gas formed is directly pro portional to the intensity of arc and roughly the same amounts of gas are evolved from Pyroclor as from mineral
OIL PYROCLOR
Hydrogen 60%
UNSATURATED HYDROCARBONS 16% SATURATED HYDROCARBONS OTHERS (NITR06EN ETC.) 14%
Decomposition products: Oil and Pyroclor
0IQZS7*
oil for a given arc intensity. However, in the case of mineral oil the gases will be a mixture of hydrogen and hydro carbons. Unlike hydrogen chloride, these gases are flam mable over a wide range of gas/air mixtures.
Whereas with transient arcing the gas scavenger additive in Pyroclor-filled transformers adequately copes with gas formation, under major fault conditions this additive would be unable to cope with the quantities of hydrogen chloride formed and the pressure in the transformer would build up. Pyroclor-fiHed transformers may be fitted with a pressure relief actuator or a pressure bursting disc to give additional protection against such a situation. Therefore, should hydrogen chloride gas be released from the transformer unit as a result of a major fault it would be expected to disperse rapidly as transformers are generally located in well venti lated areas to facilitate cooling. It should be noted that the formation of gas will only continue whilst the arc is actually striking across the fluid. As soon as the overload current protection devices trip, arcing and the formation of hydrogen chloride will cease. Hydrogen chloride is an irritant gas, but it is easily detectable at concentrations below the harmful level. The quantity of hydrogen chloride liberated under major fault conditions is not likely to have a harmful effect on personnel provided they withdraw from the area or wear breathing apparatus. The gas may cause irritation of the eyes, nose, throat and lungs. If necessary irritation of the eyes may be relieved by flushing with water.
Pyroclor derives its fire resistance from the halogen atoms in its molecular structure. Because of this some engineers have supposed that either chlorine or phosgene could be liberated by arcing. Five independent studies in three countries where askarels are extensively used have shown that both theoretically and in practice these gases are NOT produced:
U.S.A. FRANCE
GERMANY
Underwriters Laboratory Report Underwriters Laboratory Misc. Hazard Report
Jay P "Study of the Formation of Phosgene by Decomposition of Chlorinated Hydrocarbon in the electric arc" Paper: "Chimie et Industrie" 92, No 5 (Nov. 1964)
Chemische Technische Reichsanstalt May 21 1940 Report Farben Fabriken Bayer 1964
Regulations and Codes of Practice For Indoor Transformer Installations
When siting of transformers indoors by the system of load centring building regulations and codes of practice have to be taken into account.
The "regulations For the Electrical Equipment of Buildings" published by the Institution of Electrical Engineers, 1966 edition. Section C-5 (Page 63) recommends:
"Where fixed oil-filled apparatus of a capacity exceeding 20 gallons is used, means shall be provided for draining away surplus oil and for preventing the escape of oil into any other part ofthe building."
Note: It is recommended that oil-filled apparatus installed within a building and having an oil capacity exceeding 50 gallons be placed in a chamber of fire-resisting construction, ventilated to the outside of the building only.
There is no British Code of Practice covering the installation of Pyroclor-filled transformers. Reference can be made to the National Electric Code of the American Standards Association (1956) Article 450, Section 4522, page 152.
010679
69
7 Fluid Checks
1. Sealed Transformers
A properly designed, sealed Pyroclor-filled transformer needs no maintenance.
2. Unsealed Transformers
Unsealed transformers (e.g. breather types) have been manufactured. Even these, when Pyroclor-filled, require no maintenance in the true sense. However, inspection of the fluid may be necessary at intervals to determine whether it has retained in full original electrical properties. Either the transformer manufacturer or user may wish to perform these simple fluid checks and the following is the procedure.
Sampling Procedure
A sample should be taken as close to the top of the liquid surface as possible in addition to a sample from the bottom of the transformer. If sampling tube connections are attached to the valves for ease of sampling, tubes should be made of either clean glass, stainless steel, aluminium or tin for rigid types and silicone rubber or teflon tubing for flexible types. Ft is best to take the sample from a trans former which is warm and operating at average or maximum load. Sampling of the warm Pyroclor more truly represents its condition during operation.
Samples of Pyroclor to be used in tests of electrical pro perties, i.e. resistivity and power factor, are very easily
70
contaminated, and it is essential to follow the procedure recommended below in order to obtain true measurements. If a result is poorer than anticipated, the whole procedure should be repeated for a second sample (more than once if necessary).
Sample Bottle
Narrow necked glass bottle with bakelite screw-on cap is suitable. The sealing washer inside the cap should prefer ably be PTFE, but a paper disc can be used, if covered by a layer of aluminium foil. Other seals such as rubber, etc., will cause sample contami nation.
Preparation of the Sample Bottle
(a) If the bottle is new, wash out the bottle and cap with water and detergent (household type), rinse out with running warm water and then rinse three times with distilled water. If analytical quality acetone is available, give a final rinse with this to speed the drying process. (Do not use technical quality acetone as contamination is likely.) Dry in a clean oven for half an hour at approximately 110C (longer if the acetone rinse is omitted) and keep the bottle closed in a drying cabinet until required.
(b) If the bottle has been previously used (for Pyroclor sampling), first wash out with a hydrocarbon solvent such as benzene or petroleum ether, then carry out the cleaning procedure as described above.
0102690
TOWOLDMONOQ22348
The Sampling Operation
Remove the cap from the sample point and wipe the end of the pipe with a dry tissue. Place a receptacle under the sample pipe and run off about five litres. Then without stopping the flow place the sample bottle under the pipe and rinse out the internal surfaces (not forgetting the screw cap) three times with Pyroclor before filling with sample to about 90% full. Take special care to avoid touching the sample point with the neck of the sample bottle. Put the screw cap on and tighten immediately. Close sample dis charge valve and replace cap. Clean the exterior of the bottle as necessary with a clean tissue. The material used for rinsing etc. should be discarded. (See section 9 regarding arrangements for disposal of waste product.)
If the sample is to be stored for an appreciable time before testing, the bottle (even if of dark glass) should be wrapped in aluminium foil or opaque paper and placed in a card board tube or other container suitable for transportation. Sampling should be preferably carried out under cover, if this is impossible, precautions must be taken to keep any rain from the vicinity of the sample pipe and bottles. Sampling out of doors in wet weather conditions should be avoided, if at all possible. In such circumstances make a note of the adverse conditions.
Routine samples of Pyroclor should be checked for:
1. Appearance 2. Dielectric Strength 3. Moisture Content 4. Loss Tangent
1. Appearance
A blue, green or red cast in clear Pyroclor shows that it is extracting colour from internal materials. This is not an operating hazard when the dielectric strength stays above 40 kV, when the moisture content is low and when there is no leakage. However, this condition calls for a check on the interior construction of the transformer and a re-assessment of the compatibility of materials used in its construction, if the Pyroclor is dark brown or black, with small carbon
particles present and if the dielectric strength is low, then heavy arcing has been occurring and immediate action should be taken.
Because Pyroclor does not oxidise, sludge or decompose in normal use it can suffer only minor contamination. Turbi dity combined with high dielectric strength is due to insula tion particles, metallic dust or dirt in the Pyroclor. However, insulation efficiency may still be excellent, even though the D.C. resistivity may be impaired. Care must be taken to distinguish this particle contamination from the precipita tion of the gas scavenger which occurs at low temperatures.
2. Dielectric Strength
Measure this following the procedure in BS 148:1959. Appendix F. If the dielectric strength has decreased signifi cantly below 40 kV this indicates moisture pick-up, arcing or both and immediate action should be taken. Dielectric strength is a major indicator of the operating efficiency of Pyroclor. Visual and dielectric tests are the only ones necessary for routine inspection and well-sealed transformers have run satisfactorily for 30 years on the original Pyroclor.
3. Moisture Content
Water will migrate from a transformer's solid insulation to the Pyroclor liquid and vice versa, depending on tempera ture. When the transformer is hot, the moisture is likely to be found in the Pyroclor and accounts largely for periodic variations in dielectric strength--higher in winter months. Should the dielectric strength ever drop below 40 kV, measure the water content by the Karl Fischer method in ASTM D 1533-61. Over 70 ppm the dielectric strength of Pyroclor drops below the efficient insulating value and immediate action should be taken.
4. Loss Tangent
The loss tangent (power factor) of a new transformer should range from 1 % to no more than 5%. It is normal to expect the loss tangent to increase in a satisfactorily operating
010^881
71
TOWOLDMONOQ22349
Pyroclor-filled transformer, but the overall loss tangent will not be much beyond 5%. The moisture level and dielectric strength will remain satisfactory.
Occasionally the loss tangent of an unarced, satisfactorily operating Pyroclor-filled transformer may be relatively high, for example 15%. The loss tangent of the Pyroclor will also be high, as much as 50% at 20"C and 50 Hz. If this is the case, check the dielectric strength. If there is a downward trend, this indicates the probability of moisture entry which should be confirmed by the Karl Fischer test
72
for water content.
Reclamation
Provision is made to reclaim the Pyroclor in the event of unexpected deterioration due to minor arcing, entrance of moisture and the presence of other contaminants. Reclama tion services are offered by Dalton & Co. Belper, Derby shire.
The following table gives the typical properties of new and used Pyroclor.
0102682
TOWOLDMONOQ22350
Typical Values found in Pyroclor under various conditions
Inspection check points
Colour
Clarity
Water content
Dielectric Strength at jgo c__ B.S 148 (kV) D.C. restivity at 100 C. 600 v/mm (T O cm)
A New Pyroclor
Light straw
Clear, free from particles 30 ppm
40 kV min
B Pyroclor in property built1 new or rebuilt units prior to use
Light straw
Clear, practically free from particles 30 ppm
40--55 kV
B
After normal operation (a survey of 50 units most 2 to 5 years old, some 10)
D
Non-arced but slightly contaminated Pyroclor in improperly built units,1 new or slightly used
E
Same Pyroclor as in Column 0--after refining
F
Heavily arced Pyroclor due to neglect and internal electrical malfunction
Light straw
Can have blue green or red cast
Cast remains showing extrac tion of soluble colour
Black
Clear, trace of particles
Clear slight amount of particles
Clear free from particles
Contains carbon particles
10--70 ppm, all dissolved water
20--100 ppm,
all dissolved water
30 ppm max
40-51 kV
34--48 kV
40 kV min
Near 152 ppm saturation level plus possible undissolved water
6--17 kV
2
0.04 minimum
0.015 to 0.040
About 0.005
At least 1.5
About 0.003
usually
at least 0.1
Loss tangent (power factor) at 50 c/s 1 kV/mm
100 C (%) 25 C (%)
2 to 5 0.05 to 0.1
10 to 25 0.5 to 2
10 to near 80 0.5 to near 10
30 to near 100 about 7 to over 15
2 to 5 0.1 to 0.2
100 at least 255
' A properly built transformer is defined as one in which the materials of construction are chemically and electrically compatible with Pyroclor. 2 Above data relates to Pyroclor fluid not to the insulation resistance or loss tangent measurements on the transformer itself.
0102083
73
8 Design of Pyroclor-filled Transformer
Compatibility of Construction Materials:
Pyroclor is an entirely different material from mineral oil despite some superficial physical resemblances. For example, Pyroclor will soften and plasticize a number of plastics and resins that are suitable for use in mineral oil transformers. If such incompatible materials are polar, they will ionize to a greater extent in Pyroclor than they would in mineral oil and so adversely affect the dielectric strength. For these reasons, only materials compatible with Pyroclor should be used in transformer construction.
Pyroclor has a greater tendency to "creep" than oil. It is by its nature a more searching and penetrating liquid. For this reason, Pyroclor should not be added either as re-fill or top up to a mineral oil transformer. Conversely, a Pyroclorfilled transformer should not be topped up with mineral oil. Mineral oil is soluble in Pyroclor but any oil present will reduce its fire resistance. It is recommended that a maximum oil content of 2% is not exceeded and mixing of the two coolants is avoided at all times. 74 0102804
TOWOLDMONOQ22352
Coolant Volume
For economy, a Pyroclor-filled transformer design usually attempts to keep the liquid volume required as low as practical because it is more costly than oil. However, even without radical re-design the volume of fluid can be reduced by rounding the corners of the tank. Cooling tubes with oval or star-shaped cross-section will also reduce the fluid volume.
Hermetically Sealed Units
Because oftheir dependability and long service life, Pyroclorfilled transformers are normally hermetically sealed. A sealed unit made with compatible materials, requires no subsequent maintenance or fluid testing. Sealed units will also aflord the most reliable protection against entry of moisture. Sealed units are sometimes designed with "top hat" con struction providing an expansion chamber with air or nitrogen filled space. The gas in this chamber is often sealed in at a slight negative gauge pressure when cold to allow for the expansion of the coolant at operating temperatures. With sealed units, it is customary to install rupture discs for pressure relief. They are constructed to burst at 10, 14, 15 or 18 pounds pressure, plus or minus 3 pounds. They are usually
sired such that the transformer tank withstands 25% over normal operating pressure. An alternative pressure relief system is the use of a spring-actuated pressure relief vent.
Tap Changers
Since frequent arcing deteriorates Pyroclor, it is unsuitable for switchgear and on-load tap changers below the liquid surface are not recommended. The normal construction practice is to provide some form of mechanical interlock on tap changing equipment to prevent it being actuated on load.
Terminal Entry
It is recommended that terminal connections be brought through side walls below the surface of the Pyroclor as free water would tend to float on the more dense Pyroclor. If this is not possible then it is recommended that the terminals be encased in a suitable sleeving to prevent the possibility of a flash over in the rare event that water enters the transformer and migrates to the liquid surface.
0102685
75
j
TOWOLDMONOQ22353
9
Storage, Handling and Disposal of Pyroclor
Drums
Inside storage is recommended to prevent contamination of the product by water. If the drums have to be stored outside they should be stacked on their sides to prevent water accumulating around the bungs and being breathed into the drum during severe ambient temperature changes.
Drum storage areas should be organised so that any leak ages are collected for safe disposal. Partially emptied drums should not be left open to the air and filled transformers should be closed to the air as soon as possible.
Bulk
The supply of Pyroclor in bulk tank car loads, offers many advantages to medium and large volume users, compared with drum deliveries. Unloading, storing and transferring to
76
the transformers is safer, easier, faster and cheaper. Material losses due to spillage and incomplete emptying of drums are eliminated. The possibility of product contamination during handling is greatly reduced.
Even where storage and handling facilities are not at present available, the economics of bulk handling may quickly pay for the tanks and piping systems required.
A booklet indicating the type of system necessary for the efficient handling of Pyroclor in bulk is available from Monsanto.
As soon as a changeover to bulk delivery is contemplated, experienced Monsanto personnel will be available for site discussions regarding the most efficient type of installation for the particular location and an offloading procedure appropriate to that particular installation.
0l*ea<,
TOWOLDMONOQ22354
Ol0287
A modern installation for filling transformers with Pyroelor front a hulk storage tank.
77
TOWOLDMON0022355
Handling Precautions Pyroclor drums and containers carry the following label which gives general instructions for handling:
IMPORTANT
CHLORODIPHENYLS (42%-54%) (or 60%) (PCB)
This product contains POLYCHLORINATED BIPHENYLS (PCB's) which some studies have shown maybe persistent, an environmental contaminant and. possibly, injurious to certain forms of bird, aauatic and animal life. '
PREVENT ANY ENTRY INTO THE ENVIRONMENT THROUGH SPILLS. LEAKAGE. DISPOSAL. VAPOURISATION. RE-USE OF CONTAINERS OR OTHERWISE. SPILLS. LEAKAGES AND WASTE PRODUCT MUST BE COLLECTED. Use of this product must be restricted to applications which can be controlled so that entry into the environment does not occur and to applications in which it cannot come into contact with food, animal feedstuffs or pharmaceuticals. HARMFUL SUBSTANCE IF TAKEN INTERNALLY OR IF IN PROLONGED CONTACT WITH THE SKIN. CAUSES IRRITATION OF SKIN AND EYES. DURING SHIPMENT AVOID SPILLS AND LEAKAGE INTO INLAND WATERWAYS AND THE SEA. Store away from food, animal feedstuffs and pharmaceuticals. Keep container tightly closed. Do not eat or smoke when using.
Avoid breathing vapours, mist or fumes. Do not wear contaminated clothing. Wash product from skin with soap and water. Wash eyes by flushing with water.
In addition to the above we can add that:
1. Animal toxicity tests (small mammals) indicate that acute oral toxicity is low but that acute dermal toxicity may be moderate.
2. When handling the fluid minimise contact with the skin and wash any ofT with soap and water. People with sensitive skins should wear gloves resistant to chlorinated solvents or apply a silicone hand cream.
3. Should Pyroclor accidentally splash or be rubbed into the eyes, they should be rinsed thoroughly with water for a few minutes. It is suggested that all operators be pro vided with safety glasses as Pyroclor will cause pain if it gets into the eyes.
4. Elementary rules of hygiene should be applied--such as not smoking, eating or drinking during handling and contaminated clothing should be discarded.
5. Pyroclor should be handled at ambient temperatures in well ventilated areas. If a Pyroclor-filled transformer is
78
to be opened, it should be allowed to cool down to room temperature before opening it. If hot Pyroclor has to be handled, a respirator with an active carbon canister should be worn.
Disposal of empty drums and waste Pyroclor
Empty drums should not be re-used for anything except scrap Pyroclor. Unwanted empty drums should be dis posed of by a specialised waste disposal contractor familiar with PCB's who will crush the drums and bury them on an approved toxic dump in accordance with local regulations. Handling of Pyroclor in bulk will minimise the problems associated with handling of drums. Waste Pyroclor should be disposed of by special high temperature incineration at 1000X minimum with a residence time of 1.5 seconds or longer or alternatively by a method conforming to local regulations.
Care must be exercised during such disposal and the ultimate use of Pyroclor to avoid pollution, particularly of sewers and waterways.
0102606
TOWOLDMONOQ22356
11 Glossary
of Terms
The following glossary of terms has been designed as an alphabetical ready-reference guide.
Applications
Pyroclor-filled transformers have a wide range of applica tions including steel works, glass factories, public buildings, stores and offices. See pages 5-70. "Uses of Pyroclor-filled Transformers".
Arcing
Arcing will occur beneath the surface of Pyroclor analogous to arcing mineral oil in the event of a major electrical break down. However, the only gaseous product of the decom position of Pyroclor by electric arc is hydrogen chloride which is non-explosive and non-flammable. This compares with the production of hydrogen by arcing under the surface of mineral oil. However, whereas the hydrogen produced with mineral oil tends to cool the arc, the hydrogen chloride produced with Pyroclor does not have this effect and arcing would tend to persist rather longer with Pyroclor than with mineral oil. In the event of small transient arcs taking place, the small quantities of hydrogen chloride which would affect the electrical properties of Pyroclor are absorbed by a gas scavenger which is dissolved in the liquid, but this gas
scavenger is not designed to cope with the large quantities of gas produced in the event of a major internal fault.
Askarel
An askarel is defined as a liquid which is itself fire resistant and does not produce under arc conditions or thermal decomposition mixtures of gases which are themselves explosive or flammable. Askerel is a generic term for a group of fire resistant pro ducts used as electrical insulating media.
Breathers
Where breather transformers are filled with Pyroclor the silica gel breather must be regularly maintained to prevent it becoming water saturated and allowing entry of moisture into the transformer. The fluid in such units should be regularly inspected. (See External Contamination page 68.)
Conservator
If a breather unit is used it would be normal also to use a conservator to prevent loss of the volatile component of the Pyroclor through the breather.
0X02889*
79
TOWOLDMONOQ22357
Class A
PyrtKlor w,t; developed for thi^ class of insulation.
Compatibility of Materials
Pvroclpr is a natural plasticiser for a variety of resins and plastics normally used in oil-filled transformers. If polar, these materials ionise to a greater extent in Pyroclor and so increase dielectric losses.
Cost
Although Pyroclor itself is more expensive than mineral oil and the basic cost of a Pyroclor-filled transformer is still about 30,, greater than that of its oil-filled counterpart, the installed cost can be significantly less as a result of econo mies which can be made in installation. No fire-fighting equipment, fire walls, pebble drains, etc., are required. Siting Pyroclor-filled transformers near the load centre reduces L.V. cable runs and maintenance bills are almost entirely eliminated (see pages 48 to 56 for further details on economies).
D.C. Resistivity
D.C. Resistivity of Pyroclor is lower than that of mineral oil. Thus a low resistivity reading on a Pyroclor transformer, for example 10 megohms, is quite normal and does not indicate deterioration of the fluid. Such a transformer would be entirely safe for service. A reading of 100 megohms would be expected with an oil-filled transformer.
Dielectric Strength
The dielectric strength of Pyroclor is equal to, if not better than, best quality mineral oils and is suitable for the entire temperature range of transformer operation.
Explosion Risk
In the unlikely event of a persistent arc beneath the surface of Pyroclor owing to a major insulation breakdown the tank could be split by the pressure increase due to generation of gases. Pressure relief valves or bursting discs are usually
80
incorporated to safeguard against this possibility. In an oil-filled transformer there is the added possibility of explosion due to ignition of hydrogen evolved during arcing. Only non-explosive gases are evolved when Pyroclor is arced.
Filling
Pyroclor in drums or in bulk is ready for filling trans formers directly. Filling of Pyroclor transformers is best carried out indoors on a dry day and care should be taken to seal the transformers as quickly as possible afterwards to prevent ingress of moisture.
Fire Resistance
Askarels are the most widely used fire-resistant transformer coolant and installations can safely be made in areas where fire risk is considerable, especially indoors.
Gases
Phosgene and chlorine are NOT formed as decomposition products of Pyroclor. The main decomposition product is hydrogen chloride.
Handling Precautions
See page 77.
Heat Transfer
The heat transfer characteristics of Pyroclor are similar to those of mineral oil.
Hydrolysis
Pyroclor is resistant to attack by water; although water will dissolve in Pyroclor and naturally affect its dielectric properties. At room temperature the maximum solubility of water in Pyroclor is about 100 parts per million and Pyroclor normally contains less than 30 parts per million.
Insurance
In some countries fire insurance premiums can be reduced with Pyroclor-filled transformer installations.
0X02890
TOWOLDMONOQ22358
Installation
There is no British Code of Practice covering the installation of askarel-filled transformers. Reference, however, may be made to the Canadian Code of Practice and the National Electric Code of the American Standards Association (1956) Article 450, Section 4522, page 156.
L.V. Cable Runs
Pyroclor-filled transformers can be installed at the load centre and long runs of expensive low-voltage cable are reduced. See "Cost Savings using Pyroclor-filled Trans formers", pages 48-56.
Load Centring
Details of cable economies due to load centring Pyroclorfilled transformers are shown on pages 48-56.
Maintenance
A properly designed, sealed Pyroclor-filled transformer needs no maintenance. Unsealed transformers require inspection. See page 70.
Megger Readings
It is frequently found that megger readings taken on Pyroclor-filled transformers are much lower than those on their oil-filled counterparts. This is a reflection of the very much lower d.c. resistivity of Pyroclor compared with mineral oil.
Noise
Pyroclor-filled transformers are quiet in operation because of the effective dampening of core noise by the high density coolant.
Over-Voltage
Pyroclor-filled transformers can be installed where over voltages due to lightning or switching surges may occur.
Oxidation
Pyroclor has exceptional resistance to oxidation. If an askarel-filled transformer is operated under normal con ditions the fluid need not be changed or filtered during the life of the transformer, page 64.
Permittivity
Compared with the permittivity of mineral oil that of Pyroclor is much closer to the value for cellulose, leading to greater uniformity of stress in impregnated press board and paper windings.
Reliability
Properly designed and installed, askarel-filled transformers will give trouble-free service fora minimum of 30 years. Since their introduction in 1932 the manufacturers report finding the overall failure rate to be less than 0.5% for all units under test and service conditions.
Refilling Oil Units
The replacement of existing oil filling in transformers is not generally recommended since Pyroclor may attack the gaskets and many of the sleeving materials, paints and varnishes commonly used with oil. Accordingly, leakage may occur or electrical breakdown may result. In theory, if all materials could be replaced with Pyroclor resistant materials, then the oil could be replaced by Pyroclor.
Sealed Transformers
Properly designed, sealed transformers need no maintenance. These are usually hermetically sealed with an air or nitrogen space to allow for expansion.
Siting
Examples of economies achieved by siting Pyroclor-filled transformers indoors, close to the load centre, are given on pages 48-56 and are available separately in detail from Monsanto.
81
TOWOLDMONOQ22359
Size
Pyroclor-filled transformers are usually a little smaller and more compact than other units and can operate at higher voltages than air-cooled transformers.
Solubility
Water is slightly more soluble in clean Pyroclor than in mineral oil, but solubility in used or unused Pyroclor is much the same (solubility approximately 130 p.p.m. at 30C. as opposed to approximately 90 p.p.m. at 30C. in new mineral oil).
Space Saving
Well-sealed transformers can be used in dusty or corrosive atmospheres in such spaces unsuitable for other equipment e.g. Pyroclor-filled transformers have been installed close by a battery of blast furnaces.
Switchgear
Pyroclor is unsuitable for use in switchgear since arcing produces hydrogen chloride gas which in moist atmospheres might cause attack of the metallic parts of the switchgear.
Tap Changing
On load tap changing beneath the surface of the Pyroclor will result in the formation of hydrogen chloride gas and carbon. It is therefore not recommended.
Thermal Stability
Pyroclor is thermally stable up to 175C. Small quantities of hydrogen chloride are produced above this temperature but are absorbed by the gas scavenger, preventing attack on the iron core or cellulosic insulation. 82
0102892
Toxicity
Animat toxicity tests indicate that acute oral toxicity is low but that acute dermal toxicity may be moderate. See page 77.
Vapour Pressure
The variation of vapour pressure of Pyroclor and Pyroclor ETR with temperature is shown on page 62.
Viscosity
Pyroclor has been blended to match the viscosity-temperature characteristics of mineral oil (see page 62).
Voltages
Askarel transformers working at 120 kV have been made, but most work in the region of 11 kV since this is the usual level of distribution voltage. The majority of units, normally working indoors, are found in the range between 50 kVA and 4 MVA.
Volume Reduction
For successful transformer design using Pyroclor it is desirable to keep the liquid volume to a minimum to save cost. Useful economies can be made with round corner tanks, oval or star-shaped cooling tubes. Dead space fillings such as low resin wood or even glass marbles have also been used.
Venting
If Pyroclor-filled transformers are installed in confined spaces it is normal to vent the transformer to atmosphere. The vents are closed by rupture discs. Although there is no Code of Practice in the U.K. for the installation of Pyroclorfilled transformers, this recommendation is in line with the Canadian Code of Practice covering the installation of such transformers. The National Electrical Code of the American Standards Association (1956). Article 450, Section 4522, page 156, also deals with the installation of askarel-filled transformers.
11-20(E)M-E-2(6/72) Printed by Richard Madley Ltd.. London. N19 4AG.