American Society of Heating and Ventilating Engineers Guide, 1932
Fig. 41 illustrates another typical blast heater piping hook-up frequently
encountered, but with which only the return ends have auxiliary air vents. It is to be noted that while the two super-imposed heaters may. drain to
a trap common to both, the successive layers of heaters with reference to the air flow from the fan should each have a separate trap, since the condensation rate varies in each successive layer after its predecessor has warmed the entering air.
5
Chapter 10
Unit Heater Connections
When unit heaters are used with steam heating systems the designer
DEVICES FOR HANDLING CONDENSATE
must always take into consideration the great condensing capacity of these devices. They must be placed high enough above the boiler water
AND AIR
line to compensate for the pressure drop or must be used with systems having pumps or other positive return devices, and must always have
i
Weight of Condensate; Condensation
pipe connections proportional to their maximum heat emission. Some typical details, of unit heater connections are shown in Chapter 35.
i
Pumps; Vacuum Heating Pumps; Traps.
Equalizer Connection
Low pressures may be produced in the supply piping and in the boiler
THIS chapter deals with certain proprietary devices used with steam heating systems. Other equipment and accessories for steam systems, such as boilers, radiators and piping are treated elsewhere in The Guide.
of any well-built vacuum heating system by means of the vacuum of con
Information concerning specific products will be found in the Catalog
densation. This may prevent drainage of the heating units to the pump
Data Section. The Hydraulic Society's Standards give descriptions of
despite the efforts of the vacuum pump.
pumps for various services, standard equipment and installation data.
It is desirable, therefore, to install a cross-connection with a check valve between the supply main and the vacuum return main, which will:
1. Prevent such an induced vacuum in the supply main exceeding the vacuum in the return main, by opening a check valve to equalize the pressures in the two mains.
2. Allow a higher vacuum to be carried in the return main than in the supply main by keeping the check valve closed.
S t
In the selection of devices for handling condensate it is, of course, necessary to know the weight of condensate to be handled. For systems employing the use of direct radiators, the normal rate of flow is 0.25 lb of condensate per square foot of equivalent direct radiation (EDR) per hour. However, an allowance must be made for the increased rate of condensa
tion during heating-up periods.
This device has solved many complaints, especially where oil or gas
fuels are used.
IMPORTANCE OF LAYOUT
^
The rate of condensation per square foot per hour for a cast-iron column type radiator for the time elapsing after the steam is turned into the radiator is given by Fig. 2, Chapter 6. The maximum- rate of condensa tion occurs about 10 minutes after steam is turned into the cold radiator
With the increasing use of automatic temperature control, the proper layout of the steam mains to secure even distribution of the steam to all the radiators is of importance. It is not sufficient that the pipes be properly designated to carry the maximum amount of steam. Steam heating systems are operated at- their maximum capacity only for a fraction of the time and they should be designed to distribute evenly at reduced capacity. Almost any piping layout will give heat in sufficient quantities to all the radiators for zero weather if the pipes are large enough, but this is only one of the requirements; the system must be capable of operating efficiently at reduced capacities. Hence the importance of careful and
i
,
and amounts to approximately 3J^ times the normal rate. At the end of about 25 minutes the radiator reaches a normal rate of condensation. The average rate of condensation during the first 20 to 25 minutes as found by integrating the area under the curve and determining the mean ordinate is 0.50 lb per square foot per hour or twice the average rate. With, pressed metal or pipe coil radiators the condensation rate would be somewhat less due to the fact that the weight.of metal being heated is less per square foot than with the cast-iron types.
The normal weight of condensate to be handled from indirect or central fan systems may be estimated by means of the following formula:
intelligent arrangement of the steam mains.
Q X 60 x T 55.6.X Afg
(1)
where
.
W = weight of condensate, pounds per hour. Q = volume of air, cubic feet per minute. T -- temperature rise of air, degrees Fahrenheit, f'fg = latent heat of steam in the system, Btu per pound.
166 167