CHAPTER 36
1946 Guide
A spray type remote unit is illustrated by Fig. 5. Many designers prefer the air washing and coil wetting features. Air is circulated by means of attached or built-in fans, delivering the conditioned air through a system of ducts, which include outside air connections if desired.
Some types of units, mostly those suitable for suspension, employ a propeller fan such as in Fig. 6. These are located in the conditioned area, are without ducts and seldom do more than cool and dehumidify, since the propeller fan is not designed* to move air against high pressure. Generally these units are provided with a lint screen instead of filters to limit resistance to air flow.
Individual floor mounted type remote units are available for use in
offices or hotel rooms. Similar in appearance but somewhat smaller in
size than the self-contained room unit, this form of equipment may be
grouped:
,
1. Mechanical, year 'round type containing blowers, filters, humidifiers and coils, with outside air connection. Manual or automatic controls provided with each unit.
OIS^kIrGI
Unit Air Conditioners, Unit Air Coolers, Attic Fans,
633
%
Application
In the application of unit air'conditioners it is important to consider several factors:
1. Location of equipment. 2. Air distribution. 3. Multiple units versus central station system. 4. Multiple remote unit system versus a self-contained unit system. 5. Methods.of control. 6. Methods of conserving water. 7. Code limitations.
In choosing locations for air conditioning units, consideration must be given to the characteristics and use of the conditioned space; , type-of system contemplated; duct locations; sources of power, water, refrigera-
Fig. 4.. Horizontal Remote Type Unit'Air Conditioner
Fig. 5. (right) Spray Type Remote Unit Air Conditioner
2. Mechanical, semi-year `round type with .no outside air connection, containing blowers (filters optional), and coils. Usually- used where there is an existing radiation or ventilating system. Controls provided with each unit.
. 3. Non-mechanical type containing coils, using air ejected under pressure from a remote source for inducing circulation over coils '(see Chapter 43). Manual or auto matic control of air temperature only is provided. Both summer and winter air con ditioning functions may be performed by the one unit.
One coil for cooling and heating may be provided or a single coil used, through which hot water in winter and cold water in summer is circulated.' All three types of systems require remote sources of refrigeration, with' the first group obtaining outside air from the window, the second group having no outside air unless used in connection with a central plant or ventilating system and in the case of the third group, all. air delivered under pressure is outside air.
Various combinations or alterations of these room units are available. Different filtering,- humidifying and air delivery methods are employed, to achieve the desired conditions. A typical remote floor type room unit air conditioner is shown in Fig, 7. -
Fig. 6. Suspended Propeller Fan Type Unit Air Conditioner
tion, heating and drainage; and accessibility of equipment and system"
for maintenance.
Where units are' placed within the conditioned area, particular atten
tion must be given to air distribution, sources of outside air and con venience to service sources and facilities previously noted. Skill and ingenuity are required to produce a neat appearing, inconspicuous job
without sacrificing quality from an engineering point of view. This may , be accomplished by building the units into the woodwork or walls, and refinishing them to match existing furniture and fixtures. Where location
of equipment outside of conditioned space is possible, use may be made, of storage rooms, halls, basements or any space less valuable than that to be conditioned. Less emphasis need be placed on the appearance of
equipment.
.
The choice of equipment location is frequently influenced by the relative cost of long runs of insulated ducts required in order to locate units near refrigeration sources, as compared with short duct runs but long extensions of service facilities. Gare must be taken that equipment will not be damaged by climatic conditions.
Air distribution from units located within the conditioned area is by means of grilles, either fixed or adjustable and mounted in air distribution.
headers, either furnished with the unit or constructed-at the installation to meet the needs of the application under .consideration. A system of ducts and distribution grilles.may also be used, similar to the arrangement.