CHAPTER 9
1962 Guide And Data Book
Sizing: The vessel pressurized by steam should be sized for a total volume Vr which is the sum of the volume Vi required for the steam space, the volume V required for water expansion, and the volume F* required for internal headers or piping, sludge and reserve. An allowance of 20 percent of the sum of Vj and F is reasonable for the volume V,, required for the steam space.
The volume F* required for water expansion is determined from the change in water volume from the minimum operating tem peratures to the maximum operating temperatures of the com plete cycle, it is not necessary to allow for expansion of the total water volume in the system from a cold initial start. It will be necessary during a start-up period to bleed off the volume of water due to expansion from the initial starting temperature to the lowest average operating temperature.
The volume V, for internals, sludge, and reserve varies greatly depending upon size of system, design of internals and desirable allowance for sludge and reserve. For smaller systems with mini mum internals an allowance of 40 percent of the volume Vt required for water expansion is reasonable. For larger systems with horizontal tanka and complete internal distribution piping arrangements the allowance goes as high as 80 percent of Vt.
4. The simplest type of gas pressurization system uses a fixed Quantity of pas in a separate expansion vessel which accommodates the change in water volume. In this case, the pressure within the gas space varies with changes in water level in the expansion vessel. As the average system water temperature increases on partial load operation, the expansion of the system water into the vessel compresses the inert gas, raising the system pressure. The reverse condition takes place on a drop in average system water temperature. The pressure is permitted to vary from a minimum point above saturation to a maximum determined by the ma terials used in the system.4
Sizing: The vessel should be sized for a total volume Fr which is the sum of the volume Ft required for pressurization, .the volume Vt required for water expansion, and the volume V, re quired for sludge and reserve.
Reasonably accurate calculations may be made on the h**TM of pressure-volume variations following Boyle's Law, assuming that the tank operates at a relatively constant temperature. The minimum gas volume can be determined when the expansion volume V%, the minimum tank pressure Pi, and the maximum tank pressure Pt, are known. The gas volume varies from the minimum (F) to a maximum which includes the water expansion volume Vt.
The minimum gas volume Vt can be obtained from the follow ing equation:
F, - PtVt/(Pt ~P{)
where the units of Pi and Pt are An allowance of 10 percent of the sum of F, and F, is reason
able for the sludge and reserve capacity, F. The volume Fj required for water expansion should be limited to the actual expansion which occurs during system operation through its minimum to maximum operating temperatures. It would 'be necessary to bleed off water during a startup cycle from a cold start. It is generally practicable on small system* such os under 1,000,000 to 10,000,000 Btub, to size the expansion vessel for the total water expansion from the initial fill temperature.
The ratings of fittings, valves, piping and equipment is "a
consideration in determining the maximum system pressure.
The greater the maximum system pressure the smaller the
size of the expansion vessel. The savings in the cost of the
vessel, however, may be more than offset by the increase in
cost of the other elements of the system. It is suggested that
a minimum pressure be selected which is about 25 to 50 psi
over the maximum saturation pressure. In checking the ratings
of valves, pipe and fittings, it will be necessary to determine
the specific rating rating point for the given application. For
example, standard 300 psi steel fittings and valves are rated
at a temperature of 850 F. The pressure rating for a standard
300 psi steel valve when operating at 400 F is 665 psi. There
fore, it is generally not necessary to use steel valves and
fittings over 300 psi ratings in HTW systems. Similarly, stand
ard 150 psi steel fittings and valves can usually be used in
BJ'sterns operating as high as 325 F.
The expansion vessel is connected to the suction side of the
HTW pump, preferably as close as possible, by mean? 0f a
Fig. 5 .... Inert Gas Pressurization Using Variable Gas Quantity
balance line. The inert gas used for pressurization is fed into
the top of the cylinder, preferably through a manual fill
connection using a reducing station connected to an inert gas cylinder.
The basic HTW pumping arrangements may either be the
single-pump type, where one pump handles both the genera
tor and'system loads; or two-pump type, where one pump
circulates HTW water through the generator and a second
pump circulates HTW water through the system.
The use of air as the gas for pressurization is not recom
mended. Nitrogen is the most commonly used inert gas, as it
is readily available at a reasonable cost. This method of
pressurization has the greatest advantage in its relative sim
plicity, ease of control, and flexibility. There is no flow in the expansion vessel, which generally remains coo) and need not be
insulated.
:
Also used as a method of inert gas pressurization is a system
which employs a variable gas quantity (see Fig. 5).* In this
system the inert gas is relieved from the expansion vessel on
a rise in water level into a low pressure gas receiver. A gas com
pressor pumps from this low-pressure into a high pressure
receiver for storage. When the water level drops in the expan
sion vessel, the control cycle adds inert gas from the high
pressure receiver to the expansion vessel to
the re-
High-Temperature Water Systems
141
-yjjed preffiure. This system is somewhat more complicated and should be analyzed on the basis of the economics involved for each application. Generally it is more applicable to large
cental systems-
Arrangement of Direct-Fired Generators
The method of integrating the high-temperature water generator into the high-temperature water heating circuit Spends on the type of generator and the method of pressuriza-
t^Where the generator is a steam boiler with an integral steam
drum used to absorb the expansion of the water level and for prtsurization, a dip pipe is generally employed to take the water out from below the water line (see Fig. 6).` This dip pipe should be so ngfadll that it picks up water at or near the saturation temperature, but without too many steam bubbles in it, and that in the event of a pipe break somewhere in the system the boiler is not emptied to a point where heat ing surfaces are bared and the danger of a boiler explosion results. Equal precautions must be taken with the return pipe. If.the return pipe is connected in tire lower part of- the boiler, a check valve should be placed in the line connecting to the boiler to preclude the danger of emptying the boiler.
When two or more such boilers are used to supply a com mon system, means must be provided to maintain the same gfrai-n pressure and water level in each. Water and steam
pipes are usually installed between the drums (see Fig. 7). These should be liberal in size. Recommended sizes are shown in the following table.
toiler Eating MOEoat Btub
2.5 5 10
15 20 30
Bufancn Pipe 0to, lodtes
3 3H 4
6 6 8
It should be noted that a difference of only ^ psi in the system pressure between two boilers operated at 100 psig would cause a difference of 9 in. in the water level. The.situation is further aggravated by the fact that an upset is not self balancing. Rather, when too high a heat release in one of the boilers has caused the pressure to rise and the water level to fall in this boiler, the decrease in the flow of colder return water into this boiler will cause a further pressure rise, and the opposite will happen in the other boiler. It is therefore of
^ Piping Connections for Two or More Boilers In High-Temperature Water Systems Pressurized by Steam
primary importance that the firing rates match the flow through each boiler at all times.
Although some existing high-temperature water plants have up to 12 boilers operating in parallel, the trend is away from connecting more than two boilers in this manner. Mod ern practice is to employ cither flooded high-temperature water heaters with one external steam drum common to all the generators, or the combination of steam boilers and direct contact heaters.
The matching of firing and flow rates is less critical in flooded boilers operated in parallel. These boilers may carry some steam provided there is no restriction which prevents the steam that is generated from finding its way to the steam space of the drum. In systems pressurised by gas, the imposed additional pressure-head above the vapor pressure of the water is normally sufficient to prevent any steaming. This system therefore requires no means of separating the steam from the water. The expansion tonlr is usually placed on the boiler house floor.
Relief valves, drain valves, gages, thermometers, and fill connections for HTW generators should be selected with spe cial attention to the fact,that they are for HTW service. The baric HTW system operates at a relatively constant pressure with a wide variation in temperature, whereas the ordinary steam cycle operates at varying pressures and temperatures which generally rise and fall together. Trim items designed for steam may not be satisfactory when used on a HTW ap plication.
Expansion tanks used for inert gas pressurization cycles can be a simple vessel built to conform to the ASME Unfired Pressure Vessel Code, as required by the system characteris tics. Locating the relief valve below the minimum water line is an advantage since it is easier to keep the relief valve tightly sealed with water on the pressure side than if it is lo cated above the water line and is exposed to the inert gas of the system. Vertical tanks may be used to advantage since the space problem and mounting and support problem is amplified.
Expansion tanks for steam-pressurized cycles require careful design. They need to be mounted as high as practicable to give the maximum NPSH to the HTW pumps. The HTW supply from the generators should be introduced through relatively small holes by means of a perforated internal distributing pipe. The pump intake line should be located as far as possible from the return water connection and at least 6 in. below the nor mal water line. This pump intake line should have a serrated, entrance connection or similar construction to break up vortex formations at this point. The tank is normally mounted horizontally and an aspect ratio of 3.5 to 1 is generally used to accommodate the internal piping described. This tank is normally insulated. Present practice indicates that a minimum vessel diameter of approximately 6 ft is required to accommodate the internal piping and achieve stable operation.
Direct Contact Heaters
High-temperature water may be obtained from direct con tact heaters in which steam from turbine exhaust or extrac tion or from steam boilers is mixed with return water frorp the system. (See Fig. 8.) The mixing takes place in the upper part of the heater where the water cascading from horizontal baffles comes in direct contact with steam.*
The steam space in the upper part of the heaters serves as the steam cushion for pressurizing the system. The lower part of the heater serves as the expansion tank for the system.
Where the water beater and the boiler operate under the same pressure, the surplus water is usually returned directly