144 CHAPTER 9 1962 Guide And Data Book fig. 12 .... Correction of fig. 11 for Water Temperature 180 F or 200.to 250 F) depending upon how close they are . to the occupants and upon the pressure for which they are designed. The water velocity through the heating equipment affects its capacity. This must be taken into account in se lecting the equipment because, if a large water-temperature drop is used, the rate of circulation is reduced and conse quently the velocity of flow may he reduced sufficiently to lower appreciably the rate of heat transfer. High-Temperature Water Systems 145 Convectors, specially designed to provide low surface temoeiatures, are now available to operate with water tempera- in the 300-400 F range. The h'gh temperatures of these systems make them ideally gulled for direct use in radiant panel surfaces. Since radiant rtiitout is a fourth-power function of the surface temperaiare, the surface area requirements are materially reduced over low temperature water systems. The surfaces may be gat panels consisting of a steel tube, usually % or in., gelded to sheet steel turned up at the edges for stiffening. Several variations of this are available. Steel pipe may also b$ used with an aluminum, or similar, reflector to reflect the heat downward and to prevent smudging of the surfaces above the pipe. TEMPERATURE CONTROL On steam-pressurized cycles, the basic control of the firing rate to the generator should be from the temperature of the water leaving the generator. A master pressure control oper ating from the steam pressure in the expansion vessel should be incorporated as a high limit override. Inert-gas-pressurized systems should be controlled from the generator discharge temperature. Combustion controls are discussed in detail in Chapter 42 of the 1961 Guide And Data Book. In the water-tube generators most commonly used for HTW applications, the flow of water makes the pass through the generator in a matter of seconds. The temperature controller must have a rapid response to maintain a reasonably uniform leaving water temperature. It is rarely required that this temperature be held closer than phis or minus 5 F deg, but greater swings may occur if the location of the sensing element and the controller itself do not sense and react quickly enough. Simplicity of control is recommended. Due to the rapid response through the generator, some form of modulation of combustion rate is necessary on all systems having a capacity of over a few million Btuh. In the smaller size range this can take the form of high-low firing. In large systems, particularly those used for central heating applications, full modulation of the combustion rate is desirable through at least 20 percent' of full capacity. On-off burner control is generally not used in steam-pressurized cycles since the system loses pressurization during the offcycle, which can cause flashing and cavitation at tire HTW pumps. All generators should have separata safety controls to shut down the combustion apparatus on high system pressure or high water temperature. HTW generators require a minumum water flow at all times to insure against tube failure. Means should be provided to measure the flow and to stop com bustion if flow falls below the minimum value recommended by the generator manufacturer. For inert-gas-pressurized cycles, a low pressure safety control should be included to shut down the combustion system in the event of loss of pressurization. Fig. 13 shows the baric schematic control dia gram for a HTW generator. For large centre} distribution systems, it may be desirable to provide flow sensing means to shut down the combustion apparatus in the event of a line break. Further protection can be attained in such cases if automatically closing flow valves are installed in the main ,distribution system to seal off the jhre to prevent loss of water. An automatically controlled bypass valve at the central plant would then assure continu ous flow within the central plant equipment during the period of tone required to shut down and cool off the generatore, buch line breaks on underground distribution systems are re^ possibilities, and this protection would normally be fconsidered only on extensive or special systems. ktw sum.* i -messute t -thermometer T-l-0l*C*AR6 TEMP CONTROLLER (PMMRTIOWUJ ru - otreuKTUL rressure cm AND LOW fLOW CUI-OUT p-l - MSN PRESSURE cur-our T-t - msri TEMPERATURE CUT-OUT f-2 - LOW PftESSIRE CUT-OUT fig. 13 .... Control Diagram for High-Temperature Water Generator Valve selection and sizing are very important because of the relatively high temperature drops and smaller flows en countered in high-temperature water systems. To obtain . good control, the valve must be sized so that it is effective over its full range of stem travel. It is recommended that the valve size be selected on the basis of a pressure drop at full flow equal to approximately 50 percent of the pressure dif ference between supply and return mains at the location of the equipment served. The pressure drop across the valve must not be sufficient to result in a downstream- pressure below the saturation pressure at the temperature existing at any point or flashing into steam mil result. A valve with equal percentage flow characteristics is desirable. Sometimes two small valves are used rather than one large valve to improve the controllability of the system. Stainless steel trim is recommended, and all valve body materials and packing should be suitable for the high temperatures and pressures encountered. The valve should have a close-off rating at least equal to the maximum head produced by the circu lating pump. Generally, two-way valves are more desirable than the three-way type because of the equal percentage flow characteristics and the smaller capacities available in two-way valves. Single-seated valves are recommended-in preference to double-seated valves since the latter do not provide tight dosing. - Control valves preferably should be located in the return lines from beat transfer units in order to reduce the valve ' operating temperature and to prevent the high-temperature water from flashing to steam at the lower discharge pressure. Sometimes valves are located as low as practicable to in crease the static head at the valve and further minimize the possibility of flashing. This problem is minimized in sys tems pressurized by inert gas, since a greater difference is maintained between the system and saturation pressures.' A typical application is the control of the temperature of water leaving a heat exchanger in which high-temperature water is used as the heating medium. The temperature measuring element should be located where it can best detect changes and thus prevent overheating of the outlet water and possible flashing. When the measuring element is~located in the leaving water, there must be a continuous flow through the exchanger and past the element. If the water leaving the exchanger is used for space heating, the set point of the thermostat in this water (which controls the temperature of the leaving water by controlling the inlet temperature to the exchanger) can be readjusted in accord ance with outdoor temperature. 1 *i I