Document o967zEk9mNNp38vj6X7O1BN0r

American Society of Heating and Ventilating Engineers Guide, 1934 Dust and Cinder Catchers8 The various types of dust and cinder catchers available today can be divided into six general classes: 1. Settling.chambers. 2. Dust and cinder traps. 3. Centrifugal separators. 4. Electrostatic precipitators. 5. Gas scrubbers. 6. Fabric filters. The selection of the proper type of catcher calls for a careful study of the material to be caught and the draft and space available. After installation, constant vigilance is necessary to keep.the catchers in proper working condition if satisfactory operation is to be obtained. If possible, the dust or cinder catcher should be installed on the inlet side of the induced draft fans because the dust and cinders in the gases seriously erode the wheels of the fans, the inlet connections and the scrolls. Where the induced draft fans operate at high tip speeds and no catchers are installed, it is not uncommon for the fans to require major repairs within one year and complete replacement within five years. Settling Chambers Probably the oldest form of dust catcher is the settling chamber, which generally consists of a large-sized, gas-tight space into which the dust-laden gases are discharged before being delivered to the chimney. The velocity of the gas should be reduced to a point where the larger and heavier particles will be precipitated by gravity. For good operation, the velocity of the gas should be reduced to a maximum of 2 fps. The bottoms of the chambers should be provided with dump plates through which the collected dust can be removed. Because these chambers are not effective in removing the finer dust particles they have been practically superseded by smaller and less costly devices. Traps, Catchers, Precipitators Various types of traps have been devised. In general they all depend upon breaking the gas up into thin strata and subjecting those thin strata to several abrupt changes in direction. The dust is thrown out of the gas stream into specially shaped pockets, or impinged against a roughened surface. The trapping pockets are drained into a hopper below with a small quantity of gas and the dust settles out by gravity due to the low velocity in the hopper. In the roughened surface type, various sections of the trap are closed off at intervals by means of dampers and the dust is shaken off the roughened surface into a hopper below. These devices work very well in catching large size dust and cinders and trap much of the fine dust. They have been used most extensively on stoker-fired installations. They have the advantage of low pressure drop, relatively small space requirements, and low first cost. See Smoke and Dust Abatement, by M. D. Engle (A.S.H.V.E. Transactions. VoI. 37, 1931). 2X4 ii.- Chapter .15--Air Pollution Centrifugal catchers obtain separation by projecting the particles tangentially out of the gas stream. The effectiveness of this type of catcher varies directly as the specific weight of the dust and as the square of the tangential velocity, and inversely as the radius of rotation. Electrostatic precipitators are used for catching fine dust. These precipitators consist of dust-tight chambers in which are suspended rein forced concrete slabs on about 10-in. centers. Between the slabs are suspended bare metal rods. High-voltage unidirectional current is applied to the reinforcing rods in the concrete slabs acting as positive electrodes, the bare rods acting as. negative electrodes. The dust-laden gas Hows horizontally through the precipitator and the dust particles migrate toward the concrete slabs to which they adhere and then fall or are scraped off into the dust hoppers below. Gas Scrubbers Wet scrubbers have been used for many years for removing dust from gases. A number of different types of scrubbers are now being built for removing dust from boiler flue gases: One type depends upon saturating the gas and washing the dust out of suspension by a spray of water. For best results with this type, the Water should be atomized into as fine a spray as possible. Another type depends upon splitting the gas into thin strata and subjecting these strata to a number of abrupt changes in direction, throwing the dust against the wet surfaces. The main problem in develop ing a satisfactory wet dust catcher is to find suitable materials of con struction that will resist the corrosive action of the wash water for a reasonable length of time. Fabric Filters Filters of many kinds have been used with variable success. The filter bags are made of cotton, wool or asbestos fabric. The fabrics used in' these filters do not withstand the temperatures at which gases are usually discharged from the boilers, and hence the gases must be cooled by some means. Surface coolers or water sprays can be used for reducing the gas temperatures. One of the serious objections to all of these dust catchers is the relatively high cost of installation and maintenance, and the space required for installation. Disposal of Dust and Cinders Even after the dust and cinders have been caught, the disposal of the material caught presents a serious problem. The cinders discharged with the gases from stoker-fired boilers are usually very high in carbon and contain from 50 to 80 per cent as much heat per pound as the coal which is being' burned. It is possible, and usually economical, to burn these cinders. They cannot be satisfactorily mixed with the coal in the stoker hopper but they can be blown into the furnace over the stoker fuel bed and burned satisfactorily. If a sufficient quantity of cinders is caught, a small unit pulverizer can be installed to prepare them for burning over the stoker fuel bed. ~ The same pulverizer can be used for coal at times of 215 N/