Journal of Clooinnioyni/'li v, IS') (1`J.SO) 41.5 42 7 in I Ncvivr Scicttiilic I'lthlisliinn Company, Ani>krJ;ini -- Primed in Tins Nctlurtluntls
cnuom. i:,.i:o
*9
Not*
Cm chromatographic method for the analysis of polychlorinated biphenyls in transformer oil*
J. N. OGATA. J. D. OKUN, J. W. UYLJN ami A. REVENUE Department of Agriruhnral Diochetnhtty, University of Hawaii, 1800 Cast- West Itiuul, Honolulu, Hawaii 96922 (U.S.A.) (Keraivtil September 25tli, 1979)
Polychlorinated biphenyls (PCBs) arc widely distributed in the environment ami arc ubiquitously present in birds, iish. mammals, soils ami water. One source of entry of PCM* into the environment may be from the improper handling and disposal of PCB-contammalcd waste oil from old or discarded transformers'. New rotes under the provisions of the U.S. Toxic Substances Control Act*, to protect the environment from further contamination by PCBs, have been implemented by the U.S. environ mental Protection Agency1 \ The rules prescribe marking and disposal requirements for PCBs and PCB items that contain 50 ppm or greater PCBs. Transformers with dielectric Ituid containing I'CUs in excess of 500 ppm arc classified ns PCR trans formers find arc subject to marking and disposal regulations; those which contain between 50 and 500 ppm PCBs are categorized as PCB-contaminatcd transformers and arc exempt from the marking requirement only. Transformer* whose dielectric fluid contain less than 50 ppm PCB arc classified as non-PC B transformers and a disposal rule applies only if it contains a detectable concentration of PCB. To properly label and dispose of these oils, an analytical procedure was required for the routine testing of the oils for PCBs. Methods available*-" for PCI! analysis were examined, but problems were encountered with time-consuming and inadequate cleanup procedures. Therefore, a simple analytical method was developed and is the substance of this report.
This method for the routine analysis of PCB residues in transformer oil, with a sensitivity of I ppm, utilizes silica gel to isolate the PCBs from the oil. Other adsorbents, such as Plorisil, charcoal, and alumina produced less satisfactory sepa rations.
MATERIALS AND MLTHOOS
Woclu* silica gel, 70-150 mesh, obtained from 1CN Pharmaceuticals. Cleve land. Ohio, l:.S,A.f was healed overnight al 130* before use. Sodium sulfate was anhydrous, gumilar, and reagent grade. Reagent grade ^-heptane was redistilled in an all-glass apparatus.
* JMurn.il aeues No. 'ix of tU Hawaii Agtieullural Usp uncut Station.
HONS 002717
426
NOTES
NOTES
A Hewlett-Packard Model 5750 gas chromatograph equipped with a tritium electron capture detector was used Tor the analysis under the following conditions: 4 ft. (1.22 m) X 4 mm 1.17. borosilicate glass column containing 3% SE-30 silicone on high-performance grade Chromosorb W (80-100 mesh); column temperature 200, injector port temperature 210", detector temperature 208'*; carrier gas was argonmethane (90:10) at a now-rale of 60 ml/min. PCBs (Aroclors*) 1248, 1254, ami 1260 were kindly furnished by Monsanto, St. Louis, Mo., U.S.A. Solutions of the PCBs for gns chromatography (GC) were prepared in heptane and contained 1-5 nj>//d.
A chromatographic column (250 x 12 mm I.D. with a 125-ml reservoir. Cat. No. K-422250), obtained from Kontes, Vineland, N.J., U.S.A., was prepared by first inserting a plug of glass wool followed by the addition of 1 cm sodium sulfate, 10 cm hot silica gel, and topped with I cm sodium sulfate. The column was pre-wet with 50 ml Itcplnnc. A l-ml volume of oil solution (cquiv. 0.25 g sample), prepared by diluting 2.5 g of transformer oil to a 10-ml volume with heptane, was added directly onto the surface of the sodium sulfate in the column. The walls of the column were rinsed with 1-2 ml heptane. At the moment the heptane rinse entered the surface of the sodium sulfate. 75 ml heptane was added to the column and the How-rate was
adjusted to I ml/miu. Tltc first 20 ml of cluatc, which contained the non-polar oil components, was collected in a 25-ml graduated cylinder and discarded. The nest 30 ml of ciuutc. which contained the I'CUs, was collected in a 50-mi graduated cylinder, transferred to a 100-ml round bottom flask and evaporated to dryness on a Rinco vacuum evaporator at a water-bath temperature of 60*. The residue was transferred with heptane to a 2-ml volumetric dusk, made to volume, and 5 /<! was injected into the gas chromatograph. The PCBs were quantitated by comparison of peak heights in the unknown with those of commercial PCB preparations.
With this method, approximately 90% of the oil was eluted from the cleanup column in the first 20 ml of heptane: All of the Aroclors 1254 and 1260 and a major portion of 1248 were eluted in the next 40 ml; an additional 10 ml was required to completely elute the more potar components of Aroclor 1248. Three different com mercial batches of Woclm silica gel were used and the required eluting volumes for each hutch were (he same, which indicated a uniform product.
The GC patterns of the PCBs observed during the analyses of 138 transformer oil samples resembled those of tltc Aroclors 1248, 1254, and 1260. Of the 56 samples which contained >5 ppm, Aroclor 1260 was observed in 43 samples, Aroclors 1254 and 1248 in 5 samples cuch, and 3 samples had PCB patterns which indicated a mixture of Aroclors 1248 and 1260. Eighty-two samples contained less than 5 ppm PCBs, 14 samples had amounts ranging from 50 to 500 ppm, and 8 contained more than 500 ppm. The highest amount of residue found in one sample, was 5020 ppm or Aroclor 1260.
The recovery of the individual Aroclors from oil samples fortified at levels ranging from 5 to 2000 ppm averaged 95%. The limit of detectability was I ppm.
The method described here is simple and requires less than 2 h to cleanup a series of 8 samples.
.1 ht-iJ. Xrtor.X] <197* WJ
4 htt.
. 4J< 197* X*
5 Fol. Hi gitf,, 44 <197* MS
6 J. A. Armour amt 1. Al
7 O. W. Sera, P. L. Dmo*
t A. V. HoMen Md K. M*
9 L. M. Reynold, ft* Jbm
10 l. M. Reynolds, infee $
11 Mtuhtni fur Frnlychtmimmt
tion A*ency, National feet
Cincinnati, Ohio, I97X
RClIUtNCrs
1 ChvtHRvI HVrit, 122
15.
2 Pub. L. 94-169, 7'n.viV .W*.rnrrv CiMHot. Avt. W Sim. KM).I,
I, 1976.
HONS 002718
NOTES 3 *W. Ht'xhl.. 43 (H7X) 7150. 4 Iht. Rrtilst., 43 (107*) .1301*. 5 M. Resist., 44(1070) 31314. 6 J. A. Armour and J. A. Ilurkc, J. Ass. Of/ic. A mil. Clwin., 53 (1070) 761. 7 O. W. Her#, I*. L. Oiosndy and G. A. V. Rces% QuII. Environ. Cuuutm. TuxiciA., 7 (1972) 338. * A. V. Holden and K. Mumlen, J. Chrumniour., 44 <1%9) 4*1. 9 L. M. Reynolds, Bull. Etifiivn. Contain. Toxicol., 4 (I960) 128.
10 L. M. Reynolds, Residue Rev., 34 (1971) 27. ] i Methotifor Polychlorinated lliphenris (PCtt's) in Industrial Effluents, U.S. Environmental Protec
tion Agency, National Environmental Research Center, Analytical Quulity Control Laboratory, Cincinnati, Ohio, 1973,
HONS 002719