Document npGx2RVpa0rZdJ5EMQjeZmwgm
Union Carbide Agricultural Products Company, Inc.
Institute Plant
INDUSTRIAL HYGIENE SAMPLING RESULTS
TO: Mr. P- J. Morris COPIES TO:
Hr. M. Adkins, Jr.
Building 23________________________
Mr. C. R. Thomas
Institute Plant___________________
Mr. L. W. Youngblood
Purpose: ________ Quarterly ________ Semiannually ________ Annually
________ Regulatory Agency Inspection
x Other (See Comments)
Sample Date(s): December 19, 1985
Sample Location: MIC-II Unit - Malnt. Comp. 7 Department No.: 327
Process/Activity: Pipe insulation removal
Contaminant: Asbestos_______
Exposure Limit: OSHA 2 fibers/cc____________ ACGIH
UCC
Sample Type:
x Personal
x Area
______ Source
Surface Wipe
______ Other (See comments)
Analytical Method:
NIOSH 7400
Results: ______ See Comments
x See Attached Table
COMMENTS: A Maintenance Complex 7 insulator/painter was monitored for
exposure to airborne asbestos fibers on the above date. Area concentrations
of airborne asbestos fibers were measured too. Monitoring was performed while
insulation was being stripped from pipes that were lying on a plastic sheet
inside the dike wall that surrounds the old phthalic anhydride tanks at the
MIC-II Unit. It was not necessary to wet the insulation as it was being
removed because it had become water logged and, at the time of removal, was
frozen due to the cold weather. Nevertheless, respirators and protective
clothing were worn by the three men performing the work.
Since the airborne fiber concentration was unknown at the time of
sampling, two sets of samples (having different sample times) were taken to
insure that at least one of the sets would produce valid results. All
monitoring results were below the lower calibration limit for the analytical
UCC 009007
A04022
Union Carbide Agricultural Products Company, Inc.
Institute Plant
IMDUSTR IAL HYGIENE SAMPLING RESULTS- CONTINUED
method, which is well below the OSHA permissible exposure limit. Area
concentrations and personal exposures to airborne asbestos fibers were
maintained at safe levels during this lob.______________________________________
RECOMMENDATIONS: None___________________________________________ _____________________
Report Date:
January 14, 1986
Signed NOTE:
Bldg. 2
Room: 172 Phone
ALL PERSONAL SAMPLE RESULTS MUST BE DISCUSSED
WITH THE PARTICIPATING EMPLOYEE
6105
1335k
UCC 009008
Union carbide Agricultural Products Company, Inc.
Institute Plant
INDUSTRIAL HYGIENE SAMPLING RESULTS
WORKPLACE LOCATION: MIC-II Unit, Maint. Comp. 7 SAMPLER'S NAME: E. A. Osby
CONTAMINANT: Asbestos____________________
REPORT DATE: January 14, 1986
Sample Number
Sample Date
W-4409-1 V-4409-4
12-19-85 12-19-85
W-4409-2 V-4409-5
V-4409-3 V-4409-6
12-19-85 12-19-85
12-19-85 12-19-85
Sample Description
INSULATOR/PAINTER D. C. Chambers D. C. Chambers
Sample Time (min.)
60 18
East side of insulation removal site - 3 feet from activity.
60 16
Northwest side of insulation removal site - 5 feet from activity.
60 15
Sample Results fibers/cc)
< 0. < 0.
TWA=< 0.
< 0. < 0.
< 0. < 0.
1335k
UCC 009009
A U402'i
ENVIRONMENTAL HEALTH LABORATORY
1021 Georgia Ave. / Macon, Georgia 31201 {800) 841-8919 / in GA (912) 745-4702
LABORATORIES IN MACON, GA. AND HARTFORD, CT.
LABORATORY ANALYSIS REPORT
W
To: Account: Location:
E. A. Osby
Union Carbide Agricultural Products Co., Inc.
P. 0. Box 2831 Charleston, WV 25301
Report No.: Purchase Order No.:
Date Received: Date Reported:
86A0007 Revised N/A
01-03-86
01-14-86
Analysis: Fiber Count Analytical Method: NI0SH 7400; Phase Contrast Microscopy;
Walton-Beckett Reticle; 450 x magnification
Sample No (AA)
Air Volume (Liters)
Fibers, longer than 5 microns, per cc of air.
W-4409-1
120
<0.095
W-4409-2
120
<0.095
W-4409-3
120
<0.095
W-4409--4
36 <0.32
W-4409-5
32 <0.36
W-4409-6
29.8
<0.38
cc= Cubic Centimeter.
A blank filter was not provided. We recommend that a blank be submitted with each set of samples so that the sampling media can be checked for possible interferences or background contamination.
Chemist <( = Less than.
Jeanne A. Gibbs
AU402b
Date:.
UCC 009010