Boilers and Furnaces
InTERn/mon/iL He/iter Coop/my
Makers of Heating Apparatus
Utica, N. Y.
NEW YORK Brotdwa; and 57tb St.
CHICACO 19}3>3S Wentworth Are.
CLEVELAND 1441 Davenport Are., N. E.
DETROIT
NASHAU.N.H.
3952 Cass Are. 110 Chestnut St.
jjfCOJVOMY fiOIUZl&S
On the following pages we present condensed data on the INTERNATIONAL Economy Sectional Boilers, Steam and Water.
Both the Regular and the Smokeless types have the following distinctive features in common: Conservative ratings from actual tests according to the American Society of Heating and Ventilating Engineers Code the evaporative power and efficiency are exceptionally high; a long fire travel and all heating surface below the water line; a low steady water line with water gauge tapped directly into the section; dry steam guaranteed without a header and only one main outlet from boiler; grate bar connections of sectional boilers are outside the ashpit; all heating surface easily cleaned from front of boiler through large flue doors.
The temperature of the gases in the first pass or lower flues is at least 200 degrees higher than in the fire box for an hour or two after firing due to the special mixing or carburetor feature of all Regular type boilers. In the secondary combustion chamber of the Smokeless type, the temperature at times exceeds 2000 deg. fahr. which means high efficiency due to proper combustion conditions as regards, time, temperature, and mixture.
The INTERNATIONAL Economy Smokeless Boiler is an up draft boiler designed for the smokeless combustion of any bituminous fuels commonly used for heating purposes. It is built on the Kent Wing Wall principle in which the rear portion of the boiler contains a mixing chamber and a secondary combustion chamber, separated by a brick wing wall; so that the smokeless feature is entirely outside of the firebox.
This type of boiler is very simple to control and does not require the services of a skilled or expert fireman.
Cul-Away View of No. 140-4? Economy Smokeless Boiler 306
International Heater Company
Boilers and Furnaces
InTERn/rrionAL He/tter Cocop/my
SECTIONAL MEASUREMENTS Smokeless Steam Sizes
l
47 in. Series Economy Smokeless Boiler Showing Access for Cleaning
Number
'Rating
*
Ratings and Dimensions ECONOMY SMOKELESS BOILERS
Steam Pattern
tTappings Supply and Return
Minimum Chimney Dimensions
Size Flue Inches
Height Feet
Size of Grate Inches
Additional Area of Side Grate Fingers
Sq. In.
80-22 90-22 100-22
80-28 90-28 100-28
90-34 100-34 110-34 120-34 130-34 140-34 150-34
90-47 100-47 . 110-47 120-47 130-47 140-47 150-47 160-47 170-47 160-47 190-47 200-47 210-47
1700 2000 2300
2450
2800 3150
4000
4500 5000 5500 6000 6500 7000
.
8300 9300
10300 11300 12300
13300 14300 15300 16309
17300 18300 19300
20300
i-y/i' 3-3'/;' 3-3</2*
3-4" 3-4 T 3-4T .
3-5* 3-5* 3-5* 3-5' 3-5* 3-5* 3-5*
3-6" 3-6* 3-6* 4-6* 4-6* 4-6* 4-6* 4-6* 4-6* 4-6* 4-6* 4-6* 4-6*
2-3i/2* 2-3'// 2-3'/?
2-4* 2-4' ' 2-4* .
2-5* 2-5* 2-5*
2-5* 2-5* .2-5* 2-5*
2-6*. 2-6* 2-6* 2-6* 2-6* 2-6* 2-6* 2-6* 2-6* 2-6* 2-6* 2-6* 2-6*
.
12x12 12x12 12x16
16x16 16x16 16x16
16x16 16x20 20x20 ' 20x20 : 20x20 20x24 ` 20x24
24x24 24x24 24x24 24x26 24x28 24x28 28x28 28x28 28x32 28x32 28x32 32x32 32x32
40 45 50
40 45 50
50 '
so
55 55 60 60 60
60 65 70 . 70 75 75 89 85 99 95 100 105
no
22x32 22x40 22x48
28x32 28x40 . 28x46
34x40 34x48 34x56 34x64 34x64 34x64 34*72
47x50 47x60 47x60 47x60 47x70 47*70 47x70 47x70 47x70 47x80 47x80 47x80 47x80
380 432 484
432 484 536
529 580 632 684 684 664 736
677 742 742 742 607 807 807 807 807 872 872 872 872
`Judgment should be used in fitting the boiler to a job. As an example: Do not attach a short boiler to a relatively highstack, or a long boiler to a relatively low stack. Suit the boiler to the job. .
tThe Economy line of boilers does not require a header. Plug and bush tappings to size of mains.
307