1945 Guide
Table 8.. Approximate Gravity and Calorific Value of ' Standard Grades of Fuel Oil
Commercial Standard No.
_
Approximate Gratitt Ranob A. P. L
>.
Calorific Value Btu'Pbr Gallon
1
i
38-40
. 136,000
2
34-36
138,500
3
28-32
141,000
5
18-22
148,500
6
14-16
152,000'
needed., The combustion must take place in a space that maintains the temperatures high so the reaction will be completed.
CLASSIFICATION OF GAS
Gas is' broadly classified as being either natural or manufactured. Natural gas; is a mechanical mixture of several combustible arid inert, gases- rather than a chemical compound. Manufactured gas as dis tributed is usually a combination of certain proportions of gases produced by two or more processes. Representative properties of gaseous fuels commonly used in domestic heating are presented in Table 9.
Natural gas is the richest of the gases and contains from 80 to 95 per cent methane, with small percentages of the other combustible hydrocarbons. In addition, it contains from 0.5 to 5.0 per cent of COt, and from 1 to 12 or 14 per cent of nitrogen. The heat value varies from 1000 to 1200 Btu per cubic foot, the majority of natural gases averaging about 1000 Btu per cubic foot. Table 9 shows typical values for the four main oil fields, although values from any one field vary materially.
Table 9 also gives the calorific values of the more common types of manufactured gas. Most states have legislation which controls the distri bution of gas and fixes a minimum limit to its heat content. The gross or higher calorific value usually ranges between 520 and 545 Btu pier cubic foot, with an average of 535. A given heat value may be maintained and yet leave considerable latitude in the composition of the gas so that as distributed the composition is not necessarily the same in different dis-. tricts, nor at successive times in the same district. However, in any community the variations in gas composition are held within suitable limits so that the performance of approved gas appliances will not be adversely affected.
COMBUSTION OF GAS
The majority of gas burners utilized in central domestic heating plants are of the Bunsen type and operate with a non-luminous flame. In this type of burner part of the air required for combustion is mixed.with the gas as primary air,.the air arid gas mixture being fed to the burner ports. Additional secondary air is introduced around the flame by draft inspi ration. In the luminous flame burner, which is sometimes used, all of the air for combustion is brought in contact with the flame as secondary air. This secondary air should be brought into intimate contact with the gas.
Some makes of burners use radiants or refractories to convert some of the energy in the gas to radiant heat. The radiants also serve as baffles in directing the flow of the products of combustion..
The quantity of air given in Table 9 is that required for theoretical combustion, but with a properly designed and installed burner the excess
Combustion and Fuels
Table 9. Representative Properties of Gaseous Fuels, Based on Gas at 60 F and 30 in. Hg.
171
Gas
Btu per Cu Ft
High
Low
(Grose) (Net)
Specific Gravttt,
Air = 1.00
Am ILmuuvfco
for Combus tion,
(CuFt)
Products of Combustion
Cubic Feet .Total
CO* T*0 'with Nt
Ulti mate
CO* Dry Basis
Theoretical' Flame Tem
perature, (dbq F)
Natural gas--
California
1200 1085 0.67 11.26"
1.24 2.24 12.4 12.2 3610
Natural gas-- Mid-Conti nental
970 . 870 0.57
9.17
0.97 1.92 10.2 11.7 3580
Natural gas--
Ohio
1130 1025 0.65 10.70
1.17 2.16 11.8 12:1 3600
Natural gas-- Pennsylvania 1130 1025. 0.71 11.70 . 1.30 2.29 12.9 12.3 3620 '
Retort coal gas 570 510 0.42 5.00 0.50 1.21 5.7 11.2 3665
Coke oven gas 590 520 0.42 5.19 0.51 1.25 5.9 11.0 3660
Carbureted water gas
540 495 0.65 4.37 0.74 0.75 5.0 17.2 3815
Blue water gas 300 280 0.53 2.26 0.46 :0.51 2.8 22.3 3800
Anthracite pro
ducer gas
135 125 0.85
1.05
0.33 0.19 1.9 19.0 3000
Bituminous producer gas
Oil gas
150 140 0.86 575 510 0.35
1.24 4.91
0.35 0.19 0.47 1.21
2.0 19.0 5.6 10.7
3160 3725
air can be kept low. In order to insure freedom from carbon monoxide under conditions which may obtain in installations, it is customary to design gas burning appliances for a supply of 30 to 35 per cent of excess air. In individual installations in which flue gas analyses are made, the excess air is sometimes reduced to-approximately 20 per cent. The division of the air into primary and secondary is a matter of burner design, the pressure of gas available, and the type of flame desired.
The air gas ratio has a decided effect upon flame propagation. It is necessary that the gas will flow out of the burner ports fast enough so.that the flmne cannot travel back into the burner head, i.e. flash back, but the velocity must not be so high that it blows the flame away from the port.
The maximum and minimum flow speeds from burner ports which may be permitted are known to be very close together when air-gas.mixtures in theoretical proportions are being supplied to the burner. As the air-gas ra|-l is lowered, and the mixture becomes more gas rich, the limiting speeds become farther apart, until with 100 per cent gas, in ap all-yellow name, flash back cannot occur and a much higher velocity is needed to blow off the flamesi
SOOT
T]?e deposit of soot on the flue surfaces of a boiler or heater.acts as an insulating layer oVer the surface and reduces the heat transmission to the