Document nm16gLaNdeq4zNDoVprL7Z7Nw
764
CHAPTER 41
1948 Guide
HEAT LOSSES FROM DUCTS
The thermal transmittance U for ducts can be found as follows:
For uninsulated metal duct, V = J_+_L Si + So
For uninsulated non-metallic ducts, V =
h where U, Si, Jo, * and k are as defined on page 769.
k + /,,
(8)
(9)
Where x is small and k is large, however, this factor -Xy is of little im
portance and may be neglected.
Film conductance f\ for air flowing in ducts apparently depends only on the velocity of the air and the diameter of the duct. A fairly reliable inside coefficient can be calculated from Schultz's modified equation :
h = jy>jt
*(10')
Air DuctDesif'n
765
Table 7. Weights of Sheet Metal Used for Duct Construction
.:
Black Sheets
Galvanized Sheets
u. s. Std.
Gage
'.30
28 26
24 22
20
18
16 14
12
11 10
.
Approximate Thickness, In.
Steel
0.0123 0.0153 0.0184 0.0245 0.0306 0.0368 .0.0490 0.0613 0.0766 0.1072 0.1225 0.1379
Iron
0.0125 0.0156 0.0188 0.0250 0.0313 0.0375 0.0500 0.0625 0.0781 0.1094 0.1250 0.1406
'Weight Per Square Foot ,
Ounces
8 10 12 16 20 24 32 40 50 70 80 90
Pounds
0.500 0.625 0.750 1.000 1.250 1.500 2.000 2.500 3.125 4.375 5.000 5.625
Approximate Thickness. In.
Steel
0.0163 0.0193 0.0224 0.0285 0.0346 0.0408 0.0530 0.0653 0.0806 0.1112 0.1265 0.1419
Iron
0.0165 0.0196 0.0228 0.0290 0.0353 0.0415 0.0540 0.0665 0.0821 . 0.1134 0.1290 0.1446
Weight Per Square Foot
Ounces
10.5 12.5 14.5 18.5 22.5 26.5 34.5 42.5 52.5 72.5 82.5 92.5
Pounds
0.656 0.781 , 0.906 1.156 1.406 1.656 2.156 2.656 .3.281 4.531 5.156 5.781
Galvanized sheets axe gaged before galvanizing and are therefore approximately 0.004 in. thicker.
'where
Va = velocity of air in duct, feet per second.
D = inside diameter of duct, feet.
Film conductance /0 depends on a number of variables including tem perature, diameter,- and emissivity of the outer surface and can be calcu lated from data in Chapter 5. From this explanation, it is seen that it is .. unwise to recommend a given value of U for all uninsulated metal ducts.
The heat loss from a given length of duct can be expressed by:
. Q = UPI [
- t. ]
(ID
The heat given up by the air in the duct is:
Q = 0.24 W (fi - h) = 14.4 AVrafr, (/, - h)
(12)
Equating (11) and (12):
/i tt -- 2/j 28.8 A Vm py
h - it =
UPl
_Let y = 2--8-.-8--jAjpVpm ~ cfor recAtangular duct,s, -and,7--.-2--D- ^Vm--&--, (for round,
Table 8. Weights and Thicknesses of Standard Copper Sheets3 Rolled to Weight
Weight per Square Foot
Ounces
10 12 14 16 18 20 24 28 32 36 40
48
64
Pounds
0.625 0.750 0.875 1.000 1.125 1.250 1.500 1.750 2.000 2.250 2.500 2.750 3.000 3.500 4.000
Thickness, Inches
Equivalent
0.0135 0.0162 0.0189 0.0216 0.0243 0.0270 0.0324 0.0378 0.0432 0.0486 0.0540 0.0594 0.0648 0.0756 0.0864
Nearest ' Fraction
'4> Ut *44
XA& lA XA A % *4
'A '& A %
Nearest Gage No.
B. & S.
27 26 25 23 22 21 20 19 17 16 15 15 14 13 11
Stubs
29 27 26 24 23 22 21 20 19 18 17 17 16 15 14
U. S. Std.
29 28 26 25 24 23 22 20 19 18 17 17 16 ' 14 13
Variations from these weights must be expected in practice.