Document nm14xNpYOEGYxNp4mQMv3oKEa
r" ' 11 v/!
INTERNAL CORRESPONDENCE
CHEiVilCALS AND PLASTICS P. O. BOX 8361, SOUTH CHARLESTON, WEST VIRGINIA 25303
To (Name) Division Location
Copy to
Mr. J. W. Biddle Mr. C. W. Carman Mr. G. F. Hurley/ Mr. L. R. Noblev Mr. D. Paugh Mr. C. E. Richardson
Dal- June 2, 1977
O'S "Ccg Dec. IH/EP
^b,ect
Asbestos Insulation
INTRODUCTION
We were notified that asbestos insulation would be stripped from the dust collector on #2 boiler at the Institute Plant.
DISCUSSION
The area around the dust collector was isolated by ropes and warning signs were visable. Water was used to help control dust. The 3M disposable dust mask was used by all employees in the controlled area.
Air samples were taken to evaluate levels of asbestos dust in the air.
RESULTS
DATE
NAME
5/26/77 --
5/26/77 --
5/26/77 Day
TIME
AREA
CONCENTRATION FIBERS/CC
0845-0900 Area Sample1''"' 5 * Upwind, ^"6' High
.05
0902-1035 Area Sample^5* Downwind, 6 * High
.63
0935-1035
Personal Sample Scaffold-Stripping Insulation
2.44
UCC 016679
2 6/2/77
DATE
NAME
5/26/77 Hall
5/26/77
TIME
AREA
CONCENTRATION FIBERS/CC
0935-1035
Personal Sample Scaffold-Stripping Insulation
1.78
1040-1102 Area Sample^SO* Upwind 3' High
.06
CONCLUSIONS
One sample exceeded the Threshold Limit Value of two fibers/cc by a small amount. In some areas the employees were lax in us ing water to wet the insulation. Better control could have been achieved if more water was applied.
Several of the employees were not wearing the respiratory protection properly. In the use of the 3M mask, a proper face seal is essential. Both straps of the mask must be used and they must be properly positioned on the back of the head. The principles of the masks use covered in the training sessions must be applied in the field to assure adequate protection.
METHOD
Samples were counted in accordance with the NIOSH Method for Sampling Evaluation of Airborne Asbestos Dust.
Please contact us if we can provide any additional assistance.
JPG/mar
UCC 016680