266 CHAPTER 12 '1950 Guide -Cooling Load 267' decrease in amplitude in going through a wall with constant conditions maintained in the indoor space. By a shift in phase is meant that as the cyclic temperature wave passes through the wall, the time of occurrence of the maximum temperature at any point shifts farther and farther behind the time of the outer-surface maximum for successive positions through the wall. The resultant time lag between the outer-surface and inner-surface maximum temperatures is important, for it may be the determining factor in fixing the time of the maximum cooling load. By a decrease in amplitude is meant that as the cyclic temperature wave passes through the wall, the difference between the maximum temperature of a cycle and the mean temperature of the cycle, which is the amplitude of the wave by definition, decreases progressively as the wave passes through the wall. The magnitude pf the temperature amplitude at the inner wall surface is necessary for the determination of the instantaneous rate of heat transfer to the indoor space. ' t = unit convective conductance (film coefficient of heat transfer) of outdoor air for summer conditions of approximately 7.5 mph wind velocity, Btu per (hour) (square foot) (Fahrenheit degree). The time at which the maximum occurs in the rate of heat entry into the outside surface of walls or roofs is taken as the time at which the peak point occurs in the sol-air temperature cycle (mean sun time is used in the sol-air cycles). The corresponding maximum rate of heat entry follows from Equation 6 with t* being the maximum temperature of the sol-air cycle. The time of maximum heat gain to the room is obtained by adding the time lag to the time of maximum sol-air temperature (from Tables 10 or 11) for the particular wall or roof. The magnitude of the second term in Equation 6 relative to the first term indicates the relative portion of the structural heat in-flow assignable Table 12. Peeiodic Heat Flow Data for Homogeneous Walls ob Roofs Practical design data for periodic heat flow comprise a means of deter mining the time lag and amplitude decrement for different wall construc tions, and any given outdoor cycle of sol-air temperature. Both analytical and experimental studies have been made on this problem.7 While the analytical solution has been written, it .is far too detailed for direct use in rapid practical work; and the extensive numerical work required to estab lish a basis for simplified calculations, has been only partially completed. The method reported by Mackey and Wright7 will be adopted as the basis for the design procedure recommended here. Homogeneous Walls or Roofs, Constant Indoor Temperature For walls or roofs of a single, homogeneous material, the instantaneous rate of heat gain within an enclosure where the indoor air temperature is held constant is, approximately, -- = V (im -- (i) + X/ (t.* -- O Btu per (hour) (square foot) (6) Material Stone Solid Concrete Common Brick Face Brick Over-all Thick Coefficient, ness, Btu per (hr) In. (sq FT) CF) U Thermal Resistance of Solid Material, (HR) (SQ FT) (F)/Btu T Time Lag, Hr 8 0.67 . 0.64 5.5 12 0.55 0.96 8.0 16 0.47 1.28 10.5 24 0.36 1.92 15.5 2 0.98' 4 0.84 6 0.74 8 0.66 12 0.54 16 0.46 0.17 0.33 0.50 0.67 1.00 1.33 ' 1.1 2.5 3.8 5.1 7.8 10.2 4 0.60 8 0.41 12 0.31 16 0.25 0.80 1.60 2.40 3.20 2.3 5.5 8.5 12.0 4 0.77 0.44 2.4 Factor, in Equation 6 Horizontal and North East South West 0.51 0.28 0.17 0.06 0.93 0.79 0.61 0.49 0.29 0.17 0.S3 0.51 0.26 0.13 0.81 0.36 0.19 0.10 0.03 0.87 0.68 0.46 0.33 0.17 0.09 0.75 0.39 0.17 0.08 0.70 0.48 0.26 0.15 0.05 0.92 0.76 0.58 0.46 0.26 0.15 0.81 0.49 0.25 0.12 0.78 0.42 0.22 0.13 0.04 0.89 0.72 0.51 . 0.39 0.22 0.12 0.78 0.44 0.21 0.10 0.74 where ta X 24-hr average sol-air temperature for the particular value of Fahren- heit degrees. JO amplitude decrement factor, a variable that depends upon the thickness, material, and orientation of the wall or roof; see Table 12 for values. The amplitude decrement factor X as used in this chapter is equivalent to (T) as defined by Mackey and Wright! and also used by. Stew art.11 , Wood .. K 0.68 l 0.48 2 0.30 0.42 l 0.26 2 0.14 4 0.08 6 0.05 0.62 1.25 2.50 1.51 3.03 6.05 12.1 18.2 0.17 0.45 1.3 0.08 0.23 0.77 2.7 5.0 1.0 1.0 0.98 1.0 1.0 1.0 0.83 0.64 1.0 0.99 0.91' 1.0 1.0 1.0 0.74 0.49 1.0 0.99 0.96 1.0 1.0 1.0 0.81 0.61 1.0 0.99 0.94 1.0 1.0 1.0 0.76 0.55 * Based upon an outdoor combined film coefficient of 4.0 and an indoor combined film coefficient of heat transfer of 1.65 Btu per (hour) (square foot) (Fahrenheit degree). <.*1 sol-air temperature at a time earlier than the time for which the heat gain is being found by an amount that is equal to the time lag of the wall or roof, Fahrenheit degrees; see Table 12 for values of time lag. to periodic heat flow. The periodic term is continually passing through a cyclic variation from zero to a positive maximum, to zero, to a negative U overall coefficient of heat transfer of the wall or roof, Btu per (hour) maximum, to. zero again and so on over each 24 hour cycle. Surfaces with (square foot) (Fahrenheit degree). different exposures pass through these cycles with maximum points at dif u= 1 1L 1 1 L /ti +/t+*t 1r.6r6K +4: +kr L = thickness of building material, feet. L osse+k r ferent times of. day. An example in the use of Tables 10,11, and 12 follows; Example S. Find the instantaneous design rate of heat gain through an 8-in. west wall of common brick (6 = 0.7,/0 = 4) located in New York, N. Y., at 9:30 p.m. sun time, when the temperature of the indoor air is constant at 80 F.. k -- thermal conductivity of building material, Btu per (hour) (square foot) (Fahrenheit degree per foot). fi = unit convective conductance (film coefficient of heat transfer) of in door air, Btu per (hour) (square foot) (Fahrenheit degree). From Table 12, U = 0.41, the time lag is 5.5 hr, and X = 0;44. By linear interpolation on the basis of the value of 6//, in Table 10, - = 84.8 + ^ (96.5 - 84.8) = 93 F .