American Society of Heating and Ventilating Engineers
/Rui
Wall line.
...A.
^SwSiwngi"n^a^H
S' joint vj
...Radiator
- Runout below floor PLAN
Fig. 12. Top and Bottom Radiator Connections from Up- or Down-Febd-Risers; (Not-to-Exceed 8 "to lo
Sections.)
Note.--Suitable for up-feed or down-feed at mospheric, vapor, vacuum, sub-atmospheric, and oprreifficeerabsyles.tems. Opposite end connectioas always
''Runout below floor
ELEVATION
Fig. 9. Typical One-Pjpe Radiator Connections (Up-Feed or Down-Feed)
Fig. 10. Connections to Steam-Type Radiator for Two-Pipe Gravity System, Up-Feed or Down-Feed
Note.--Steam-type radiators should not be used on any except gravity one-pipe and gravity twopipe systems.
Fig. 13. Top and. Bottom Opposite End Radiator Connections with Heel of Down-Feed Riser Dripped into Dry Return
Note.--Suitable for down-feed only. For at mospheric, vapor, vacuum, sub-atmospheric, and orifice systems:------
Fig. 11. Top and Bottom Opposite End Radiator Connections from Up or Down-Feed Risers
Note.--Suitable for up-feed or down-feed atmospheric. vapor, vacuum, sub-atmospheric and orifice systems.
Fig. 14. Connections to Radiator Hung on Wall
Note.- For up-feed with radiators below level oj steam main. For atmospheric and vapor systems. Not suitable for vacuum, sub-atmospheric, or orihce systems.
548
Chapter 32--Piping for Steam Heating Systems
merit are located below the level of the steam main, the drop to the ^iFator is dripped into the wet return and an air line is used to vent the
t\rn radiator connection into an overhead return line, as illustrated in Ir 14. When the radiator stands on the floor below the main, the drip
-ihe steam branch down to the radiator may be omitted if an overhead ^fve as shown in Fig. 15, is used. This method is also suitable for acuum, sub-atmospheric, and orifice systems.
Convector Connections
Convectors often are installed without control valves, a damper being used to shut off the flow of air to retard the heat transfer from the con vector even though it is still supplied with steam. The piping connec tions for a convector with the inlet and outlet at the same end are shown in Fig. 16. There is no valve on the steam side but there is a thermostatic trap on the return. The damper for control is shown immediately above the convector. This piping is suitable for atmospheric, vapor, vacuum, sub-atmospheric, and orifice systems of the up-feed type. A similar unit with connections on opposite ends and suitable for the same systems is shown in Fig. 17. This unit has no damper but requires a valve on the steam connection for control. When valves must.be located so as to be accessible from the supply air grille, the arrangement usually takes the form indicated in Fig. 18. Convectors with damper control, installed in cabinets or under window sills, usually are connected as shown in Fig. 19. A convector located in the basement and supplying air to a room on the floor above may be piped as pictured in Fig. 20 for all systems except gravity one-pipe or two-pipe systems.
Vapor systems with heating units in the basement where the returns are wet would be treated as in Fig. 21. Similar heating units where a dry return is available would be connected ais shown in Fig. 22. If the dryreturn were on a vacuum, atmospheric, sub-atmospheric or orifice system, the treatment would be identical.
Pipe Coil Connections
Pipe coils, unless coupled in a correct manner, often give trouble from
short circuiting and poor circulation. The method of connecting shown
in Fig. 23 is suitable for atmospheric, vapor, vacuum, sub-atmospheric,
and orifice systems.
9
Indirect Air Heater Connections
Heating units for central fan systems have simple connections on the steam side. The steam main is carried into the fan room and has a single branch tapped off for each row of heating units.- Each of these iriain branches is split into as many connections as need bejnade to each row, governed by the number of stacks and the width of the stacks. Each stack must have at least one steam connection, and wide stacks are more evenly heated with two steam connections, one at each end.
The piping shown in Fig. 24 is for small stacks and has the steam con nected at only one end. On the return side all of the returns are collected together through check valves and are passed through blast traps which are connected to the vacuum return or to an atmospheric return. The air
549